<?xml version="1.0" encoding="UTF-8"?>
<!DOCTYPE article PUBLIC "-//NLM//DTD Journal Publishing DTD v2.3 20070202//EN" "journalpublishing.dtd">
<article article-type="review-article" dtd-version="2.3" xml:lang="EN" xmlns:mml="http://www.w3.org/1998/Math/MathML" xmlns:xlink="http://www.w3.org/1999/xlink">
<front>
<journal-meta>
<journal-id journal-id-type="publisher-id">Front. Energy Res.</journal-id>
<journal-title>Frontiers in Energy Research</journal-title>
<abbrev-journal-title abbrev-type="pubmed">Front. Energy Res.</abbrev-journal-title>
<issn pub-type="epub">2296-598X</issn>
<publisher>
<publisher-name>Frontiers Media S.A.</publisher-name>
</publisher>
</journal-meta>
<article-meta>
<article-id pub-id-type="publisher-id">1114230</article-id>
<article-id pub-id-type="doi">10.3389/fenrg.2023.1114230</article-id>
<article-categories>
<subj-group subj-group-type="heading">
<subject>Energy Research</subject>
<subj-group>
<subject>Review</subject>
</subj-group>
</subj-group>
</article-categories>
<title-group>
<article-title>Application of signal processing techniques and intelligent classifiers for high-impedance fault detection in ensuring the reliable operation of power distribution systems</article-title>
<alt-title alt-title-type="left-running-head">Varghese P et al.</alt-title>
<alt-title alt-title-type="right-running-head">
<ext-link ext-link-type="uri" xlink:href="https://doi.org/10.3389/fenrg.2023.1114230">10.3389/fenrg.2023.1114230</ext-link>
</alt-title>
</title-group>
<contrib-group>
<contrib contrib-type="author">
<name>
<surname>Varghese P</surname>
<given-names>Rini</given-names>
</name>
<xref ref-type="aff" rid="aff1">
<sup>1</sup>
</xref>
<uri xlink:href="https://loop.frontiersin.org/people/2164413/overview"/>
</contrib>
<contrib contrib-type="author" corresp="yes">
<name>
<surname>Subathra</surname>
<given-names>M. S. P.</given-names>
</name>
<xref ref-type="aff" rid="aff2">
<sup>2</sup>
</xref>
<xref ref-type="corresp" rid="c001">&#x2a;</xref>
<uri xlink:href="https://loop.frontiersin.org/people/1477891/overview"/>
</contrib>
<contrib contrib-type="author">
<name>
<surname>George</surname>
<given-names>S. Thomas</given-names>
</name>
<xref ref-type="aff" rid="aff3">
<sup>3</sup>
</xref>
<uri xlink:href="https://loop.frontiersin.org/people/1882328/overview"/>
</contrib>
<contrib contrib-type="author" corresp="yes">
<name>
<surname>Kumar</surname>
<given-names>Nallapaneni Manoj</given-names>
</name>
<xref ref-type="aff" rid="aff4">
<sup>4</sup>
</xref>
<xref ref-type="aff" rid="aff5">
<sup>5</sup>
</xref>
<xref ref-type="aff" rid="aff6">
<sup>6</sup>
</xref>
<xref ref-type="corresp" rid="c001">&#x2a;</xref>
<uri xlink:href="https://loop.frontiersin.org/people/1031506/overview"/>
</contrib>
<contrib contrib-type="author">
<name>
<surname>Suviseshamuthu</surname>
<given-names>Easter Selvan</given-names>
</name>
<xref ref-type="aff" rid="aff7">
<sup>7</sup>
</xref>
<uri xlink:href="https://loop.frontiersin.org/people/1277565/overview"/>
</contrib>
<contrib contrib-type="author" corresp="yes">
<name>
<surname>Deb</surname>
<given-names>Sanchari</given-names>
</name>
<xref ref-type="aff" rid="aff8">
<sup>8</sup>
</xref>
<xref ref-type="corresp" rid="c001">&#x2a;</xref>
</contrib>
</contrib-group>
<aff id="aff1">
<sup>1</sup>
<institution>Department of Electrical and Electronics Engineering</institution>, <institution>School of Engineering and Technology</institution>, <institution>Karunya Institute of Technology and Sciences</institution>, <addr-line>Coimbatore</addr-line>, <addr-line>Tamil Nadu</addr-line>, <country>India</country>
</aff>
<aff id="aff2">
<sup>2</sup>
<institution>Department of Robotics Engineering</institution>, <institution>School of Engineering and Technology</institution>, <institution>Karunya Institute of Technology and Sciences</institution>, <addr-line>Coimbatore</addr-line>, <addr-line>Tamil Nadu</addr-line>, <country>India</country>
</aff>
<aff id="aff3">
<sup>3</sup>
<institution>Department of Biomedical Engineering</institution>, <institution>School of Engineering and Technology</institution>, <institution>Karunya Institute of Technology and Sciences</institution>, <addr-line>Coimbatore</addr-line>, <addr-line>Tamil Nadu</addr-line>, <country>India</country>
</aff>
<aff id="aff4">
<sup>4</sup>
<institution>School of Energy and Environment</institution>, <institution>City University of Hong Kong</institution>, <addr-line>Kowloon</addr-line>, <country>Hong Kong SAR, China</country>
</aff>
<aff id="aff5">
<sup>5</sup>
<institution>Department of Electrical Engineering</institution>, <institution>Graphic Era (Deemed to be University)</institution>, <addr-line>Dehradun</addr-line>, <addr-line>Uttarakhand</addr-line>, <country>India</country>
</aff>
<aff id="aff6">
<sup>6</sup>
<institution>Center for Research and Innovation in Science</institution>, <institution>Technology</institution>, <institution>Engineering</institution>, <institution>Arts</institution>, <institution>and Mathematics (STEAM) Education</institution>, <institution>HICCER&#x2014;Hariterde International Council of Circular Economy Research</institution>, <addr-line>Palakkad</addr-line>, <addr-line>Kerala</addr-line>, <country>India</country>
</aff>
<aff id="aff7">
<sup>7</sup>
<institution>Center for Mobility and Rehabilitation Engineering Research</institution>, <institution>Kessler Foundation</institution>, <addr-line>West Orange</addr-line>, <addr-line>NJ</addr-line>, <country>United States</country>
</aff>
<aff id="aff8">
<sup>8</sup>
<institution>School of Engineering</institution>, <institution>University of Warwick</institution>, <addr-line>Coventry</addr-line>, <country>United Kingdom</country>
</aff>
<author-notes>
<fn fn-type="edited-by">
<p>
<bold>Edited by:</bold> <ext-link ext-link-type="uri" xlink:href="https://loop.frontiersin.org/people/1744378/overview">Jose Luis Dom&#xed;nguez-Garc&#xed;a</ext-link>, Energy Research Institute of Catalonia, Spain</p>
</fn>
<fn fn-type="edited-by">
<p>
<bold>Reviewed by:</bold> <ext-link ext-link-type="uri" xlink:href="https://loop.frontiersin.org/people/1762097/overview">Srikanth Goud B</ext-link>, Anurag Group of Institutions, India</p>
<p>
<ext-link ext-link-type="uri" xlink:href="https://loop.frontiersin.org/people/2136086/overview">Manohar Mishra</ext-link>, Siksha O Anusandhan University, India</p>
</fn>
<corresp id="c001">&#x2a;Correspondence: M. S. P. Subathra, <email>subathra@karunya.edu</email>; Nallapaneni Manoj Kumar, <email>mnallapan2-c@my.cityu.edu.hk</email>; Sanchari Deb, <email>sanchari.deb@warwick.ac.uk</email>
</corresp>
<fn fn-type="other">
<p>This article was submitted to Smart Grids, a section of the journal Frontiers in Energy Research</p>
</fn>
</author-notes>
<pub-date pub-type="epub">
<day>17</day>
<month>03</month>
<year>2023</year>
</pub-date>
<pub-date pub-type="collection">
<year>2023</year>
</pub-date>
<volume>11</volume>
<elocation-id>1114230</elocation-id>
<history>
<date date-type="received">
<day>02</day>
<month>12</month>
<year>2022</year>
</date>
<date date-type="accepted">
<day>23</day>
<month>02</month>
<year>2023</year>
</date>
</history>
<permissions>
<copyright-statement>Copyright &#xa9; 2023 Varghese P, Subathra, George, Kumar, Suviseshamuthu and Deb.</copyright-statement>
<copyright-year>2023</copyright-year>
<copyright-holder>Varghese P, Subathra, George, Kumar, Suviseshamuthu and Deb</copyright-holder>
<license xlink:href="http://creativecommons.org/licenses/by/4.0/">
<p>This is an open-access article distributed under the terms of the Creative Commons Attribution License (CC BY). The use, distribution or reproduction in other forums is permitted, provided the original author(s) and the copyright owner(s) are credited and that the original publication in this journal is cited, in accordance with accepted academic practice. No use, distribution or reproduction is permitted which does not comply with these terms.</p>
</license>
</permissions>
<abstract>
<p>High-impedance fault (HIF) is always a threat and the biggest challenge in the power transmission and distribution system (PTDS). For a PTDS to operate effectively, HIF diagnosis is essential. However, given the HIF&#x2019;s nature and the involved complexity, detection, identification, and fault location are difficult. This will be even more complicated in conventional PTDSs as they are inefficient and highly vulnerable. Given the importance and urgent need for HIF diagnosis in PTDS, this study reviews state-of-the-art HIF phenomenon and detection techniques and proposes the use of &#x201c;various signal processing techniques for fault feature extraction&#x201d; and &#x201c; different classifiers for identifying HIF.&#x201d; First, HIF current/voltage signals are analyzed using signal processing techniques, which include the discrete wavelet transform (DWT), pattern recognition, Kalman filtering, TT transform, mathematical morphology (MM), S transform (ST), fast Fourier transform (FFT), principal component analysis (PCA), linear discriminant analysis (LDA), and wavelet transforms, such as dual-tree, maximum overlap discrete wavelet transform (MODWT), and lifting wavelet transform (LWT). Second, the various HIF and non-HIF faults are classified using intelligent classifiers. The intelligent classifiers include artificial neural networks (ANNs), probabilistic neural networks (PNNs), genetic algorithms (GAs), fuzzy logic, adaptive neuro-fuzzy interface system, support vector machine (SVM), extreme learning machine (ELM), adaptive resonance theory, random forests (RFs), decision trees (DTs), and convolution neural networks (CNNs). In addition to the comparative discussion of various classifier techniques, their evaluation criterion and performance are prioritized. Third, this review also studied different test systems, such as radial distribution network, mesh distribution network, IEEE 4 node, IEEE 13 node feeder, IEEE 34 node feeder, IEEE 39 node feeder, IEEE 123 node feeder, Palash feeder, and test microgrid systems, to assess the pertinence of various HIF detection schemes and the behavior along with methods to locate the HIF. Overall, we believe this review would serve as a comprehensive compendium of advanced techniques for HIF diagnosis in different test systems.</p>
</abstract>
<kwd-group>
<kwd>high-impedance fault</kwd>
<kwd>power system protection</kwd>
<kwd>signal processing</kwd>
<kwd>artificial neural networks</kwd>
<kwd>feature extraction</kwd>
<kwd>HIF detection</kwd>
<kwd>intelligent classifier</kwd>
<kwd>electrical test systems</kwd>
</kwd-group>
</article-meta>
</front>
<body>
<sec id="s1">
<title>1 Introduction</title>
<p>Faults are often observed in electrical power transmission and distribution systems (PTDSs). The faults in a PTDS will distract the current from the intended path (<xref ref-type="bibr" rid="B6">Ali et al., 2014</xref>; <xref ref-type="bibr" rid="B104">Russell and Benner, 1995</xref>). The fault causes an irregular condition that decreases the strength of insulation between the conductors (<xref ref-type="bibr" rid="B104">Russell and Benner, 1995</xref>; <xref ref-type="bibr" rid="B142">Theron et al., 2018</xref>). There are numerous fault types, among which high-impedance faults (HIFs) are critical. HIF occurs when a conductor touches a tree with a high impedance or when a broken conductor touches the ground (<xref ref-type="bibr" rid="B32">Chen et al., 2013</xref>; <xref ref-type="bibr" rid="B7">Aljohani and Habiballah, 2020a</xref>). The HIF draws non-predictable currents from the distribution network, sometimes leading to arcing (<xref ref-type="bibr" rid="B32">Chen et al., 2013</xref>). This is visually represented and shown in <xref ref-type="fig" rid="F1">Figure 1</xref>. Such faults can impose fire risks and cause an electrical shock that endangers electrical system operators, engineers, live stocks, and individuals' lives (<xref ref-type="bibr" rid="B7">Aljohani and Habiballah, 2020a</xref>; <xref ref-type="bibr" rid="B136">Sultan et al., 1994</xref>). In industrial applications, HIF detection is inevitable to ensure the safety of working persons and equipment and continuity in the service for critical loads. Thus, HIF detection and diagnosis are vital to ensure safety and continuous PTDS operation. However, its detection is quite challenging because HIFs are often not recorded as faults; hence, the reported cases are fewer than the observed ones (<xref ref-type="bibr" rid="B6">Ali et al., 2014</xref>). As the fault current draws less current, it remains unnoticed and persists for days. Owing to small fault currents, HIFs are difficult to detect using traditional protection relays and should be addressed through algorithms. HIF depends on various factors, such as the ground surface type, humidity, type of conductor, environmental conditions, and voltage degree, of which surface humidity and surface materials are the most influenced (<xref ref-type="bibr" rid="B121">Sedighizadeh et al., 2010</xref>). Many HIFs have similar features that can be represented because of differences in the arc parameters, such as conductance and time constant (<xref ref-type="bibr" rid="B148">Vyshnavi and Prasad, 2018</xref>; <xref ref-type="bibr" rid="B33">Chen et al., 2016</xref>). Low impedance fault (LIF) (<xref ref-type="bibr" rid="B69">Kavaskar and Mohanty, 2019</xref>; <xref ref-type="bibr" rid="B67">Kannan and Rathinam, 2012</xref>) is short-circuiting, followed by a high current that is sensed by a breaker.</p>
<fig id="F1" position="float">
<label>FIGURE 1</label>
<caption>
<p>HIF in the downed conductor. <bold>(A)</bold> Arcing in the downed conductor. <bold>(B)</bold> Source end and load end conductors (<xref ref-type="bibr" rid="B102">Roberts et al., 2001</xref>; <xref ref-type="bibr" rid="B135">Suliman and Ghazal, 2019</xref>).</p>
</caption>
<graphic xlink:href="fenrg-11-1114230-g001.tif"/>
</fig>
<p>Arc type fault (HIF) usually occurs when a current-carrying conductor touches the ground or with another conductor through a high-impedance medium for a short time. HIF is a disturbance in a power system of approximately 15&#x2013;25&#xa0;kV that blocks the current required to trip the overcurrent relay (<xref ref-type="bibr" rid="B6">Ali et al., 2014</xref>; <xref ref-type="bibr" rid="B26">Calhoun et al., 1982</xref>). The voltage&#x2013;current characteristics are highly dependent on various materials (<xref ref-type="bibr" rid="B6">Ali et al., 2014</xref>), including tree branches, lawns, gravel, stout gravel, asphalt, concrete, crushed stone, board blocks, and cement (<xref ref-type="bibr" rid="B105">Russell et al., 1988</xref>). Furthermore, deteriorated insulators due to cracks, dust, humidity, and ice, among others, are some of the main triggers of HIF in PTDSs (<xref ref-type="bibr" rid="B76">Langeroudi and Abdelaziz, 2020</xref>). The long-term persistence of HIF is undesirable for profitable and smooth operations (<xref ref-type="bibr" rid="B76">Langeroudi and Abdelaziz, 2020</xref>). Various faults and incorrect operations can cause blackouts (<xref ref-type="bibr" rid="B73">Kj&#xf8;lle et al., 2006</xref>). Various vulnerable surfaces to HIF with the corresponding fault currents as indicated by <xref ref-type="bibr" rid="B121">Sedighizadeh et al. (2010</xref>) and <xref ref-type="bibr" rid="B141">Tengdin et al. (1996</xref>) are wet sand 15A, dry sod 20A, dry grass 25A, wet sod 40A, wet grass 50A, reinforced concrete 75A, dry asphalt &#x3c;1A, and dry sand &#x3c;1A. HIFs are sub-classified into active and passive faults (<xref ref-type="bibr" rid="B65">Jota and Jota, 1999</xref>). Active faults possess fault currents below the threshold values of protection relays accompanied by an electric arc. An electric arc does not follow passive faults. They are challenging to detect as there is no indication of the energization of the conductor and can be detected by phase unbalance analysis. The studies evaluated that approximately 10% of the distribution faults in power systems are HIF, of which 25%&#x2013;32% of the down conductors are not detected with overcurrent relays (<xref ref-type="bibr" rid="B138">Sultan and Swift, 1992</xref>). Hence, the detection and isolation of HIF become important. Studies show that conventional protection methods identify only 17.5% of staged HIFs, but the introduction of hybrid energies to distribution grids made the HIF detection demand necessary. An efficient detection method of HIF became necessary to eliminate false tripping and stabilize the power supply. Unlike other faults that endanger electrical appliances, HIF threatens human life. The formation of flammable gases after a HIF interception, which is near flammable material, can cause a fire or explosion. HIF can be caused by a broken or unbroken conductor. <xref ref-type="fig" rid="F2">Figure 2</xref> shows ice and a tree causing HIF in unbroken and broken conductors (<xref ref-type="bibr" rid="B142">Theron et al., 2018</xref>).</p>
<fig id="F2" position="float">
<label>FIGURE 2</label>
<caption>
<p>
<bold>(A)</bold> Ice and a tree causing HIF in unbroken conductors (<xref ref-type="bibr" rid="B142">Theron et al., 2018</xref>). <bold>(B)</bold> HIF arcing on grass (<xref ref-type="bibr" rid="B121">Sedighizadeh et al., 2010</xref>) and concrete (<xref ref-type="bibr" rid="B27">Carpenter et al., 2005</xref>). <bold>(C)</bold> Unbroken conductors (<xref ref-type="bibr" rid="B84">Louis, 2015</xref>).</p>
</caption>
<graphic xlink:href="fenrg-11-1114230-g002.tif"/>
</fig>
<p>As shown by <xref ref-type="bibr" rid="B59">Gururajapathy et al. (2017</xref>), faults in power systems can be broadly classified into symmetrical or asymmetrical faults and balanced or unbalanced faults, among which unbalanced loads are more frequent and can be categorized as series and shunt faults. Series faults are caused by broken conductors or otherwise unbalanced series impedances. These faults can be recognized by an increase in voltage and frequency and a reduction in the current of the faulty feeder. However, in the shunt fault, there will be a fall in frequency and voltage and a rise in current, which is common in power systems. The percentage of occurrence in the power system for a single-line-to-ground fault (SLGF) is 70% which, is less severe. In line-to-line fault (LLF), it is 15%, and the severity is less. In LLF, it is 10% and less severe, whereas the triple-line-to-ground fault (LLLGF) is more severe, and occurrence is only 5%. When any phase of the transmission system comes in contact with the ground or neutral wire, an SLGF occurs due to wind and tree falling, among others. In LLF, the occurrence can be due to heavy wind or when two conductors contact each other, which can happen in overhead and underground systems. The variation of impendence spreads over a wide range in this case, and it is difficult to predict the upper and lower limits. Double-line-to-ground fault (DLGF) occurs when a tree falls on the two phases of the transmission system connecting the ground, which is considered asymmetric and a severe event if not cleared in a certain time. LLLGF is symmetrical owing to equipment failure or a tower falling on the transmission line. This is considered a serious situation as the voltages become zero, and the current may be too high. Low fault current resulting from contact with the high-impedance surface, asymmetry (<xref ref-type="bibr" rid="B136">Sultan et al., 1994</xref>) resulting from the presence of silica on the contact surface, randomness (<xref ref-type="bibr" rid="B21">Benner et al., 1989</xref>) resulting from rapid electrical discharges and floating conductors on the surface of the field, and non-linearity resulting from the different soil layer resistivity (<xref ref-type="bibr" rid="B6">Ali et al., 2014</xref>) are the key characteristics of the HIF. The non-linearity results from the fact that the HIF characteristic curve of the voltage&#x2013;current is non-linear. Low-frequency components are present in the voltage and current waveform due to the non-linearity of HIF, which can range up to 600&#xa0;Hz for current and 300&#xa0;Hz for voltage. The fault current has different waveforms, and a disparity in the peak value and shape is called asymmetry for the positive and negative half periods. HIF is called an arcing fault because it is preceded by an arc, producing a few cycles of conduction followed by cycles of non-conduction. The current HIF value increases for a few cycles and holds a constant value. The current range changes over time, making it non-stationary. Random values are both the current magnitude during conduction and non-conduction periods. Arc results in the present waveform&#x2019;s high-frequency components, and because of the non-linearity of the HIF waveform, it contains harmonics. HIF normally occurs at medium voltages and becomes severe at low voltages and less severe at a high voltage above 25&#xa0;kV. HIF is influenced by several factors, such as feeder configuration, voltage level, weather conditions, and load type (<xref ref-type="bibr" rid="B84">Louis, 2015</xref>). HIF detectors find it hard to detect conductors in run-out conditions or undergo severe weather conditions, tree contacts, and a history of excessive breakage. Researchers working on HIF detection concentrated on lab-based staged fault studies. Owing to the critical nature of the faults, industry and academia focus more on simulations and software studies. Early and accurate fault detection will reduce interruption time and increase the safety and reliability of the power system. Advanced signal processing techniques depend on specialized knowledge and the accuracy of the measured data. The modern power system is currently challenged by the growing volumes of data of different natures, the need for data storage, the introduction of distributed generations, and technological advancements. However, the simulation techniques are still in their developing state. During the signal processing analysis, the hidden characteristics of the measured data are revealed, such as randomness, non-linearity, and asymmetry. Machine learning techniques can acquire hidden data from the measured data, thus providing a promising way to meet the challenges in the power system. These fault characteristics are used by the classifiers to discriminate HIFs from other disturbances.</p>
</sec>
<sec id="s2">
<title>2 HIF detection</title>
<p>The power system network generally has a healthy state and a faulty state. The fault identification task has three main steps: measurements (current, voltage, current and voltage, and magnetic field intensity), feature extraction, and classification (<xref ref-type="bibr" rid="B28">Carr, 1981</xref>). Signal processing techniques are frequently used to increase the effectiveness of HIF detection techniques. The signal processing techniques&#x2019; characteristics extracted their hidden characteristics and measured the three-phase voltage/current signals for HIF detection, improving versatility, stability, and economy. Based on these extracted features, the classifier discriminates whether the HIF event occurred.</p>
<p>
<xref ref-type="fig" rid="F3">Figure 3</xref> shows the basic steps involved in HIF detection using signal processing techniques. The signal processing techniques commonly used for HIF detection schemes are discrete wavelet transform (DWT) (<xref ref-type="bibr" rid="B42">Elkalashy et al., 2007a</xref>; <xref ref-type="bibr" rid="B43">Elkalashy et al., 2008</xref>; <xref ref-type="bibr" rid="B44">Elkalashy et al., 2007b</xref>; <xref ref-type="bibr" rid="B64">Ibrahim et al., 2010a</xref>), principal component analysis (PCA) (<xref ref-type="bibr" rid="B113">Sarlak and Shahrtash, 2008</xref>), linear discriminant analysis (LDA) (<xref ref-type="bibr" rid="B113">Sarlak and Shahrtash, 2008</xref>), continuous wavelet transform (CWT), extended Kalman filter (EKF) (<xref ref-type="bibr" rid="B134">Soheili et al., 2018</xref>), time&#x2013;time transform (TTT) (<xref ref-type="bibr" rid="B97">Nikoofekr et al., 2013</xref>), dual-tree complex wavelet transform (DTWT) (<xref ref-type="bibr" rid="B92">Moravej et al., 2015</xref>), S transform (ST) (<xref ref-type="bibr" rid="B103">Routray et al., 2016</xref>), maximum overlap discrete wavelet transform (MODWT) (<xref ref-type="bibr" rid="B68">Kar and Samantaray, 2017</xref>), fast Fourier transform (FFT) (<xref ref-type="bibr" rid="B24">Bin Sulaiman et al., 2017</xref>), Stockwell transform (<xref ref-type="bibr" rid="B16">Balser et al., 1982</xref>), mathematical morphology filters (MMF) (<xref ref-type="bibr" rid="B124">Sekar and Mohanty, 2018</xref>), and lifting wavelet transform (LWT) (<xref ref-type="bibr" rid="B95">Narasimhulu et al., 2020</xref>). The description of these signal processing tools used in HIF detection techniques is discussed in <xref ref-type="sec" rid="s2-3">Section 2.3</xref>, emphasizing time-domain analysis, frequency-domain analysis, and time&#x2013;frequency-domain analysis. The selected features are extracted from the input signal and then compared to a threshold value in signal processing techniques for HIF detection. Setting the threshold value is challenging because HIF would not be detected if the threshold is set too high. If it is set to an extremely low value, the relay will trip even with light disturbances. This issue can be resolved by introducing intelligent classifiers along with signal processing techniques.</p>
<fig id="F3" position="float">
<label>FIGURE 3</label>
<caption>
<p>Steps involved in pattern classification of HIF detection.</p>
</caption>
<graphic xlink:href="fenrg-11-1114230-g003.tif"/>
</fig>
<p>Commonly used intelligent classifiers in signal processing-based HIF detection techniques are probabilistic neural network (PNN) (<xref ref-type="bibr" rid="B110">Samantaray et al., 2008</xref>), artificial neural network (ANN) (<xref ref-type="bibr" rid="B19">Baqui et al., 2011</xref>), adaptive resonant theory (ART) neural network and Fuzzy ARTMAP (<xref ref-type="bibr" rid="B97">Nikoofekr et al., 2013</xref>), extreme learning machines (ELMs) (<xref ref-type="bibr" rid="B101">Reddy et al., 2013</xref>), genetic algorithm (GA) (<xref ref-type="bibr" rid="B153">Xie et al., 2013a</xref>), support vector machine (SVM) (<xref ref-type="bibr" rid="B23">Bhongade and Golhani, 2016</xref>), adaptive neuro-fuzzy inference system (ANFIS) (<xref ref-type="bibr" rid="B146">Veerasamy et al., 2018</xref>), decision tree (DT) (<xref ref-type="bibr" rid="B124">Sekar and Mohanty, 2018</xref>), random forest (RF) (<xref ref-type="bibr" rid="B122">Sekar and Mohanty, 2020</xref>), convolution neural network (CNN) (<xref ref-type="bibr" rid="B47">Fan and Yin, 2019</xref>), and fuzzy logic control (FLC) (<xref ref-type="bibr" rid="B135">Suliman and Ghazal, 2019</xref>) explained in <xref ref-type="sec" rid="s4">Section 4</xref>. These intelligent classifiers improved the efficiency, speed, and accuracy of signal processing-based procedures by detecting HIFs without the use of threshold settings.</p>
<p>The practical detection of HIFs was explained by <xref ref-type="bibr" rid="B72">Kistler et al. (2019</xref>), who used two relay-based HIF detection algorithms. The former uses the odd-harmonic contents of phase current, whereas the latter uses the inter-harmonic contents. The first algorithm uses total odd harmonic content from phase currents using the FIR filter. A threshold value was set, and the odd harmonic contents were compared. If the difference is more significant than the threshold, the counter increments, and the alarm is set. The second algorithm uses the sum of the difference of inter harmonic content that uses a reference and compares it to the measured sum of difference currents to detect the increase in the sum of difference currents during an HIF. The second algorithm was more successful for HIF detection, mainly on grassy surfaces, and slightly less for fully contact good insulators that do not cause an arc. The algorithm&#x2019;s performance was tested in a live conductor by the Electric Power Research Institute and PPL electric utilities (<xref ref-type="bibr" rid="B125">SEL, 2007</xref>).</p>
<p>Mitigation of forest fires and human safety issues were addressed by <xref ref-type="bibr" rid="B53">Gashteroodkhani et al. (2021</xref>) through the practical detection of HIFs. Two strategies for fault current detection, one based on the non-harmonic content of fault currents and the other on the odd-harmonic content of fault currents, are explained and evaluated in a hardware-in-the-loop (HIL) platform employing a real-time digital simulator (RTDS). With 1,736 relay events reported, the first algorithm detected 95% of the HIFs, whereas the second detected only 5% of HIFs. The test system chosen was from a distribution network in the Northern Nevada area with a 14.4-kV three-phase three-wire feeder. <xref ref-type="bibr" rid="B30">Chakraborty and Das (2019</xref>) explained that smart meters are installed for voltage measurements compared with a threshold value to detect the presence of HIFs. It is tested in six different situations of three broken and three unbroken conductors. The method is implemented along with a single-phase energy meter capable of detecting the presence of HIFs, voltage sag-swells, capacitor/load switching (<xref ref-type="bibr" rid="B98">Panigrahi et al., 2018</xref>; <xref ref-type="bibr" rid="B99">Prasad et al., 2022</xref>), transformer and feeder energization (<xref ref-type="bibr" rid="B25">Biswal et al., 2022</xref>), power electronic loads, arc furnace loads, and distributed generators (DG). The method gives satisfactory results in HIF detection. The detection methods proposed in previous studies (<xref ref-type="bibr" rid="B82">Lima et al., 2018</xref>; <xref ref-type="bibr" rid="B155">Yang et al., 2006</xref>; <xref ref-type="bibr" rid="B119">Sedighi et al., 2005a</xref>; <xref ref-type="bibr" rid="B3">Abdelgayed et al., 2017</xref>; <xref ref-type="bibr" rid="B151">Wang et al., 2019</xref>) also experimented on real-time systems discussed in the various sections of the manuscript. Discrimination of HIF along with cross-country faults was explained by <xref ref-type="bibr" rid="B10">Ashok and Yadav (2021</xref>). A simulation model of the IEEE 13-bus system is used to obtain the three-phase current signals, and MODWPT is used for feature extraction. The real-time field data from Chhattisgarh State Power Transmission Network are collected and tested using the same algorithm. Classification of HIF, non-HIF boundary fault conditions, capacitor switching, reactor string switching, load switching, power swing effects, the effect of noise, lightly load conditions, and electric arc furnace effects in PTDSs is done. The classification is conducted by setting a threshold value for the energy envelop index. The response time of the proposed method for each case is recorded, which is less than 14.3&#xa0;m. When compared with earlier studies (<xref ref-type="bibr" rid="B56">Ghaderi et al., 2017</xref>; <xref ref-type="bibr" rid="B121">Sedighizadeh et al., 2010</xref>; <xref ref-type="bibr" rid="B148">Vyshnavi and Prasad, 2018</xref>, this study gives an insight into various test systems used for testing various HIF detection methods and studies the nature of HIF, which is discussed in <xref ref-type="sec" rid="s3">Section 3</xref>.</p>
<sec id="s2-1">
<title>2.1 Measurements</title>
<p>Measurements such as current measurement, voltage measurement, and both current-voltage measurements extract features for fault analysis. An HIF is accompanied by the intermittence of arc (<xref ref-type="bibr" rid="B32">Chen et al., 2013</xref>). The arcing fault contains low- and high-frequency components in the current frequency spectrum. The low frequency-based technique results in lower-order harmonics with even, odd, and intermittent harmonics extracted for HIF detection. High frequency-based techniques show short variations in the HIF current.</p>
<p>Voltage measurement is performed by extracting three-phase voltage signals proposed by <xref ref-type="bibr" rid="B6">Ali et al. (2014</xref>) during the HIF phenomenon in an underground distribution network. <xref ref-type="bibr" rid="B15">Bakar et al. (2014</xref>) performed a voltage measurement at the primary substation and compared fault features with the database generated from the simulation. The method has a single measurement and multiple branches that can detect multiple faulty sections. Detection of HIFs by voltage measurement is efficient only when there is a voltage drop between the relay and fault location. The proposed method by <xref ref-type="bibr" rid="B150">Wang et al. (2018</xref>) used the discriminant vector of negative and zero sequence current and voltage in the substation.</p>
<p>Current and voltage measurement has improved reliability compared to the latter measurements. Magnetic field intensity measurement increases the cost and complexity of the detection technique (<xref ref-type="bibr" rid="B14">Bahador et al., 2018</xref>).</p>
</sec>
<sec id="s2-2">
<title>2.2 Signal processing techniques and feature extraction</title>
<p>Signal processing techniques are widely used to improve the effectiveness of high-impedance defect detection approaches. Signal processing techniques extract the hidden properties of observed three-phase signals for HIF detection, enhancing adaptability, stability, and cost-effectiveness. More informative data are obtained using various analyses based on these extracted data, such as time-domain analysis, frequency-domain analysis, and time&#x2013;frequency analysis (<xref ref-type="bibr" rid="B34">Chen et al., 1990</xref>; <xref ref-type="bibr" rid="B115">Sarlak and Shahrtash, 2013</xref>). <xref ref-type="table" rid="T1">Table 1</xref> gives a detailed comparison of various signal processing techniques for HIF detection using intelligent classifiers.</p>
<table-wrap id="T1" position="float">
<label>TABLE 1</label>
<caption>
<p>Comparison of various signal processing techniques for HIF detection using intelligent classifiers.</p>
</caption>
<table>
<thead valign="top">
<tr>
<th align="center">Ref. No.</th>
<th align="center">Feature extraction approach</th>
<th align="center">Classifier</th>
<th align="center">Test system</th>
<th align="center">Year</th>
<th align="center">Remarks</th>
</tr>
</thead>
<tbody valign="top">
<tr>
<td rowspan="2" align="left">
<xref ref-type="bibr" rid="B108">Samantaray et al. (2009a)</xref>
</td>
<td rowspan="2" align="left">Adaptive extended Kalman filter (AEKF)</td>
<td rowspan="2" align="left">Feedforward neural network and PNN</td>
<td rowspan="2" align="left">i) Radial distribution feeder, 15&#xa0;kV<break/>ii) Mesh distribution network, 15&#xa0;kV</td>
<td rowspan="2" align="center">2009</td>
<td align="left">Detection time, 0.01&#xa0;s</td>
</tr>
<tr>
<td align="left">PNN classification rate is 99.11%, whereas for FNN, it is 96.51%</td>
</tr>
<tr>
<td align="left">
<xref ref-type="bibr" rid="B37">Cui et al. (2017)</xref>
</td>
<td align="left">Discrete Fourier transform (DFT) and Kalman filter</td>
<td align="left">Pattern recognition</td>
<td align="left">Benchmark test system 25&#xa0;kV</td>
<td align="center">2017</td>
<td align="left">An effective feature set algorithm is introduced to the feature extracted and compared with Naive Bayes, support vector machine, KNN, J48, and RF, of which J48 and RF give better results</td>
</tr>
<tr>
<td align="left">
<xref ref-type="bibr" rid="B23">Bhongade and Golhani (2016)</xref>
</td>
<td align="left">DWT</td>
<td align="left">Support vector machine</td>
<td align="left">Radial distribution system, 400 kV</td>
<td align="center">2017</td>
<td align="left">The traveling wave method is used for locating the fault. Good accuracy as the % error is below 1.22%</td>
</tr>
<tr>
<td align="left">
<xref ref-type="bibr" rid="B31">Chen et al. (2014)</xref>
</td>
<td align="left">DWT-MRA</td>
<td align="left">Simple detection criterion</td>
<td align="left">IEEE 13-node test</td>
<td align="center">2014</td>
<td align="left">Efficient and fast method. Economical since voltage signal measurement is needed</td>
</tr>
<tr>
<td align="left">
<xref ref-type="bibr" rid="B157">Yeh et al. (2019)</xref>
</td>
<td align="left">DWT</td>
<td align="left">Digital signal processor</td>
<td align="left">Distribution network at Southern California Edison, 12 kV</td>
<td align="center">2019</td>
<td align="left">Detection time 32.9&#xa0;m. Effective and flexible method. Tested on real-time data</td>
</tr>
<tr>
<td align="left">
<xref ref-type="bibr" rid="B4">Akorede and Katende (2010)</xref>
</td>
<td align="left">DWT</td>
<td align="left">Pattern classifier</td>
<td align="left">The radial distribution network, 11&#xa0;kV</td>
<td align="center">2010</td>
<td align="left">Moving window approach. Two-class classification only</td>
</tr>
<tr>
<td align="left">
<xref ref-type="bibr" rid="B19">Baqui et al. (2011)</xref>
</td>
<td align="left">DWT</td>
<td align="left">ANN</td>
<td align="left">Radial distribution, 13.8&#xa0;kV, Basque Country (Spain)</td>
<td align="center">2011</td>
<td align="left">Discriminates HIF, LIF, and switching events. Multilayer perceptron network and Levenberg&#x2013;Marquardt backpropagation algorithm are the learning algorithms used</td>
</tr>
<tr>
<td align="left">
<xref ref-type="bibr" rid="B6">Ali et al. (2014)</xref>
</td>
<td align="left">DWT</td>
<td align="left">Short distance algorithm and matching approach</td>
<td align="left">38-Node underground distribution, 132/11&#xa0;kV, Malaysia</td>
<td align="center">2014</td>
<td align="left">Locating time required is less compared to conventional methods</td>
</tr>
<tr>
<td align="left">
<xref ref-type="bibr" rid="B153">Xie et al. (2013a)</xref>
</td>
<td align="left">Dual-tree complex wavelet transforms</td>
<td align="left">PNN</td>
<td align="left">IEEE 34-node test feeder</td>
<td align="center">2014</td>
<td align="left">PNN requires no iteration. Detection time 1.5&#xa0;m. The error of detection of 1.4%</td>
</tr>
<tr>
<td align="left">
<xref ref-type="bibr" rid="B62">Ibrahim et al. (2008)</xref>
</td>
<td align="left">DWT</td>
<td align="left">Moving window-based pattern recognition</td>
<td align="left">JMARTY model 500 kV, Egypt</td>
<td align="center">2007</td>
<td align="left">Simple, accurate, and fast technique. EHV transmission lines</td>
</tr>
<tr>
<td align="left">
<xref ref-type="bibr" rid="B139">Tag Eldin et al. (2009)</xref>
</td>
<td align="left">DWT</td>
<td align="left">An algorithm based on a recursive method (Clark&#x2019;s transformation)</td>
<td align="left">ATP/EMTP model for real CCVT, 500&#xa0;kV, 150&#xa0;km, 500&#xa0;kV transmission line</td>
<td align="center">2009</td>
<td align="left">Accurately detect HIF detection in EHV transmission lines. Independent of the HIF model. Detects HIF in &#xbe;th of a cycle</td>
</tr>
<tr>
<td rowspan="3" align="left">
<xref ref-type="bibr" rid="B75">Lai et al. (2005)</xref>
</td>
<td rowspan="3" align="left">DWT and pattern recognition</td>
<td rowspan="3" align="left">Nearest neighboring rule</td>
<td align="left">25&#xa0;kV power distribution networks</td>
<td rowspan="3" align="center">2005</td>
<td rowspan="3" align="left">Error range 2.52% and 45.4%. It will not indicate the physical properties of the output coefficient</td>
</tr>
<tr>
<td align="left">i) Distribution network with a single branch of a non-linear load</td>
</tr>
<tr>
<td align="left">ii) Radial distribution network<break/>iii) Meshed network</td>
</tr>
<tr>
<td align="left">
<xref ref-type="bibr" rid="B154">Xie et al. (2013b)</xref>
</td>
<td align="left">Extended Kalman filter</td>
<td align="left">Support vector machine</td>
<td align="left">Radial distribution feeder, 13.8&#xa0;kV</td>
<td align="center">2009</td>
<td align="left">Classification accuracy of 98%. Excellent results under noisy conditions also</td>
</tr>
<tr>
<td align="left">
<xref ref-type="bibr" rid="B149">Wali et al. (2018)</xref>
</td>
<td align="left">FFT</td>
<td align="left">Power spectrum (PS) technique</td>
<td align="left">Radial distribution feeder, 13.8&#xa0;kV</td>
<td align="center">2018</td>
<td align="left">Detection accuracy of 100%, simple technique, requires less time because training is not needed</td>
</tr>
<tr>
<td align="left">
<xref ref-type="bibr" rid="B140">Tawafan et al. (2012)</xref>
</td>
<td align="left">FFT</td>
<td align="left">ANFIS</td>
<td align="left">Radial distribution feeder, 13.8&#xa0;kV</td>
<td align="center">2012</td>
<td align="left">Mean squared value of 0.084. ANFIS is based on subtractive clustering. The classification rate is above 96.4%</td>
</tr>
<tr>
<td align="left">
<xref ref-type="bibr" rid="B158">Yeh et al. (2014)</xref>
</td>
<td align="left">FFT and Walsh&#x2013;Hadamard transforms (WHTs)</td>
<td align="left">Threshold and shape of the magnitude and phase responses of orthogonal transforms</td>
<td align="left">Official websites of DOE/EPRI National Database Repository of Power System Events</td>
<td align="center">2015</td>
<td align="left">Detection time is 0.033&#xa0;s. The performance of the method is correct and precise</td>
</tr>
<tr>
<td align="left">
<xref ref-type="bibr" rid="B95">Narasimhulu et al. (2020)</xref>
</td>
<td align="left">LWT</td>
<td align="left">ANN</td>
<td align="left">Radial distribution network, 400&#xa0;kV</td>
<td align="center">2020</td>
<td align="left">Efficiency is 98%. Superior to GA-fuzzy, GSA-ANN, and ALO</td>
</tr>
<tr>
<td align="left">
<xref ref-type="bibr" rid="B123">Sekar and Mohanty (2017)</xref>
</td>
<td align="left">MM</td>
<td align="left">DT</td>
<td align="left">IEEE 13, IEEE 34-node feeder</td>
<td align="center">2017</td>
<td align="left">Detection time 30&#xa0;m, accuracy 98.33%</td>
</tr>
<tr>
<td align="left">
<xref ref-type="bibr" rid="B55">Gautam and Brahma (2013)</xref>
</td>
<td align="left">MM</td>
<td align="left">Implemented on overcurrent relay</td>
<td align="left">IEEE 13-node test feeder</td>
<td align="center">2012</td>
<td align="left">Detection time 1&#xa0;s. The success rate of detection and classification is 100%</td>
</tr>
<tr>
<td align="left">
<xref ref-type="bibr" rid="B98">Panigrahi et al. (2018)</xref>
</td>
<td align="left">MM</td>
<td align="left">Detection algorithm</td>
<td align="left">IEEE PSRC Working Group D15</td>
<td align="center">2020</td>
<td align="left">Detection time 0.8&#xa0;s</td>
</tr>
<tr>
<td rowspan="3" align="left">
<xref ref-type="bibr" rid="B69">Kavaskar and Mohanty (2019)</xref>
</td>
<td rowspan="3" align="left">MM</td>
<td rowspan="3" align="left">Simple rule-based algorithm</td>
<td rowspan="3" align="left">EPDS 11&#xa0;kV radial distribution, Chennai</td>
<td rowspan="3" align="center">2019</td>
<td align="left">Detection time 80&#xa0;m</td>
</tr>
<tr>
<td align="left">Security and dependability 100%</td>
</tr>
<tr>
<td align="left">HIF, LIF, load, and capacitor switching are classified</td>
</tr>
<tr>
<td align="left">
<xref ref-type="bibr" rid="B115">Sarlak and Shahrtash (2013)</xref>
</td>
<td align="left">MM</td>
<td align="left">SVM</td>
<td align="left">Palash feeder in southwestern Tehran, radial distribution</td>
<td align="center">2013</td>
<td align="left">HIF indicator is introduced, which is based on magnetic field strength signals</td>
</tr>
<tr>
<td rowspan="2" align="left">
<xref ref-type="bibr" rid="B124">Sekar and Mohanty (2018)</xref>
</td>
<td rowspan="2" align="left">MM</td>
<td rowspan="2" align="left">DT</td>
<td rowspan="2" align="left">EPDS 11&#xa0;kV radial distribution system, Chennai</td>
<td rowspan="2" align="center">2018</td>
<td align="left">Detection time 30.66&#xa0;m</td>
</tr>
<tr>
<td align="left">Accuracy 99.34%</td>
</tr>
<tr>
<td align="left">
<xref ref-type="bibr" rid="B122">Sekar and Mohanty (2020)</xref>
</td>
<td align="left">Morphology gradient (MG)</td>
<td align="left">Fuzzy rule base</td>
<td align="left">EPDS distribution, Chennai, 33 kV</td>
<td align="center">2020</td>
<td align="left">Accuracy of 99.3%. Less computation time</td>
</tr>
<tr>
<td align="left">
<xref ref-type="bibr" rid="B50">Gadanayak and Mallick (2019)</xref>
</td>
<td align="left">MODWT</td>
<td align="left">Knot-based EMD</td>
<td align="left">CERTS microgrid system</td>
<td align="center">2019</td>
<td align="left">Detection time is 0.12&#xa0;s Accuracy of 100%. The current from the proposed algorithm cannot be used in a mesh network</td>
</tr>
<tr>
<td align="left">
<xref ref-type="bibr" rid="B68">Kar and Samantaray (2017)</xref>
</td>
<td align="left">MODWT</td>
<td align="left">DT</td>
<td align="left">Test microgrid system</td>
<td align="center">2017</td>
<td align="left">Classification accuracy of 99.77%. Highly reliable for microgrid distribution systems. The test is also performed in islanded mode</td>
</tr>
<tr>
<td align="left">
<xref ref-type="bibr" rid="B114">Sarlak and Shahrtash (2011)</xref>
</td>
<td align="left">Multi-resolution MG</td>
<td align="left">MLPNN</td>
<td align="left">Palash feeder in the southwest of Tehran, simulation, distribution</td>
<td align="center">2011</td>
<td align="left">Superior to other feature extraction techniques like DWT, DFT, discrete s-transform (DST), discrete time&#x2013;time (DTT) transform. Security 92.8%, dependability 96.4%</td>
</tr>
<tr>
<td align="left">
<xref ref-type="bibr" rid="B113">Sarlak and Shahrtash (2008)</xref>
</td>
<td align="left">PCA and LDA</td>
<td align="left">SVM</td>
<td align="left">IEEE four-node test feeders</td>
<td align="center">2008</td>
<td align="left">Better accuracy of 97.5% compared to Bayes and Parzen classifiers</td>
</tr>
<tr>
<td align="left">
<xref ref-type="bibr" rid="B107">Samantaray et al. (2009b)</xref>
</td>
<td align="left">S and TT transform</td>
<td align="left">PNN and FNN</td>
<td align="left">i) Three-phase radial distribution feeder <break/>ii) Three-phase mesh network. Both have 15&#xa0;kV</td>
<td align="center">2009</td>
<td align="left">The classification rate of PNN is 98.02% as it is 94.04% for FNN for the radial network. The testing time is 0.3 s for FNN and 0.01 s for PNN</td>
</tr>
<tr>
<td align="left">
<xref ref-type="bibr" rid="B81">Lima et al. (2019)</xref>
</td>
<td align="left">Stockwell transform</td>
<td align="left">Probabilistic analysis</td>
<td align="left">Brazilian utility, 13.8&#xa0;kV real distribution</td>
<td align="center">2019</td>
<td align="left">Accuracy rate of 94.4%. Detection time is 166&#xa0;m. Tested on six different surfaces, and detection time is measured</td>
</tr>
<tr>
<td align="left">
<xref ref-type="bibr" rid="B90">Mishra et al. (2016)</xref>
</td>
<td align="left">Stockwell transform</td>
<td align="left">ANN and SVM</td>
<td align="left">Radial and Mesh distribution system, 138&#xa0;kV</td>
<td align="center">2016</td>
<td align="left">Comparison of ANN with SVM. ANN in the radial network gives 93.7% accuracy as SVM with 86.25% in the mesh network</td>
</tr>
<tr>
<td align="left">
<xref ref-type="bibr" rid="B93">Naik and Yadav (2018)</xref>
</td>
<td align="left">DFT</td>
<td align="left">Fuzzy interface system</td>
<td align="left">IEEE 15-bus system</td>
<td align="center">2018</td>
<td align="left">Effective classification of HIF, symmetrical and unsymmetrical faults in less than 8.33&#xa0;m</td>
</tr>
<tr>
<td align="left">
<xref ref-type="bibr" rid="B66">K. Chaitanya and Yadav (2020)</xref>
</td>
<td align="left">EWT-SVD</td>
<td align="left">SVM</td>
<td align="left">Modified IEEE 13-node system</td>
<td align="center">2020</td>
<td align="left">Classification accuracy of 99% for 60&#xa0;dB noisy environment</td>
</tr>
<tr>
<td align="left">
<xref ref-type="bibr" rid="B29">Chaitanya et al. (2020)</xref>
</td>
<td align="left">Variational mode de-composition (VMD)</td>
<td align="left">SVM</td>
<td align="left">IEEE 13-node system</td>
<td align="center">2020</td>
<td align="left">Effective classification of HIF, LIF, and non-faulty conditions with a classification accuracy of 99% and response time for LIF is 16.67&#xa0;m, and that for HIF is 166.7&#xa0;m</td>
</tr>
<tr>
<td align="left">
<xref ref-type="bibr" rid="B103">Routray et al. (2016)</xref>
</td>
<td align="left">Stockwell transform</td>
<td align="left">ANN</td>
<td align="left">Radial distribution system, 138&#xa0;kV</td>
<td align="center">2015</td>
<td align="left">Accuracy of 98.75%</td>
</tr>
<tr>
<td align="left">
<xref ref-type="bibr" rid="B57">Ghaderi et al. (2015)</xref>
</td>
<td align="left">Time freq. analysis</td>
<td align="left">SVM</td>
<td align="left">The test was conducted in a real-time, high-current research laboratory</td>
<td align="center">2013</td>
<td align="left">Simple, reliable, and efficient. Accuracy of 93.6%</td>
</tr>
<tr>
<td align="left">
<xref ref-type="bibr" rid="B97">Nikoofekr et al. (2013)</xref>
</td>
<td align="left">TT transform</td>
<td align="left">ART neural networks and Fuzzy ARTMAP</td>
<td align="left">Palash feeder in the southwest region of Tehran</td>
<td align="center">2013</td>
<td align="left">Accuracy of 99.18%. Five-class classification</td>
</tr>
<tr>
<td rowspan="2" align="left">
<xref ref-type="bibr" rid="B155">Yang et al. (2006)</xref>
</td>
<td rowspan="2" align="left">Wavelet transform</td>
<td rowspan="2" align="left">Pattern recognition-based ANN</td>
<td align="left">Tai-16 distribution feeder system 11.4&#xa0;kV from Taishi substation</td>
<td rowspan="2" align="center">2006</td>
<td rowspan="2" align="left">Detection rate of 81%. More accurate than unintelligent algorithms</td>
</tr>
<tr>
<td align="left">Yunlin</td>
</tr>
<tr>
<td rowspan="2" align="left">
<xref ref-type="bibr" rid="B61">Hubana et al. (2018)</xref>
</td>
<td rowspan="2" align="left">DWT</td>
<td rowspan="2" align="left">ANN</td>
<td align="left">i) Two-bus test distribution system of the city of Mostar (Bosnia and Herzegovina), 35/10&#xa0;kV</td>
<td rowspan="2" align="center">2018</td>
<td rowspan="2" align="left">A two-bus system gives a classification accuracy of 92.5%, and an eight-bus system gives 90.19%. Highly effective with good noise removal capability</td>
</tr>
<tr>
<td align="left">ii) Eight-bus system with the same specifications, including underground cables, substations</td>
</tr>
<tr>
<td align="left">
<xref ref-type="bibr" rid="B82">Lima et al. (2018)</xref>
</td>
<td align="left">STFT</td>
<td align="left">Blackman&#x2013;Harris window, spectrogram analysis</td>
<td align="left">Brazilian utility, 13.8&#xa0;kV, real distribution</td>
<td align="center">2018</td>
<td align="left">Tested in simulated data and real-time oscilloscopic data, which gave the best results</td>
</tr>
<tr>
<td align="left">
<xref ref-type="bibr" rid="B52">Gashteroodkhani et al. (2020)</xref>
</td>
<td align="left">TT</td>
<td align="left">Deep belief neural network</td>
<td align="left">IEC microgrid 61,850-7-420, 25&#xa0;kV</td>
<td align="center">2020</td>
<td align="left">Tested in grid-connected as well as an islanded mode of operation. The accuracy of the proposed system for fault detection is 99.8%, and fault classification is 99.32%</td>
</tr>
<tr>
<td align="left">
<xref ref-type="bibr" rid="B3">Abdelgayed et al. (2017)</xref>
</td>
<td align="left">DWT</td>
<td align="left">DT and KNN</td>
<td align="left">CERTS microgrid system</td>
<td align="center">2017</td>
<td align="left">The experimental result of DT is 100%, and that of KNN is 95%</td>
</tr>
<tr>
<td align="left">
<xref ref-type="bibr" rid="B54">Gashteroodkhani et al. (2019)</xref>
</td>
<td align="left">TT and S transform</td>
<td align="left">SVM</td>
<td align="left">Transmission line, 230&#xa0;kV</td>
<td align="center">2019</td>
<td align="left">Fault identification is 98%</td>
</tr>
</tbody>
</table>
</table-wrap>
</sec>
<sec id="s2-3">
<title>2.3 Domain analysis</title>
<sec id="s2-3-1">
<title>2.3.1 Time-domain analysis</title>
<p>The time-domain analysis uses the measure of zero-sequence voltage and current for feature extraction of HIF. The time-domain analysis is based on arc current waveform. Time-domain takes out the temporary irregularities in the HIF waveform, making the system computationally complex (<xref ref-type="bibr" rid="B78">Lee and Bishop, 1985</xref>).</p>
<p>
<xref ref-type="bibr" rid="B96">Nezamzadeh-Ejieh and Sadeghkhani (2020</xref>) proposed that Kullback&#x2013;Leibler divergence extracts the non-linearity and asymmetry characteristics of two half-cycles of the current waveform from the substation in a time-domain detection of HIF. The method is tested in 13-node and IEEE 34 systems (the Institute of Electrical and Electronics Engineers). Without any harmonic component analysis or training set, the method can identify an HIF by calculating the energization of feeders, voltage swag, and swell.</p>
<p>Mathematical morphology (MM) is a signal processing technique applied to issues in the power system illustrated in the literature (<xref ref-type="bibr" rid="B124">Sekar and Mohanty, 2018</xref>; <xref ref-type="bibr" rid="B98">Panigrahi et al., 2018</xref>). MM uses simple arithmetic operations, such as set theory and integral geometry, and due to its simple calculations, the processing time is less.</p>
<p>The basic functions in MM are dilation and erosion (<xref ref-type="bibr" rid="B69">Kavaskar and Mohanty, 2019</xref>). MM is non-linear, and it is time-domain processing of the signal widely used to extract high- and low-frequency signals. Here, the proposed MM, along with data mining DT, is used for HIF detection. Statistical features are extracted, which serve as input to DT and RF for discriminating with non-HIF conditions (load switching, capacitor switching, and inrush current).</p>
<p>The morphology gradient filter extracts statistical features from the features. A rule set is created using RF, which will accept the crisp inputs using a fuzzy-based algorithm proposed by <xref ref-type="bibr" rid="B122">Sekar and Mohanty (2020</xref>). This method detects HIFs and normal events with high dependability. The chosen sampling rate was 60 samples/cycle, requiring less memory space and less computational time.</p>
<p>The adaptive extended Kalman filter (AEKF) estimates the harmonic components in fault currents for non-linear loading conditions (<xref ref-type="bibr" rid="B108">Samantaray et al., 2009a</xref>). The harmonic components estimated by the technique are fundamental, third, fifth, seventh, eleventh, and thirteenth harmonics. Based on the Kalman filtering principle, <xref ref-type="bibr" rid="B58">Girgis et al. (1990</xref>) built an approach based on the time-varying existence of the fundamental and harmonic components to obtain the best estimate of the time variations of the harmonic components. <xref ref-type="bibr" rid="B49">Faridnia et al. (2012</xref>) presented a partial co-relation function for HIF detection from voltage and current relays. The method is tested in a radial feeder system with two HIF models in PSCAD/EMTDC. Twelve indices-based correlation function is implemented and tested on a wide data set to obtain accurate results for HIF detection.</p>
</sec>
<sec id="s2-3-2">
<title>2.3.2 Frequency-domain analysis</title>
<p>Frequency-domain analysis extracts harmonics in the current spectrum. In the current spectrum, an HIF event will produce low- and high-frequency components. Low-frequency components are based on non-linearity results, whereas high-frequency components are based on sudden and random changes in a non-stationary HIF current waveform. FFT extracts the current signal data after the simulation is applied to a power spectrum (PS) technique that can detect an HIF and distinguish it from non-faulty conditions, such as capacitor banks, non-linear loads, and linear loads, which have the same features (<xref ref-type="bibr" rid="B149">Wali et al., 2018</xref>). FFT is used to calculate the impulse response of the frequency domain (<xref ref-type="bibr" rid="B118">Scott, 1994</xref>). <xref ref-type="bibr" rid="B11">Aucoin and Russell (1982</xref>) utilized high-frequency current components to detect HIF. The low-frequency spectrum is compared with the harmonics of the current waveform measured in the primary substation over a week (<xref ref-type="bibr" rid="B46">Emanuel et al., 1990</xref>).</p>
</sec>
<sec id="s2-3-3">
<title>2.3.3 Time&#x2013;frequency domain</title>
<p>The wavelet methods are more potent as they extract the frequency and instant or position for signal analysis. Time&#x2013;frequency analysis (TFA) could effectively detect discontinuities, repeated patterns, and non-stationary aspects of signals. It measures the energy of the signal at each moment of time and frequency coordinates. TFA has been successfully applied to various power system applications, such as the evaluation of power efficiency, security of power systems, and pathfinding for disturbances of capacitor switching.</p>
<p>
<xref ref-type="bibr" rid="B82">Lima et al. (2018</xref>) proposed a method that uses a short-time Fourier transform for feature extraction that extracts harmonic components of phase current as of the magnitude and phase of the third harmonic component and magnitude of second and fifth harmonics to identify the presence of HIFs. The window length chosen is directly proportional to frequency resolution and inversely proportional to time resolution. The sampling frequency is 15.6&#xa0;kHz. A Brazilian distribution feeder of 13.8&#xa0;kV is used to evaluate the methodology. A Blackman&#x2013;Harris window with five cycles is chosen for this method, and the spectrum analysis is performed. The method was tested in sand, asphalt, gravel, grass, cobblestones, and local soil. The detection time is less than 200&#xa0;ms.</p>
<p>The ST is an extended wavelet transform class based on Gaussian window shifting and scalable localizing. The S transform has absolute phase information and good time&#x2013;frequency resolution for all frequencies. Unlike wavelet transformation, the ST is extremely resistant to noise (<xref ref-type="bibr" rid="B90">Mishra et al., 2016</xref>). Morlet wavelet transform differentiates between HIFs and regular switching events and investigates faults for different surfaces, including Portland cement, wet soil, and grass (<xref ref-type="bibr" rid="B60">Huang and Hsieh, 1999</xref>). DWT decomposes time-domain signals into different harmonics in the time&#x2013;frequency domain, and the extracted features are used to train ANN (<xref ref-type="bibr" rid="B19">Baqui et al., 2011</xref>). The mother wavelet of Daubechies is superior to others, such as Morlet, symet, and rbior, as it can accurately detect low-amplitude signals. The method was also verified on various wet and dry surfaces.</p>
<p>The proposed method uses DWT, and high- and low-frequency voltage components at various system points are measured (<xref ref-type="bibr" rid="B111">Santos et al., 2017</xref>). The energy spectrum of the detailed and approximation coefficient is calculated. The method is evaluated using a 13.8-kV Brazilian distribution feeder with a signal-to-noise ratio (SNR) of 60&#xa0;dB, and the two-time varying resistances HIF model is used. The method requires no monitoring devices and information about the feeder and load parameters. The method is reliable and efficiently identifies the HIF with a 70% search field reduction obtained.</p>
<p>Wavelet transform decomposes and extracts the features, PCA performs feature selection, and the Bayesian classifier discriminates the HIF with normal events (<xref ref-type="bibr" rid="B119">Sedighi et al., 2005a</xref>). Various tests were conducted on wet and dry surfaces. A pattern recognition system is proposed and is simulated using EMTP software. A real-time experiment is performed in Qeshm island, Iran, and an HIF is created in 8,209&#xa0;m and 8,446&#xa0;m locations from the site. The sampling rate of the data is 24.67&#xa0;kHz, and the classifier success rate is 97.6%.</p>
<p>In (<xref ref-type="bibr" rid="B80">Li and Li, 2005</xref>) arc fault detection with automatically modified time windows to differentiate arc fault from non-arc fault is done using wavelet packet transform-based. At level 3 decomposition, db10 is used at a sampling frequency of 12.5&#xa0;kHz. The window length in this study is 1/2 cycle (1.25&#xa0;ms in 400&#xa0;Hz for an airplane). The size of the moving window is 1/4 cycle (0.625&#xa0;m in 400&#xa0;Hz), such that &#x2206;t &#x3d; 0.625&#xa0;m. The proposed method is powerful with simple calculations.</p>
<p>
<xref ref-type="bibr" rid="B87">Michalik et al. (2006</xref>) proposed an approach in which a wavelet-based measurement is performed for zero-sequence voltage and current signals. This method gave fast and reliable HIF detection and location and obtained better performance compared to conventional methods. ANN is used for classification, and the decision module is implemented in real-time using a single neuron. The proposed method gives good results with low-impedance permanent ground faults.</p>
<p>
<xref ref-type="bibr" rid="B77">Lazkano et al.&#x2019;s (2004</xref>) method is based on the decomposition of three-phase unbalanced current data utilizing wavelet transform techniques. Arc phenomena linked with an HIF can be detected due to the WT&#x2019;s time-frequency characteristic, and the signal is broken down into frequency sub-bands. The Db4 mother wavelet was chosen for the four-level decomposition of the arc current signal. A 20-kV Tuejar feeder of Spain is selected and simulated to test the proposed method, which gives satisfactory results.</p>
<p>
<xref ref-type="bibr" rid="B38">De Alvarenga Ferreira and Mariano Lessa Assis (2019</xref>) illustrated a novel approach for HIF detection in smart grids using multi-resolution signal decomposition to decompose the DWT coefficient. The HIF model used for testing is the Kizilcay arc model. The IEEE 13-node test feeder simulated in PSCAD/EMTP is used to evaluate the proposed method. Level 3 decomposition with db8 mother wavelet function is adopted for the proposed work. Various conditions are illustrated with HIF and non-HIF conditions, such as capacitor switching. The method provides robust, fast, and reliable HIF detection.</p>
<p>Features of Earth faults due to leaning trees are extracted from the phase currents and voltages using the DWT (<xref ref-type="bibr" rid="B44">Elkalashy et al., 2007b</xref>; <xref ref-type="bibr" rid="B42">Elkalashy et al., 2007a</xref>; <xref ref-type="bibr" rid="B45">Elkalashy, 2007</xref>). The detailed coefficient of current and voltage is used, whose product is taken to compute power. A positive polarity of power gives a healthy feeder, and negative polarity gives a faulty feeder. The method has been tested on a leaning tree in a laboratory setup.</p>
<p>The wavelet-based algorithm is used to detect HIF detection (<xref ref-type="bibr" rid="B86">Michalik et al., 2007</xref>). The algorithm works great for ground fault currents above 3A, irrespective of phase and location. The method is tested in the Next-Generation Power Technology Center and KEPCo, South Korea. The sampling rate is 10k Hz, and the detection time ranges from 0.2 to 0.7s depending on the distance.</p>
<p>Stockwell&#x2019;s transform extracts the parameters in both the time and frequency domains proposed by <xref ref-type="bibr" rid="B81">Lima et al. (2019</xref>) that select the statistical features discussed in <xref ref-type="table" rid="T1">Table 1</xref>. The simulated data and real-time field data (from the substation) provide the two databases for the method validation that can discriminate an HIF with other power system disturbances. The method is efficient and accurate in action.</p>
<p>
<xref ref-type="bibr" rid="B16">Balser et al. (1982</xref>) utilized Hilbert transform (HT) for HIF detection in transmission lines in which an uncompensated line, series compensated line, single-pole tripping situation, and a load change are tested. The method is simulated in MATLAB/SIMULINK, and the data sampling rate is 1&#xa0;kHz. An HIF detector is placed in certain locations that indicate whether a fault occurred. The method gives good accuracy and consistency. The HIF detection method using optimal transient extracting transform (OTET) was proposed by <xref ref-type="bibr" rid="B99">Prasad et al. (2022</xref>) and can be used in grid-connected and islanded mode systems, and is also reliable in unbalanced and harmonic contaminated signals. <xref ref-type="bibr" rid="B25">Biswal et al. (2022</xref>) reconstructed the features extracted from the current signals using the Savitzky&#x2013;Golay filter (SGF) using the matrix pencil method (MPM), and the Teager energy of the error is estimated. The proposed method is verified in the Aalborg test feeder and modified IEEE 30-bus test systems and proven with an accuracy of 98.6%.</p>
</sec>
</sec>
</sec>
<sec id="s3">
<title>3 Test systems</title>
<p>In this section, various test systems are discussed for HIF detection. The various standard test systems were selected and simulated using MATLAB/SIMULINK, PSCAD, EMTP-RV, EMTP-ATP, and a real-time laboratory setup to investigate the performance of the different algorithms for HIF location and detection. Faults at the distribution system are a priority because the risk is greater relative to HIFs at the transmission level. An acceptable test system is selected for a suitable case study for simulation purposes and performance validation of the proposed methods. Proper data signals from the power system must be obtained under various possible operating scenarios to validate the proposed approaches. For technological and economic reasons, field fault testing on actual power systems is known to be difficult, with field test findings often having certain limitations. PDS must be correctly modeled because of these reasons. <xref ref-type="table" rid="T1">Table 1</xref> gives a detailed discussion of various signal processing techniques for HIF detection using intelligent classifiers with various test systems used. <xref ref-type="table" rid="T2">Table 2</xref> gives a comparison of various test systems used in HIF detection.</p>
<table-wrap id="T2" position="float">
<label>TABLE 2</label>
<caption>
<p>Comparison of various test systems.</p>
</caption>
<table>
<thead valign="top">
<tr>
<th align="center">Test system with ratings</th>
<th align="center">Methodology used</th>
<th align="center">Remarks</th>
</tr>
</thead>
<tbody valign="top">
<tr>
<td align="left">IEEE PSRC distribution of radials 11&#xa0;KV (<xref ref-type="bibr" rid="B98">Panigrahi et al., 2018</xref>)</td>
<td align="left">MM employs morphology gradient, and the statistical features are obtained from dilation and erosion</td>
<td align="left">Identify HIF occurrence in 0.08&#xa0;s</td>
</tr>
<tr>
<td align="left">Radial 13.8&#xa0;kV distribution feeder (<xref ref-type="bibr" rid="B149">Wali et al., 2018</xref>)</td>
<td align="left">FFT extracts features, which are then subjected to power spectrum analysis</td>
<td align="left">Power spectrum identifies the HIF occurrence with 100% accuracy</td>
</tr>
<tr>
<td align="left">Radial 13.8&#xa0;kV distribution feeder (<xref ref-type="bibr" rid="B140">Tawafan et al., 2012</xref>)</td>
<td align="left">FFT extracts features, and the classifier used is ANFIS.</td>
<td align="left">The success rate of detecting HIF cases was 97.8%, and that of non-HIF cases was 99%</td>
</tr>
<tr>
<td align="left">Radial distribution system, 115&#xa0;kV feeder (<xref ref-type="bibr" rid="B150">Wang et al., 2018</xref>)</td>
<td align="left">VCCP-based disturbance detection approach</td>
<td align="left">The wavelet correlation coefficient was calculated for various surfaces and was less than 0.966 for a healthy feeder</td>
</tr>
<tr>
<td align="left">Radial distribution system, 138&#xa0;kV (<xref ref-type="bibr" rid="B134">Soheili et al., 2018</xref>)</td>
<td align="left">Two approaches were compared. 1) Kalman filter and RF and 2) DT with FFT</td>
<td align="left">RF proved to be the best, with 93.56% accuracy and 94.56% dependability</td>
</tr>
<tr>
<td align="left">Radial distribution network, 13.8&#xa0;kV (<xref ref-type="bibr" rid="B146">Veerasamy et al., 2018</xref>)</td>
<td align="left">Feature extraction by CWT and DWT</td>
<td align="left">Accuracy 100%</td>
</tr>
<tr>
<td align="left">Radial distribution system, 138 V (<xref ref-type="bibr" rid="B103">Routray et al., 2016</xref>)</td>
<td align="left">Stockwell transform with ANN</td>
<td align="left">Accuracy 98.75%</td>
</tr>
<tr>
<td align="left">Radial distribution system, 138&#xa0;kV (<xref ref-type="bibr" rid="B90">Mishra et al., 2016</xref>)</td>
<td align="left">Stockwell transform for feature extraction. ANN and SVM as classifier</td>
<td align="left">For the ideal case, ST with ANN and ST with SVM give 100% accuracy, whereas with SNR 30&#xa0;dB, ST with ANN gives 93.7% and ST with SVM gives 92.15% accuracy</td>
</tr>
<tr>
<td align="left">Radial distribution system, 15&#xa0;kV (<xref ref-type="bibr" rid="B110">Samantaray et al., 2008</xref>)</td>
<td align="left">S transform and TT transform with PNN and FNN</td>
<td align="left">PNN with ST features provides a classification rate of up to 98.06%. PNN with features from TT transform provides a classification rate of up to 98.05%. FNN and S transform combination gives 93.04%, and that with TT transform gives 94.16% accuracy</td>
</tr>
<tr>
<td align="left">Radial distribution system, 33&#xa0;kV (<xref ref-type="bibr" rid="B116">Sarwagya et al., 2018</xref>)</td>
<td align="left">Measuring the residual voltage at the substation and negative sequence current flowing through the feeders</td>
<td align="left">The presence of the HIF is detected at 3 s</td>
</tr>
<tr>
<td align="left">Distribution system, 12.5&#xa0;kV (<xref ref-type="bibr" rid="B126">Shahrtash and Sarlak, 2006</xref>)</td>
<td align="left">Pattern recognition-based algorithm and DT as the classifier</td>
<td align="left">For different values of the sampling frequency, data window, and preprocessing time interval, the accuracy of the method is 99.4%</td>
</tr>
<tr>
<td align="left">Radial distribution network with 63&#xa0;kV (<xref ref-type="bibr" rid="B145">Vahidi et al., 2010</xref>)</td>
<td align="left">DWT extracts the features, and ANN is the classifier used along with the denoising method</td>
<td align="left">Accuracy is 99%</td>
</tr>
<tr>
<td align="left">Medium voltage distribution system from the city of Mostar with two-bus and eight-bus systems of 33&#xa0;kV (<xref ref-type="bibr" rid="B61">Hubana et al., 2018</xref>)</td>
<td align="left">Voltage phase difference algorithm and a combination of DWT with ANN</td>
<td align="left">Two-bus systems, the accuracy obtained is 92.5%, whereas the eight-bus system is 90.19%</td>
</tr>
<tr>
<td align="left">Electric power distribution system, Chennai, 33&#xa0;kV (<xref ref-type="bibr" rid="B122">Sekar and Mohanty, 2020</xref>)</td>
<td align="left">MG with fuzzy rule base algorithm</td>
<td align="left">Accuracy is 99.3%, and the computational time required is less</td>
</tr>
<tr>
<td align="left">Mesh distribution network, 25&#xa0;kV (<xref ref-type="bibr" rid="B108">Samantaray et al., 2009a</xref>)</td>
<td align="left">AEKF with PNN and FNN</td>
<td align="left">The accuracy rate of PNN is 99.11% compared to FNN with 96.51%</td>
</tr>
<tr>
<td align="left">Mesh distribution network, 138&#xa0;kV (<xref ref-type="bibr" rid="B134">Soheili et al., 2018</xref>)</td>
<td align="left">Two approaches were compared. 1) Kalman filter and RF and 2) DT with FFT</td>
<td align="left">RF proved to be the best with 93.56% accuracy and 94.56% dependability</td>
</tr>
<tr>
<td align="left">Mesh distribution network, 25&#xa0;kV (<xref ref-type="bibr" rid="B75">Lai et al., 2005</xref>)</td>
<td align="left">DWT and pattern recognition</td>
<td align="left">Error range 2.52% and 45.4%. It will not indicate the physical properties of the output coefficient</td>
</tr>
<tr>
<td align="left">Mesh distribution network, 138&#xa0;kV (<xref ref-type="bibr" rid="B90">Mishra et al., 2016</xref>)</td>
<td align="left">Stockwell transform for feature extraction. ANN and SVM as classifiers</td>
<td align="left">For the ideal case, ST with ANN and ST with SVM give 100% accuracy, whereas with SNR 30&#xa0;dB, ST with ANN gives 81% and ST with SVM gives 86% accuracy</td>
</tr>
<tr>
<td align="left">Mesh distribution network, 15&#xa0;kV (<xref ref-type="bibr" rid="B110">Samantaray et al., 2008</xref>)</td>
<td align="left">S transform and TT transform with PNN and FNN</td>
<td align="left">The accuracy of the mesh network with S transform and FNN is 92.86%, and that with TT transform and FNN is 93.55%. S transform and PNN combination gives 97.85% accuracy, and TT transform with PNN gives 97.09%</td>
</tr>
<tr>
<td align="left">IEEE 13-node test systems, 4.16&#xa0;kV (<xref ref-type="bibr" rid="B47">Fan and Yin, 2019</xref>)</td>
<td align="left">CNN and transfer learning algorithm</td>
<td align="left">The accuracy obtained was 95.06%</td>
</tr>
<tr>
<td align="left">IEEE 13-node test systems, 4.16&#xa0;kV (<xref ref-type="bibr" rid="B131">Silva et al., 2020</xref>)</td>
<td align="left">Wavelet packet-based feature extraction along with EuFNN classifier</td>
<td align="left">97.14% accuracy</td>
</tr>
<tr>
<td align="left">IEEE 13-node test systems, 4.16&#xa0;kV (<xref ref-type="bibr" rid="B117">Sarwar et al., 2020</xref>)</td>
<td align="left">PCA, Fisher discriminant analysis, binary and multi-class SVM</td>
<td align="left">Security and dependability of 100%</td>
</tr>
<tr>
<td align="left">IEEE 13-node test systems, 4.16&#xa0;kV (<xref ref-type="bibr" rid="B134">Soheili et al., 2018</xref>)</td>
<td align="left">FFT approach and harmonic analysis of the sum of all three-phase currents</td>
<td align="left">Detection time is 1.5&#xa0;s</td>
</tr>
<tr>
<td align="left">IEEE 13-node test systems, 4.16&#xa0;kV (<xref ref-type="bibr" rid="B123">Sekar and Mohanty, 2017</xref>)</td>
<td align="left">MM and DT</td>
<td align="left">The detection time is 30&#xa0;m. Performance indices are 99%. Accuracy is 98.33%</td>
</tr>
<tr>
<td align="left">IEEE 13-node test systems, 4.16&#xa0;kV (<xref ref-type="bibr" rid="B55">Gautam and Brahma, 2013</xref>)</td>
<td align="left">MM that can be implemented on a conventional over current relay</td>
<td align="left">The success rate of detection and classification is 100%</td>
</tr>
<tr>
<td align="left">IEEE 13-node test systems (<xref ref-type="bibr" rid="B31">Chen et al., 2014</xref>)</td>
<td align="left">DWT with MRA</td>
<td align="left">Fast, economical, and efficient</td>
</tr>
<tr>
<td align="left">IEEE 13-node test systems (<xref ref-type="bibr" rid="B151">Wang et al., 2019</xref>)</td>
<td align="left">Variational mode decomposition (VMD) and Teager&#x2013;Kaiser energy operators (TKEOs)</td>
<td align="left">Calculation time is 0.0028 s</td>
</tr>
<tr>
<td align="left">IEEE 34-node test system, 24.9&#xa0;kV (<xref ref-type="bibr" rid="B92">Moravej et al., 2015</xref>)</td>
<td align="left">Dual-tree complex wavelet transforms for feature extraction and PNN for classification</td>
<td align="left">PNN requires no iteration. Detection time 1.5&#xa0;m. The error of detection is 1.4%. The proposed algorithm gives an accuracy of 98.88%</td>
</tr>
<tr>
<td align="left">IEEE 34-node test system, 24.9&#xa0;kV (<xref ref-type="bibr" rid="B47">Fan and Yin, 2019</xref>)</td>
<td align="left">CNN and transfer learning algorithm</td>
<td align="left">The accuracy of CNN obtained is 99.52%</td>
</tr>
<tr>
<td align="left">IEEE 34-node test, 24.9&#xa0;kV (<xref ref-type="bibr" rid="B123">Sekar and Mohanty, 2017</xref>)</td>
<td align="left">MM and DT</td>
<td align="left">The detection time is 30&#xa0;m. Performance indices are 99%. Accuracy is 98.33% at lightly loaded conditions</td>
</tr>
<tr>
<td align="left">IEEE 34-node test, 24.9&#xa0;kV (<xref ref-type="bibr" rid="B151">Wang et al., 2019</xref>)</td>
<td align="left">Variational mode decomposition (VMD) and Teager&#x2013;Kaiser energy operators (TKEOs)</td>
<td align="left">Calculation time is 0.0028 s</td>
</tr>
<tr>
<td align="left">IEEE 13-node test systems (<xref ref-type="bibr" rid="B31">Chen et al., 2014</xref>)</td>
<td align="left">DWT with MRA</td>
<td align="left">Fast, economical, and efficient</td>
</tr>
<tr>
<td align="left">IEEE four-node test feeder, 12.47&#xa0;kV (<xref ref-type="bibr" rid="B113">Sarlak and Shahrtash, 2008</xref>)</td>
<td align="left">PCA and LDA with SVM</td>
<td align="left">Accuracy is 97.5% compared to Bayes and Parzen classifiers</td>
</tr>
<tr>
<td align="left">IEEE-123 distribution feeder, 4.16&#xa0;kV (<xref ref-type="bibr" rid="B144">Tonelli-Neto et al., 2017</xref>)</td>
<td align="left">DWT with a fuzzy interference system and Fuzzy ARTMAP neural network combination based on Dempster&#x2013;Shafer evidence theory</td>
<td align="left">The accuracy of FANN is 97.69%, and that of FIS is 99.25%</td>
</tr>
<tr>
<td align="left">Palash feeder, Tehran, 63&#xa0;kV (<xref ref-type="bibr" rid="B114">Sarlak and Shahrtash, 2011</xref>)</td>
<td align="left">TT transform, ART neural networks, and Fuzzy ARTMAP</td>
<td align="left">Accuracy of 99.18%. Five-class classification</td>
</tr>
<tr>
<td align="left">Palash feeder, Tehran, 63&#xa0;kV (<xref ref-type="bibr" rid="B115">Sarlak and Shahrtash, 2013</xref>)</td>
<td align="left">MM and SVM</td>
<td align="left">Security of 96.9% and dependability of 97.2%</td>
</tr>
<tr>
<td align="left">Palash feeder, Tehran, 63&#xa0;kV (<xref ref-type="bibr" rid="B97">Nikoofekr et al., 2013</xref>)</td>
<td align="left">Multi-resolution MG and MLPNN</td>
<td align="left">Superior to other feature extraction techniques, such as DWT, DFT, DST, and DTT. Security of 92.8%, dependability of 96.4%</td>
</tr>
<tr>
<td align="left">Palash feeder, Tehran, 63&#xa0;kV (<xref ref-type="bibr" rid="B134">Soheili et al., 2018</xref>)</td>
<td align="left">FFT approach and harmonic analysis of the sum of all three-phase currents</td>
<td align="left">Detection time is 1.13 s</td>
</tr>
<tr>
<td align="left">CERTS microgrids, 480 V (<xref ref-type="bibr" rid="B50">Gadanayak and Mallick, 2019</xref>)</td>
<td align="left">MODWT and Knot-based EMD</td>
<td align="left">Classification accuracy of 99.77%. The mean detection time is 0.12 s</td>
</tr>
<tr>
<td align="left">Test microgrid system, 120&#xa0;kV (<xref ref-type="bibr" rid="B68">Kar and Samantaray, 2017</xref>)</td>
<td align="left">MODWT and DT</td>
<td align="left">The detection time is 0.12 s. Accuracy of 100%</td>
</tr>
<tr>
<td align="left">IEC standard microgrid,<break/>25&#xa0;kV (<xref ref-type="bibr" rid="B52">Gashteroodkhani et al., 2020</xref>)</td>
<td align="left">Deep-belief neural network with time&#x2013;time transform</td>
<td align="left">Accuracy of 99.74% and 99.46% radial network with grid-connected and islanded modes, respectively, and 100% for mesh topology in both modes of operation</td>
</tr>
<tr>
<td align="left">Test microsystem (CERTS), 13.8&#xa0;kV (<xref ref-type="bibr" rid="B3">Abdelgayed et al., 2017</xref>)</td>
<td align="left">DWT, DT, and k-nearest neighbor</td>
<td align="left">The experimental result of DT is 100%, and that of KNN is 95%</td>
</tr>
<tr>
<td align="left">JMARTY model test system, 500&#xa0;kV (<xref ref-type="bibr" rid="B41">Eldin et al., 2007</xref>)</td>
<td align="left">DWT and moving window-based pattern recognition</td>
<td align="left">Simple, accurate, and fast technique for EHV transmission lines. The algorithm can be applied to an already existing digital relay microprocessor</td>
</tr>
<tr>
<td align="left">JMARTY model test system, 500&#xa0;kV (<xref ref-type="bibr" rid="B62">Ibrahim et al., 2008</xref>)</td>
<td align="left">DWT and moving window-based pattern recognition</td>
<td align="left">Simple, accurate, and fast technique for EHV transmission lines. The algorithm can be applied to an already existing digital relay microprocessor</td>
</tr>
<tr>
<td align="left">Tai-16 feeder, 11.4&#xa0;kV (<xref ref-type="bibr" rid="B155">Yang et al., 2006</xref>)</td>
<td align="left">Wavelet transforms and pattern recognition-based feature extraction with backpropagation ANN</td>
<td align="left">The detection rate is 81%</td>
</tr>
<tr>
<td align="left">Benchmark system, 25&#xa0;kV (<xref ref-type="bibr" rid="B37">Cui et al., 2017</xref>)</td>
<td align="left">The signal processing technique of DFT and Kalman filtering estimation and classifiers such as Native Bayer&#x2019;s, SVM (Gaussian kernel), KNN, RF, and J48 are compared</td>
<td align="left">RF and J48 proved to be the best, with 99% accuracy for both</td>
</tr>
<tr>
<td align="left">Test system, 38 nodes, 132&#xa0;kV (<xref ref-type="bibr" rid="B6">Ali et al., 2014</xref>)</td>
<td align="left">DWT for feature extraction and matching approach technique is used for classification</td>
<td align="left">Identify the faulty section in four or five iterations</td>
</tr>
</tbody>
</table>
</table-wrap>
<sec id="s3-1">
<title>3.1 Radial distribution network</title>
<p>
<xref ref-type="bibr" rid="B126">Shahrtash and Sarlak (2006</xref>) used a pattern recognition-based approach for HIF detection with DT as the classifier. The power distribution system is illustrated in which the system voltage is 12.5&#xa0;kV, the short circuit level (at the infinite bus) is 866 MVA, and a time constant of 45&#xa0;ms is shown in <xref ref-type="fig" rid="F4">Figure 4A</xref>. The following data about transmission lines are given inductance of transmission line of 825&#xa0;nH/m, resistance of transmission of 313&#xa0;&#x2126;/m, and line length of 33&#xa0;km. The loads connected are a capacitor load rated 4.08 MVAr, transformer (10/0.4&#xa0;kV) connected in delta-star, three-phase thyristor converter as harmonic load, and nominal load current of 630 A. The best results are obtained in even, odd, and in-between harmonics below 400&#xa0;Hz. The classification factor is based on entropy, which is the effectiveness of an attribute in classifying data. A total of 2,583 and 1,331 cases were used for training and testing purposes, respectively. For different values of the sampling frequency of 2&#xa0;kHz, a data window size of 2 cycles, and a pre-processing-time interval of 30 cycles, the accuracy of the proposed method was 99.4%.</p>
<fig id="F4" position="float">
<label>FIGURE 4</label>
<caption>
<p>(Continued)</p>
</caption>
<graphic xlink:href="fenrg-11-1114230-g004.tif"/>
</fig>
<p>
<xref ref-type="bibr" rid="B145">Vahidi et al. (2010</xref>) used the DWT technique to extract the features, and ANN classifies the faulty cases with other power system disturbances. A three-phase radial distribution network is modeled using the PSCAD/EMTDC software used as the test system. The power system frequency is 50&#xa0;Hz, and the power is supplied at 63&#xa0;kV from a 30-MVA transformer (wye/delta). The transformers and line parameters are shown in <xref ref-type="fig" rid="F4">Figure 4C</xref>. Line currents during the HIF have high-frequency components and are used for feature extraction. The extracted features are decomposed into two levels of detailed and approximation coefficients at six cycles. The performance of the DWT-based denoising technique depends on the threshold value <inline-formula id="inf1">
<mml:math id="m1">
<mml:mrow>
<mml:mi>&#x3b3;</mml:mi>
<mml:mo>,</mml:mo>
</mml:mrow>
</mml:math>
</inline-formula> which can be divided into hard thresholding and soft thresholding. A large value of <inline-formula id="inf2">
<mml:math id="m2">
<mml:mrow>
<mml:mi>&#x3b3;</mml:mi>
</mml:mrow>
</mml:math>
</inline-formula> will shrink most of the coefficients to zero and for small values, denoising outcomes are inefficient. The extracted data are trained and compared with six different types of mother wavelet transforms: haar, coif2, dmey, db9, bior2.6, and sym8. Sym8 gives the best performance and accuracy. The sampling rate chosen is 20&#xa0;kHz. A multi-layer perceptron neural network (MLPNN) with a Levenberg&#x2013;Marquardt algorithm is used. The effect of SNR on the proposed algorithm is also studied. The HIF model is introduced to buses 2 and 3 to mimic the HIFs that exist on different ground conditions, such as sand, wet soil, dry soil, asphalt, and grass, giving an accuracy of 99%.</p>
<p>The system tested by <xref ref-type="bibr" rid="B140">Tawafan et al. (2012</xref>) is a 115-kV distribution feeder comprised of a substation, and three radial network distribution feeders are shown in <xref ref-type="fig" rid="F4">Figure 4B</xref>. The generator is 30&#xa0;kV and 10&#xa0;MV connected to the 30/13.8-kV and 10-MV transformers. The 6-pulse rectifier is used for the representation of the non-linear load. The simulation models are created using PSCAD, and the sampling rate is 15.36&#xa0;kHz. FFT is the feature extraction technique used, with an algorithm based on the adaptive neural Takagi&#x2013;Sugeno&#x2013;Kang (TSK) fuzzy modeling scheme, where the HIF detection is performed by taking the amplitude of the ratio of the second and odd harmonics to fundamental harmonics of the current signals that serve as input to ANFIS. The fundamental harmonics are decreased when the fault has occurred. A total of 570 cases are taken, among which 138 cases are HIFs and 432 are non-HIFs. The mean squared error value of the model is 0.1163, and based on the output of ANFIS, if the HIF current is greater than 0.6 it indicates HIF conditions and if it is less than 0.4; it is non-HIF conditions. The detection accuracy of HIF cases is 97.8%, and non-HIFs is 99%. The method was proposed by <xref ref-type="bibr" rid="B134">Soheili et al. (2018</xref>). The harmonic components of the third, fifth, seventh, eleventh, and thirteenth HIF current are preprocessed in an EKF, and 12 features are extracted. These features of one-, two-, and three-cycle windows are considered the input to train the RF. RF is trained with 20,580 and 8,820 data sets. The SNR chosen is 20&#xa0;dB. Two separate, three-phase sources are connected through transformers to a transmission line of length 100&#xa0;km. The transmission lines are 138&#xa0;kV, and the transformers are 50 MVA, supplying at 138/25&#xa0;kV to the distribution network (<xref ref-type="fig" rid="F4">Figure 4D</xref>).</p>
<p>The distribution feeders (pi sections of 20&#xa0;km each) work at 25&#xa0;kV and are connected with shunt capacitors, linear loads, and a 2-MVA 6-pulse rectifier load (non-linear load). The resistance, inductance, and capacitance of positive and zero sequences of transmission lines are as follows: R<sub>1</sub> &#x3d; 0.01273&#xa0;&#x2126;/km, X<sub>1</sub> &#x3d; 0.9337&#xa0;mH/km, C<sub>1</sub> &#x3d; 0.0012 lF/km and R<sub>0</sub> &#x3d; 0.3864&#xa0;&#x2126;/km, X<sub>0</sub> &#x3d; 4.1264&#xa0;mH/km, and C<sub>0</sub> &#x3d; 0.0075 lF/km, respectively. The resistance, inductance, and capacitance of distribution lines (pi-section) are R<sub>1</sub> &#x3d; 0.2568&#xa0;&#x2126;/km, X<sub>1</sub> &#x3d; 2.0&#xa0;mH/km, and C<sub>1</sub> &#x3d; 0.0086, respectively. The total percentage impedance of the transformers is 6.75%. The simulation models are developed using PSCAD (EMTDC), and the sampling rate chosen is 1.0&#xa0;kHz on a 50-Hz base frequency (20 samples per cycle). RF proved to be the best, with 93.56% accuracy and 94.56% dependability. A multi-feeder radial distribution system was proposed by <xref ref-type="bibr" rid="B116">Sarwagya et al. (2018</xref>) to detect and segregate HIFs. It consists of a 30-MVA, 33-kV substation, and five numbers of 11&#xa0;kV radial distribution feeders. The positive-sequence impedance of the distribution line is 0.3 &#x2b; j0.25&#xa0;&#x3a9;/km. The discrimination of the HIF is performed based on two criteria. The first is based on the maximum value of the one-cycle sum of superimposed components of negative-sequence current for faulty feeder identification, and the second is based on the one-cycle sum of superimposed components of residual voltage for HIF detection. The substation bus provides the residual voltage. The negative sequence current of all the feeders is compared, and the maximum value of the negative sequence will be for the feeder where HIF has occurred. The HIF is accurately detected in 3 s with the proposed method. The performance of the method with HIF during unbalanced loading, unbalanced loading conditions, capacitor switching, and occurrence of an HIF in various feeders is analyzed. <xref ref-type="bibr" rid="B114">Sarlak and Shahrtash (2011</xref>) compared two approaches for HIF identification: the voltage phase difference algorithm and a combination of DWT and ANN. The test system chosen is from Bosnia and Herzegovina, a distribution system like in Europe. The article includes two test systems: a two-bus feeder system and the other is an eight-bus system. The two-bus system is a simple one with a main transformer of 35/10&#xa0;kV, whereas the latter one is more complex, consisting of 8 feeders fed from 35/10&#xa0;kV, with underground cables and a transformer at the end consumers rating at 10/0.4&#xa0;kV. <xref ref-type="fig" rid="F4">Figures 4E, G</xref> represent two- and eight-bus systems, respectively. The sampling frequency is 3.2&#xa0;kHz. The first method DWT is applied to the measured voltage signals. Each voltage has four detailed coefficients and one approximation coefficient. An algorithm is proposed in which DWT signals are combined, representing a signature for symmetrical and unsymmetrical faults. These data are then used to train and test the ANN. A total of 1,600 cases are simulated, including non-faulty conditions and three types of fault conditions. The method gives an accuracy of 100% for the 20&#x2013;600&#xa0;&#x3a9; range of fault resistances and at different fault locations. In the second method, a voltage measurement is performed, and the Hilbert transform is applied to obtain the best features. The best feature is an instantaneous frequency, which represents the time rate of change of the instantaneous phase angle. The phase difference is calculated by the difference between the instantaneous phases of voltage signals. The voltage phase difference algorithm calculates the PD during normal and fault conditions. At normal working operation, the phase difference will be 120<sup>0</sup>, and during each fault condition, the phase difference will be different. This parameter is used to detect and classify the fault. With 2,000 cases in two-bus systems, the accuracy obtained is 92.5%, whereas the eight-bus system showed 90.19%. <xref ref-type="bibr" rid="B98">Panigrahi et al. (2018</xref>) used the IEEE Power System Relaying Committee Working Group at medium voltage levels. A simple 11-kV radial distribution feeder with eight nodes is shown in <xref ref-type="fig" rid="F4">Figure 4F</xref>. MATLAB/SIMULINK program is selected and modeled, and the line impedance (positive sequence) is chosen as 0.3&#xa0;&#x2126;/km &#x2b; j 0.25&#xa0;&#x2126;/km. At a distance of 5&#xa0;km, nodes are isolated from each other, in which nodes 1, 3, 5, and 7 are connected to linear capacity loads of 1 MVA each at power factor 0.9/phase, and nodes 2, 4, 6, and 8 are linked to linear capacity loads of 2&#xa0;MVA each at power factor 0.9/phase. The method discussed the MM gradient for HIF detection and classified HIF, LIF, capacitor switching, and load switching (balanced and unbalanced).</p>
<p>The proposed method measures the three-phase voltage at a relay location and evaluates the residual voltage. The morphology gradient is used to extract the irregularities in the voltage signal. The extracted feature index is determined from the zero-energy index at NC and compared with a predefined threshold value. The extracted feature index value will jump slightly for HIF, LIF, and other disturbances for faulty conditions. An HIF is created at nodes 1, 4, and 9, and the occurrence will be for 1&#xa0;s. The method accurately detects HIF occurrence in 0.8&#xa0;s. The test system model proposed by <xref ref-type="bibr" rid="B149">Wali et al. (2018</xref>) is a 13.8-kV radial distribution feeder simulated by MATLAB/SIMULINK under different scenarios, such as linear load, non-linear load, and several other conditions. <xref ref-type="fig" rid="F4">Figure 4H</xref> shows a single-line representation, a three-phase transformer, and a 13.8-kV distribution network. The non-linear load is represented by a 6-pulse rectifier that creates non-linear features in the feeder. The method used for HIF detection is FFT for feature extraction, and the power spectrum technique is used to identify the fault, which gives an accuracy rate of 100%, the time required is less, and that does not require any level of training. FFT extracts the feature of the current signal from the faulty feeder, and the power spectrum of the time signal is determined using the function FFT. If PS is less than 0.005, then a HIF occurs. HIF of 250 cases and other power system disturbances of 750 cases have been analyzed in this study. The method distinguishes events due to capacitor banks, non-linear loads, linear loads, and HIF.</p>
<p>The test system used for HIF detection (<xref ref-type="bibr" rid="B146">Veerasamy et al., 2018</xref>) consists of a grid source of 50&#xa0;MVA/30&#xa0;kV, a distribution transformer (12&#xa0;MVA, 30&#xa0;kV/13.8&#xa0;kV), a common bus of 13.8&#xa0;kV, and five radial type distribution feeders, integrated into the load facility. An Emanuel two-diode model consisting of two variable DC voltage sources of 1&#x2013;10&#xa0;kV connected to anti-parallel diodes by non-linear resistors of 50&#x2013;500&#xa0;&#x2126; is considered an HIF model with non-linear arc characteristics. The method is proposed by extracting the features using CWT and DWT and classifying the extracted features by ANFIS. CWT gives the region at which the fault has occurred, and DWT can locate it by calculating the standard deviation (SD) using a five-level decomposition. The extracted SD values of different fault conditions with different values of fault resistance from the detailed and approximation coefficients are obtained, which are used to train classifiers FLS and ANFIS. Various faults, such as symmetrical, unsymmetrical, and HIFs, were tested using MATLAB/SIMULINK. The classification rate of ANFIS is 100%, which proved more effective than FLS. <xref ref-type="bibr" rid="B150">Wang et al. (2018</xref>) proposed that an HIF detection algorithm identifies the non-linear voltage&#x2013;current characteristic profiles (VCCP) for identifying an HIF in the MV distribution system. During HIF, the zero-sequence current is less than the positive-sequence current. The slope of the VCCP is the numerical difference between voltage data from current sample data, and the least square linear fitting method is proposed. The wavelet correlation coefficient (WCC) is considered to improve the reliability of the algorithm. If WCC is greater than 0.966, the metered data are from a faulty feeder, and if less than the value, it is a healthy feeder. The radial distribution system is the test system in <xref ref-type="fig" rid="F4">Figure 4J</xref> that uses EMTP/ATP program. The typical Mayr arc model is simulated and drawn in series with constant resistance using a switcher and parallel branches. The simulation time stage was set at 2&#xa0;&#x3bc;s field-metered data from KEPCo, South Korea, and HIF experiments were performed on a 22.9-kV no-load overhead feeder to check the simulations. As it is a no-load feeder, the zero-sequence current and phase voltage were used at a faulty feeder outlet to correctly estimate the fault point voltage and fault branch current. The faults have been tested on various dry surfaces. The algorithm showed excellent results in real-time digital simulator tests. The test system proposed by <xref ref-type="bibr" rid="B120">Sedighi et al. (2005b</xref>) for HIF tests and data collection is a radial feeder of 20&#xa0;kV at Qeshm Island, Iran, as shown in <xref ref-type="fig" rid="F4">Figure 4K</xref>. The feeder is energized from another 20-kV feeder by two distribution transformers (20/0.4&#xa0;kV, 100&#xa0;kV&#xa0;A) connected back-to-back. The HV and LV connections of the transformers are delta/star connected. The HV sides of the transformers are connected to feeders, and the LV sides are connected to the low-voltage switch. Three-phase voltages and currents were monitored and recorded using Hall effect current transformers, potential transformers (PT), power analyzers, and computers. The sampling rate of the recorded data was 24,670&#xa0;kHz for each test, and the overall recorded time was 15&#xa0;s. The method used for HIF detection uses WT for feature extraction with a three-level decomposition of current signals. The first method uses GA for feature vector reduction, and the Bayes classifier is used for classification. In the first method, coefficients of three-level decomposition are used for feature extraction. They are divided into 10, 5, and 5 segments. In GA, each segment is mapped to a 20-dimensional space. A space with 20 dimensions is mapped to a space with five dimensions. The Bayes classifier is used to classify the mapped space. In the second method, WT transforms are also applied for the current signals, PCA is used for feature vector reduction, and NN is the classifier. The coefficients of three-level decomposition are used for feature extraction, divided into 10, 5, and 5 segments. Means of the absolute value of each segment were chosen as features, and the extracted signals were mapped to a 20-dimensional space. Using PCA, space was reduced to a 7-dimensional space. A perceptron NN using backpropagation discriminates between HIF, isolator leakage current, and other power system transients. <xref ref-type="bibr" rid="B122">Sekar and Mohanty (2020</xref>) stated that morphology gradient extracts the features of which a rule is set by RF and then fed to a fuzzy rule-based algorithm for HIF detection. The electric power distribution system (EPDS) was modeled using MATLAB/SIMULINK. A three-phase shunt capacitor of 1 Mvar has been connected to the busbar to improve power quality and output. The inrush current of a transformer produces an asymmetrical current signal that may serve as a transient signal generated by switching that may be like the HIF current waveform. An induction motor is connected as a load to study the motor operation impacts. The EPDS uses linear and non-linear loads to simulate the loading scenario, as shown in <xref ref-type="fig" rid="F4">Figure 4I</xref>. One cycle window length of the current signal is measured, the impulsive feature of the signal is extracted, and a rule set is created from the statistical features of RF. The sampling frequency is 1,000&#xa0;Hz, and the signal length is 0.5&#xa0;s. The periodic signal has third- and fifth-order harmonics, and other harmonics that are negligible make the filter closer to HIF detection. The method effectively detects an HIF from other power system disturbances.</p>
</sec>
<sec id="s3-2">
<title>3.2 Mesh distribution network</title>
<p>The test system proposed by <xref ref-type="bibr" rid="B75">Lai et al. (2005</xref>) consists of two 50&#xa0;MVA generators with 25&#xa0;kV lines, two transformers, and linear and non-linear loads. In DWT, db4 was chosen as the mother wavelet, with a downsampling frequency chosen as 9,600&#xa0;Hz, used to extract the detailed and approximation coefficients from the signals of the HIF and non-fault. The current and voltage signals at a targeted circuit breaker are measured. The RMS values of the measured quantities at various frequencies are analyzed and given as input to the nearest neighbor to classify fault signals. The HIF and non-HIF cases (1,000 cases each) were simulated with HIF and LIF models. The range of total error corresponding to the RMS value of the voltage wavelet coefficient is from 2.52% to 45.4% and will not indicate the physical properties of the output coefficient.</p>
<p>
<xref ref-type="bibr" rid="B110">Samantaray et al. (2008</xref>) reported that S transform and TT extract the features, and FNN and PNN classify the faulty and non-faulty conditions of the HIF. The ST features are extracted from the HIF and normal fault current signals for half-cycle current signals after fault inception. The energy and SD of time and frequency information are considered feature sets. These features are used to train and test the FNN for radial and mesh networks. TT transform also extracts energy and SD of the TT-counter and time index after fault inception for the first half-cycle of the fault current. A total of 500 cases are simulated for training and testing the classifier. The system is modeled in MATLAB/SIMULINK, and the sampling rate chosen is 1&#xa0;kHz. The PNN classification is based on the distribution values of the probability density function. The classification rate of a radial network with PNN using ST features is up to 98.06%. PNN with TT transform features gives a classification rate of up to 98.05%. The accuracy of the FNN and S transform combination is 93.04%, and the accuracy of the TT transform is 94.16%. The proposed method is also tested in a mesh network. The accuracy of the mesh network with S transform and FNN is 92.86%, and that with TT transform and FNN is 93.55%. The S transform and PNN combination gives 97.85% accuracy, and the TT transform and PNN combination gives 97.09% accuracy.</p>
<p>The HIF detection method used by <xref ref-type="bibr" rid="B108">Samantaray et al. (2009a</xref>) is a combination of AEKF with FNN and PNN. The schematic diagram of the test system chosen is given in Figure 5. The base voltage of the distribution network is 25&#xa0;kV, and the generator is 10 MVA, 15&#xa0;kV capacity. The harmonic components estimated by the AEKF are fundamental, third, fifth, seventh, eleventh, and thirteenth harmonics for the HIF and NF under non-linear loads. The AEKF calculates the harmonic component within half a cycle of the fault occurrence, with the peak of the estimated harmonic component considered that inputs to PNN and FNN. The PNN classification is based on the probability density function&#x2019;s distribution values. PNN is analyzed using a data set with an SNR of 20&#xa0;dB, 300 data sets for training, and 200 data sets for testing. For the classification, PNN takes 0.1&#xa0;s time, whereas FNN takes 0.2&#xa0;s. Fault and non-fault conditions with non-linear switching (a six-pulse rectifier is used) are checked using various models of MATLAB/SIMULINK, and the sampling rate chosen is 1.6&#xa0;kHz. The accuracy rate of PNN is 99.11% compared with FNN having 96.51%.</p>
<p>The detection of HIF described by <xref ref-type="bibr" rid="B103">Routray et al. (2016</xref>) uses a test system with a generator of 50&#xa0;MVA supplying 138&#xa0;KV of voltage to the utility sector through a transmission line 100&#xa0;km long, and a 138/25-kV star/delta transformer is considered for testing the method. The method uses ST for feature extraction and ANN for discriminating the HIF with load switching, capacitor switching, and NC. The time and frequency information is extracted from the S matrix, and the amplitude factor is calculated from current signals. A total of 4,010 cases were considered, of which 60% is used for training and 40% for testing. The overall accuracy of classifiers for normal fault is 98.75%, 96.4%, 94.06%, and 92.60% for normal (without noise) and noisy conditions.</p>
<p>
<xref ref-type="bibr" rid="B109">Samantaray (2012</xref>) studies two test systems: one with a radial feeder mentioned in <xref ref-type="fig" rid="F5">Figure 5</xref> and the other with a mesh feeder given in <xref ref-type="fig" rid="F7">Figure 7C</xref>. The test system studied is connected to a 50-MVA generator and a transformer of 138/25&#xa0;kV from a transmission line of 138&#xa0;kV and a length of 100&#xa0;km. Loads are connected with linear and non-linear loads. The resistance, inductance, and capacitance of positive and zero sequences of transmission lines are R<sub>1</sub> &#x3d; 0.01273&#xa0;&#x2126;/km, X<sub>1</sub> &#x3d; 0.9337&#xa0;mH/km, C<sub>1</sub> &#x3d; 0.0012 lF/km and R<sub>0</sub> &#x3d; 0.3864&#xa0;&#x2126;/km, X<sub>0</sub> &#x3d; 4.1264&#xa0;mH/km, and C<sub>0</sub> &#x3d; 0.0075&#xa0;lF/km, respectively. The resistance, inductance, and capacitance of distribution lines (pi-section) are R<sub>1</sub> &#x3d; 0.2568&#xa0;&#x2126;/km, X<sub>1</sub> &#x3d; 2.0&#xa0;mH/km, and C<sub>1</sub> &#x3d; 0.0086, respectively. The total percentage impedance of the transformers is 6.75%. The simulation models are developed using PSCAD (EMTDC), and the sampling rate chosen is 1.0&#xa0;kHz on a 50-Hz base frequency (20 samples per cycle). RF proved to be the best, with 93.56% accuracy and 94.56% dependability. On the distribution feeder, the HIF faults are generated at 25 kV, 20 km, pi section. Different simulation conditions are also considered, such as three-phase loadings, single-phase loadings, transformer energizations, shunt capacitor switching, and HIF by varying DC voltage sources. Two combinations of the HIF detection technique are proposed: the first is an EKF and RF and the latter is DT with FFT. The harmonic components of the third, fifth, seventh, eleventh, and thirteenth HIF current are preprocessed in an EKF, and 12 features are extracted. These features of one-, two-, and three-cycle windows are considered in this work. Considering the two-cycle window and with SNR set at 20&#xa0;db. The simulation models are developed using PSCAD (EMTDC), and the sampling rate chosen is 1.0&#xa0;kHz. RF is trained with 20,580 data sets, and 8,820 data sets are tested. RF proved to be the best, with 93.56% accuracy and 94.56% dependability compared with DT.</p>
<fig id="F5" position="float">
<label>FIGURE 5</label>
<caption>
<p>Three-phase meshed network.</p>
</caption>
<graphic xlink:href="fenrg-11-1114230-g005.tif"/>
</fig>
<p>
<xref ref-type="bibr" rid="B90">Mishra et al. (2016</xref>) used S transform with ANN and SVM to discriminate the HIF from other power system disturbances. A total of 4,000 cases, including HIF, normal, load switching, capacitor switching, and normal faults, are taken. Features are extracted from three-phase currents measured from the bus, and the best feature vector is selected. MLPNN with backpropagation NN and SVM along with ST is used, with 60% data for training and 40% for testing. The distribution model with a radial pattern of a 50-MVA generator is connected to a 100-km-long transmission line and a 138/25-kV star/delta transformer to supply 138&#xa0;kV voltage to the utility sector. For the ideal case, ST with ANN and ST with SVM give 100% accuracy, whereas with SNR 30&#xa0;dB, ST with ANN gives 93.7% and ST with SVM gives 92.15% accuracy. For the ideal case with the mesh network, ST with ANN and ST with SVM give 100% accuracy, whereas with SNR 30&#xa0;dB, ST with ANN gives 81% and ST with SVM gives 86% accuracy.</p>
</sec>
<sec id="s3-3">
<title>3.3 Palash feeder, Tehran</title>
<p>Detection of the HIF using a combination of MLPNN based on multi-resolution morphological gradient features of the current waveform is described by <xref ref-type="bibr" rid="B114">Sarlak and Shahrtash (2011</xref>). The MMG features of the current signals (for three half-cycles) of broken and unbroken conductors are considered, and the features from DFT, DTT, DST, and DWT are compared. The morphology gradient is the difference between the dilation and erosion functions. Data acquisition is performed using the ION7650 meter, and the input port of the meters is connected to the outputs of the current transformers at the 63/20-kV substation. The sampling rate of the current waveform is 1.6&#xa0;kHz. A disturbance detection module is based on MMG-extracted features of any subwindow with a predefined threshold. Three MLPNNs (A, B, and C) are trained individually by applying the time-based features obtained from the first, second, and third sub-windows. Then, their decisions are concatenated to make the final decision. The proposed algorithm gives security of 96.3% and dependability of 98.3%.</p>
<p>
<xref ref-type="bibr" rid="B97">Nikoofekr et al. (2013</xref>) used a test system from Tehran, Iran, which has a 63/20-kV transformer feeder with 30&#xa0;MVA apparent power, and the HV side has been grounded with a zigzag transformer and variable resistance adjusted at 29.5&#xa0;&#x2126;. Moreover, two 2.4-MVAR capacitor banks are connected through the HV circuit breakers. The ION 7,650-meter tests the HIF current and non-HIF current signals, such as insulator leakage current (ILC) and harmonic load current, with a sampling rate of 64 samples per cycle at the site. The method uses ST for phase correction in CWT, which localizes the phase and amplitude spectrum. TT transform extracts the features of the measured signals. Five different ART neural networks are used to classify the HIF and tested with broken conductors in asphalt, concrete, gravel surfaces and unbroken conductor on trees and under no fault conditions. This study uses five types of ART networks, namely, ART1, ART2, ART2-A, Fuzzy ART, and Fuzzy ARTMAP. The different features extracted were energy, SD, and median absolute deviation. The performance of the ART network is based on the vigilance parameter <inline-formula id="inf3">
<mml:math id="m3">
<mml:mrow>
<mml:mi>&#x3c1;</mml:mi>
</mml:mrow>
</mml:math>
</inline-formula> whose value ranges from 0 to 1. For lower values of <inline-formula id="inf4">
<mml:math id="m4">
<mml:mrow>
<mml:mi>&#x3c1;</mml:mi>
</mml:mrow>
</mml:math>
</inline-formula>, the classification is rough, and categories are less, and for higher values of <inline-formula id="inf5">
<mml:math id="m5">
<mml:mrow>
<mml:mi>&#x3c1;</mml:mi>
</mml:mrow>
</mml:math>
</inline-formula> the categories are more, and classification is fine. In the basic ART training process, the input pattern is delivered to the input layer, which activates F2 neurons <italic>via</italic> bottom-up weights. Because the F2 layer is a competitive layer, the neurons compete with each other to learn the input vector, and the larger neuron wins. All other F2 units&#x2019; activations (outputs) are set to zero. Then, the top-down weights of the winner neuron are sent back to the F1 layer. <xref ref-type="fig" rid="F6">Figure 6</xref> shows the Palash feeder in Tehran. From the total 6,437 data taken, 60% were used for training and 40% for testing. The result of the network shows an accuracy of ART1 of 91.61%, ART2 of 98.65%, ART2-A of 99%, Fuzzy ART of 99.18%, and Fuzzy ARTMAP of 99.18%.</p>
<fig id="F6" position="float">
<label>FIGURE 6</label>
<caption>
<p>Palash feeder single-line diagram.</p>
</caption>
<graphic xlink:href="fenrg-11-1114230-g006.tif"/>
</fig>
<p>MMG is the feature extraction used by <xref ref-type="bibr" rid="B115">Sarlak and Shahrtash (2013</xref>) and tested on the Palash feeder in the Southwestern Tehran distribution network, as shown in <xref ref-type="fig" rid="F6">Figure 6</xref>. An HIF indicator is installed in various poles that detect HIF at various locations. The HIF indicators are installed in the feeder based on the processing of the magnetic-field strength signal. The fitness evaluation combines three goals: accuracy, number of training samples, and the weighting factor. The impulse response of magnetic response in the frequency domain is calculated in terms of the electric hertz vector. By simulation, a 978-feature vector for the HIF and 852 non-HIF is calculated. The dependability and security of the proposed system are best above the 20&#xa0;db SNR. To evaluate the proposed method, MMG extracts a magnetic field strength signal, which is given to SVM for classification. The proposed algorithm has 96.9% security and 97.2% dependability.</p>
<p>The real-time experiments are performed in the Palash feeder, Tehran (<xref ref-type="bibr" rid="B134">Soheili et al., 2018</xref>). The modified FFT approach is used to detect the HIF concerning non-linear loads. In the proposed method, the measured three-phase current is analyzed by FFT. These currents are continuously monitored for non-linear loads, abnormal conditions, and HIF detection. HIF currents during non-linear loading conditions and different ground types are recorded. The proposed algorithm has divided the output into three levels: 0, 0.5, and 1. NC, pickup, and HIF, respectively, are represented by these levels. Various scenarios in the simulated data are considered, including high current three-phase feeder, low current three-phase feeder, low current single-phase feeder, and capacitor switching events. The distribution network is energized <italic>via</italic> a 63-kV/20-kV three-phase transformer with a rated power of 30 MVA. Data recording has been conducted using the ION 7650, with a sampling rate of 64 samples per cycle (3.2&#xa0;kHz). The various surfaces where real-time experiments are conducted are concrete with 20&#xa0;cm in no-load conditions, concrete with 10&#xa0;cm in 55% full load conditions, and asphalt with 2&#xa0;cm under 55% full load conditions. The HIF detection time of the proposed method was 1.13&#xa0;s.</p>
</sec>
<sec id="s3-4">
<title>3.4 IEEE test systems</title>
<p>There are various IEEE test systems, such as the single-line diagram of the IEEE 13-node system (<xref ref-type="fig" rid="F7">Figure 7A</xref>), the single-line representation of the IEEE four-node test system <xref ref-type="fig" rid="F7">(Figure 7B</xref>), the IEEE-123 distribution feeder (<xref ref-type="fig" rid="F7">Figure 7C</xref>), and the IEEE 34-node test system (<xref ref-type="fig" rid="F7">Figure 7D</xref>).</p>
<fig id="F7" position="float">
<label>FIGURE 7</label>
<caption>
<p>
<bold>(A)</bold> Single-line diagram of the IEEE 13-node system. <bold>(B)</bold> Single-line representation of the IEEE four-node test system. <bold>(C)</bold> IEEE-123 distribution feeder. <bold>(D)</bold> IEEE 34-node test system.</p>
</caption>
<graphic xlink:href="fenrg-11-1114230-g007.tif"/>
</fig>
<sec id="s3-4-1">
<title>3.4.1 IEEE 13-node systems</title>
<p>The illustration given by <xref ref-type="bibr" rid="B55">Gautam and Brahma (2013</xref>) used an HIF detection tool using MM that can be implemented along with the conventional overcurrent relays in the substation. Both IEEE 13- and IEEE 34-node test feeders are used to validate the approach. Closing Opening Difference Operation effectively detects a disturbance in waveforms. A low sampling rate of 3,840&#xa0;Hz (64 samples per cycle) was chosen to reduce computing time. The dilation and erosion function of MM and its difference will effectively detect the disturbance in the waveform. Voltage waveforms measured at substations are used in the procedure. The fault detection time is less than 1 s, and the method is fast and reliable. The two-test system gives 100% accuracy in detecting and classifying unbroken, broken conductors, capacitor switching, and load switching. A modified FFT approach based on HIF detection is proposed by <xref ref-type="bibr" rid="B134">Soheili et al. (2018</xref>), in which non-linear loading conditions are also considered. At node 630 of the IEEE 13-node system, the type of feeder, point of common coupling (PCC), and the current rate are considered, and the recording devices are installed at this node to resemble the real-world scenario. The feeder connected between 650 and 632 is considered the three-phase high current feeder with 300 A, 606&#xa0;m long. The feeder between 692 and 675 is considered a low-current three-phase feeder with 80 A. The main factors considered include high and low three-phase currents and low current single-phase feeders. The scheme successfully distinguishes the HIF with load switching and capacitor bank switching in 1.15 s. <xref ref-type="bibr" rid="B151">Wang et al. (2019</xref>) used variational mode decomposition (VMD) and Teager&#x2013;Kaiser energy operators (TKEOs) to identify the HIF. The method is tested in radial, IEEE 13-node, IEEE 34-node, and test microgrid systems, as well as experimental field tests. Three-phase current signals are measured, and VMD is performed on transient zero sequence currents (TZSCs) to obtain the intrinsic mode functions (IMFs). Then, the IMFs with the largest kurtosis value were selected as the characteristic IMFs. Second, the characteristic IMFs are calculated to obtain TKEOs and divided into subintervals of TKEOs waveform to calculate the time entropy values. The HIF detection criterion is when the time entropy value is 0; then, CS or LS has occurred. When the entropy value is not 0, it is judged as an HIF. The calculation time taken is 0.0028&#xa0;s.</p>
<p>A data-driven technique includes PCA, Fisher discriminant analysis, and binary and multi-class SVM for HIF detection. Compared with PCA, FDA can classify and locate the HIF successfully (<xref ref-type="bibr" rid="B117">Sarwar et al., 2020</xref>). PCA utilizes Hotelling&#x2019;s T<sup>2</sup> statics for HIF discrimination (see Eq. <xref ref-type="disp-formula" rid="e1">1</xref>). The IEEE 13-node system is used for testing:<disp-formula id="e1">
<mml:math id="m6">
<mml:mrow>
<mml:msubsup>
<mml:mi>T</mml:mi>
<mml:mi>&#x3b1;</mml:mi>
<mml:mn>2</mml:mn>
</mml:msubsup>
<mml:mo>&#x3d;</mml:mo>
<mml:mfrac>
<mml:mrow>
<mml:mi>m</mml:mi>
<mml:mrow>
<mml:mfenced open="(" close=")" separators="|">
<mml:mrow>
<mml:mi>n</mml:mi>
<mml:mo>&#x2b;</mml:mo>
<mml:mn>1</mml:mn>
</mml:mrow>
</mml:mfenced>
</mml:mrow>
<mml:mrow>
<mml:mfenced open="(" close=")" separators="|">
<mml:mrow>
<mml:mi>n</mml:mi>
<mml:mo>&#x2212;</mml:mo>
<mml:mn>1</mml:mn>
</mml:mrow>
</mml:mfenced>
</mml:mrow>
</mml:mrow>
<mml:mrow>
<mml:mi>n</mml:mi>
<mml:mtext>&#x2009;</mml:mtext>
<mml:mrow>
<mml:mfenced open="(" close=")" separators="|">
<mml:mrow>
<mml:mi>n</mml:mi>
<mml:mo>&#x2212;</mml:mo>
<mml:mi>m</mml:mi>
</mml:mrow>
</mml:mfenced>
</mml:mrow>
<mml:msub>
<mml:mi>F</mml:mi>
<mml:mi>&#x3b1;</mml:mi>
</mml:msub>
<mml:mrow>
<mml:mfenced open="(" close=")" separators="|">
<mml:mrow>
<mml:mi>m</mml:mi>
<mml:mo>,</mml:mo>
<mml:mi>n</mml:mi>
<mml:mo>&#x2212;</mml:mo>
<mml:mi>m</mml:mi>
</mml:mrow>
</mml:mfenced>
</mml:mrow>
</mml:mrow>
</mml:mfrac>
<mml:mo>,</mml:mo>
</mml:mrow>
</mml:math>
<label>(1)</label>
</disp-formula>where <italic>F</italic>
<sub>
<italic>&#x3b1;</italic>
</sub> <italic>(m, n-m)</italic> is the <italic>F</italic> distribution with m; (<italic>n&#x2013;m</italic>) is the degree of freedom; T<sub>2</sub> &#x2264; T<sup>2</sup> <sub>&#x3b1;</sub> means no-fault condition; and T<sub>2</sub> &#x3e; T<sup>2</sup> <sub>&#x3b1;</sub> means faulty condition.</p>
<p>The SVM uses a discriminant function to differentiate various classes. Non-linear classification is based on a kernel function from kernelized SVM. <xref ref-type="fig" rid="F7">Figure 7A</xref> shows the single-line diagram of the IEEE 13-node system. Multiclass SVM gives the best results, with dependability and security at 100%. <xref ref-type="bibr" rid="B131">Silva et al. (2020</xref>) performed a wavelet packet-based feature extraction with a three-level decomposition of signals at 2.5&#xa0;kHz along with the EuFNN classifier. The IEEE 13-bus system is considered for testing the method, which is a highly charged compact feeder with a rating of 4,053&#xa0;kV&#xa0;A and a power factor of 0.85, and an extension of approximately 1.5&#xa0;km from bus 650 to bus 680. Several line configurations, such as three-phase and single-phase lines, overhead, and underground sections, are considered. Different families of wavelet transform, namely, Haar, Symlet, Daubechies, Biorthogonal, and Coiflet, used to extract features from a one-cycle time window of current signals were chosen. The RMS and the entropy values calculated for Daubechie-8 give the best discrimination rate. Various WPT families, the MLP, learning vector quantization (LVQ), SVM, and EFuNN classifiers were compared, among which MLPNN gave the least accuracy, and all other classifiers gave an average of 97.14% accuracy. <xref ref-type="bibr" rid="B96">Nezamzadeh-Ejieh and Sadeghkhani (2020</xref>) performed the time-domain HIF detection algorithm by analyzing the substation current employing Kullback-divergence that measures the similarity between asymmetry and non-linearity of two consequent half cycles. Both IEEE 13-node and IEEE 34-node feeders are used to test the approach. The amplitude of the fault current of 15 A is approximately 3% of the normal feeder current. An intelligent electronic device samples the signals at 4.8&#xa0;kHz and measures the current in each phase. The current vector measurement is formed by <disp-formula id="e2">
<mml:math id="m7">
<mml:mrow>
<mml:msub>
<mml:mi>M</mml:mi>
<mml:mi>j</mml:mi>
</mml:msub>
<mml:mo>&#x3d;</mml:mo>
<mml:msup>
<mml:mrow>
<mml:mfenced open="[" close="]" separators="|">
<mml:mrow>
<mml:msub>
<mml:mi>i</mml:mi>
<mml:mi>j</mml:mi>
</mml:msub>
<mml:mrow>
<mml:mfenced open="(" close=")" separators="|">
<mml:mrow>
<mml:msub>
<mml:mi>t</mml:mi>
<mml:mn>0</mml:mn>
</mml:msub>
<mml:mo>&#x2b;</mml:mo>
<mml:msub>
<mml:mi>T</mml:mi>
<mml:mi>s</mml:mi>
</mml:msub>
</mml:mrow>
</mml:mfenced>
</mml:mrow>
<mml:mtext>&#x2003;</mml:mtext>
<mml:msub>
<mml:mi>i</mml:mi>
<mml:mi>j</mml:mi>
</mml:msub>
<mml:mrow>
<mml:mfenced open="(" close=")" separators="|">
<mml:mrow>
<mml:msub>
<mml:mi>t</mml:mi>
<mml:mn>0</mml:mn>
</mml:msub>
<mml:mo>&#x2b;</mml:mo>
<mml:mn>2</mml:mn>
<mml:msub>
<mml:mi>T</mml:mi>
<mml:mi>s</mml:mi>
</mml:msub>
</mml:mrow>
</mml:mfenced>
</mml:mrow>
<mml:mtext>&#x2003;</mml:mtext>
<mml:msub>
<mml:mi>i</mml:mi>
<mml:mi>j</mml:mi>
</mml:msub>
<mml:mrow>
<mml:mfenced open="(" close=")" separators="|">
<mml:mrow>
<mml:msub>
<mml:mi>t</mml:mi>
<mml:mn>0</mml:mn>
</mml:msub>
<mml:mo>&#x2b;</mml:mo>
<mml:mi>K</mml:mi>
<mml:msub>
<mml:mi>T</mml:mi>
<mml:mi>s</mml:mi>
</mml:msub>
</mml:mrow>
</mml:mfenced>
</mml:mrow>
</mml:mrow>
</mml:mfenced>
</mml:mrow>
<mml:mi>T</mml:mi>
</mml:msup>
<mml:mo>,</mml:mo>
</mml:mrow>
</mml:math>
<label>(2)</label>
</disp-formula>
<disp-formula id="e3">
<mml:math id="m8">
<mml:mrow>
<mml:msub>
<mml:mi>M</mml:mi>
<mml:mrow>
<mml:mi>i</mml:mi>
<mml:mi>j</mml:mi>
</mml:mrow>
</mml:msub>
<mml:mo>&#x3d;</mml:mo>
<mml:msup>
<mml:mrow>
<mml:mfenced open="[" close="]" separators="|">
<mml:mrow>
<mml:mrow>
<mml:mfenced open="|" close="|" separators="|">
<mml:mrow>
<mml:msub>
<mml:mi>i</mml:mi>
<mml:mi>j</mml:mi>
</mml:msub>
<mml:mrow>
<mml:mfenced open="(" close=")" separators="|">
<mml:mrow>
<mml:msub>
<mml:mi>t</mml:mi>
<mml:mn>0</mml:mn>
</mml:msub>
<mml:mo>&#x2b;</mml:mo>
<mml:msub>
<mml:mi>T</mml:mi>
<mml:mi>s</mml:mi>
</mml:msub>
</mml:mrow>
</mml:mfenced>
</mml:mrow>
</mml:mrow>
</mml:mfenced>
</mml:mrow>
<mml:mtext>&#x2002;</mml:mtext>
<mml:mo>&#x2026;</mml:mo>
<mml:mtext>&#x2002;</mml:mtext>
<mml:mrow>
<mml:mfenced open="|" close="|" separators="|">
<mml:mrow>
<mml:msub>
<mml:mi>i</mml:mi>
<mml:mi>j</mml:mi>
</mml:msub>
<mml:mrow>
<mml:mfenced open="(" close=")" separators="|">
<mml:mrow>
<mml:msub>
<mml:mi>t</mml:mi>
<mml:mn>0</mml:mn>
</mml:msub>
<mml:mo>&#x2b;</mml:mo>
<mml:mrow>
<mml:mfenced open="(" close=")" separators="|">
<mml:mrow>
<mml:mi>K</mml:mi>
<mml:mo>/</mml:mo>
<mml:mn>2</mml:mn>
</mml:mrow>
</mml:mfenced>
</mml:mrow>
<mml:msub>
<mml:mi>T</mml:mi>
<mml:mi>s</mml:mi>
</mml:msub>
</mml:mrow>
</mml:mfenced>
</mml:mrow>
</mml:mrow>
</mml:mfenced>
</mml:mrow>
</mml:mrow>
</mml:mfenced>
</mml:mrow>
<mml:mi>T</mml:mi>
</mml:msup>
<mml:mo>,</mml:mo>
</mml:mrow>
</mml:math>
<label>(3)</label>
</disp-formula>
<disp-formula id="e4">
<mml:math id="m9">
<mml:mrow>
<mml:msub>
<mml:mi>M</mml:mi>
<mml:mrow>
<mml:mi>i</mml:mi>
<mml:mi>j</mml:mi>
</mml:mrow>
</mml:msub>
<mml:mo>&#x3d;</mml:mo>
<mml:msup>
<mml:mrow>
<mml:mfenced open="[" close="]" separators="|">
<mml:mrow>
<mml:mrow>
<mml:mfenced open="|" close="|" separators="|">
<mml:mrow>
<mml:msub>
<mml:mi>i</mml:mi>
<mml:mi>j</mml:mi>
</mml:msub>
<mml:mrow>
<mml:mfenced open="(" close=")" separators="|">
<mml:mrow>
<mml:msub>
<mml:mi>t</mml:mi>
<mml:mn>0</mml:mn>
</mml:msub>
<mml:mo>&#x2b;</mml:mo>
<mml:mrow>
<mml:mfenced open="(" close=")" separators="|">
<mml:mrow>
<mml:mi>K</mml:mi>
<mml:mo>/</mml:mo>
<mml:mn>2</mml:mn>
</mml:mrow>
</mml:mfenced>
</mml:mrow>
<mml:mtext>&#x2009;</mml:mtext>
<mml:msub>
<mml:mi>T</mml:mi>
<mml:mi>s</mml:mi>
</mml:msub>
</mml:mrow>
</mml:mfenced>
</mml:mrow>
</mml:mrow>
</mml:mfenced>
</mml:mrow>
<mml:mtext>&#x2002;</mml:mtext>
<mml:mo>&#x2026;</mml:mo>
<mml:mtext>&#x2002;</mml:mtext>
<mml:mrow>
<mml:mfenced open="|" close="|" separators="|">
<mml:mrow>
<mml:msub>
<mml:mi>i</mml:mi>
<mml:mi>j</mml:mi>
</mml:msub>
<mml:mrow>
<mml:mfenced open="(" close=")" separators="|">
<mml:mrow>
<mml:msub>
<mml:mi>t</mml:mi>
<mml:mn>0</mml:mn>
</mml:msub>
<mml:mo>&#x2b;</mml:mo>
<mml:mi>K</mml:mi>
<mml:mo>/</mml:mo>
<mml:msub>
<mml:mi>T</mml:mi>
<mml:mi>s</mml:mi>
</mml:msub>
</mml:mrow>
</mml:mfenced>
</mml:mrow>
</mml:mrow>
</mml:mfenced>
</mml:mrow>
</mml:mrow>
</mml:mfenced>
</mml:mrow>
<mml:mi>T</mml:mi>
</mml:msup>
<mml:mo>,</mml:mo>
</mml:mrow>
</mml:math>
<label>(4)</label>
</disp-formula>
<disp-formula id="e5">
<mml:math id="m10">
<mml:mrow>
<mml:msub>
<mml:mi>D</mml:mi>
<mml:mrow>
<mml:mi>K</mml:mi>
<mml:mi>L</mml:mi>
<mml:mo>,</mml:mo>
<mml:mi>j</mml:mi>
</mml:mrow>
</mml:msub>
<mml:mrow>
<mml:mfenced open="(" close=")" separators="|">
<mml:mrow>
<mml:msub>
<mml:mi>M</mml:mi>
<mml:mrow>
<mml:mn>1</mml:mn>
<mml:mo>,</mml:mo>
<mml:mi>j</mml:mi>
</mml:mrow>
</mml:msub>
<mml:mo>&#x2016;</mml:mo>
<mml:msub>
<mml:mi>M</mml:mi>
<mml:mrow>
<mml:mn>2</mml:mn>
<mml:mo>,</mml:mo>
<mml:mi>j</mml:mi>
</mml:mrow>
</mml:msub>
</mml:mrow>
</mml:mfenced>
</mml:mrow>
<mml:mo>&#x3d;</mml:mo>
<mml:mrow>
<mml:munderover>
<mml:mstyle displaystyle="true">
<mml:mo>&#x2211;</mml:mo>
</mml:mstyle>
<mml:mrow>
<mml:mi>r</mml:mi>
<mml:mo>&#x3d;</mml:mo>
<mml:mn>1</mml:mn>
</mml:mrow>
<mml:mi>N</mml:mi>
</mml:munderover>
<mml:mrow>
<mml:msub>
<mml:mi>M</mml:mi>
<mml:mrow>
<mml:mn>1</mml:mn>
<mml:mo>,</mml:mo>
<mml:mi>j</mml:mi>
</mml:mrow>
</mml:msub>
<mml:mrow>
<mml:mfenced open="(" close=")" separators="|">
<mml:mrow>
<mml:mi>r</mml:mi>
</mml:mrow>
</mml:mfenced>
</mml:mrow>
</mml:mrow>
</mml:mrow>
<mml:mtext>&#x2009;</mml:mtext>
<mml:mi>log</mml:mi>
<mml:mfrac>
<mml:mrow>
<mml:msub>
<mml:mi>M</mml:mi>
<mml:mrow>
<mml:mn>1</mml:mn>
<mml:mo>,</mml:mo>
<mml:mi>j</mml:mi>
</mml:mrow>
</mml:msub>
<mml:mrow>
<mml:mfenced open="(" close=")" separators="|">
<mml:mrow>
<mml:mi>r</mml:mi>
</mml:mrow>
</mml:mfenced>
</mml:mrow>
</mml:mrow>
<mml:mrow>
<mml:msub>
<mml:mi>M</mml:mi>
<mml:mrow>
<mml:mn>2</mml:mn>
<mml:mo>,</mml:mo>
<mml:mi>j</mml:mi>
</mml:mrow>
</mml:msub>
<mml:mrow>
<mml:mfenced open="(" close=")" separators="|">
<mml:mrow>
<mml:mi>r</mml:mi>
</mml:mrow>
</mml:mfenced>
</mml:mrow>
</mml:mrow>
</mml:mfrac>
<mml:mo>.</mml:mo>
</mml:mrow>
</mml:math>
<label>(5)</label>
</disp-formula>
</p>
<p>During normal operation, there is no change in the waveforms of two consecutive half-cycles D<sub>KL</sub> &#x3d; 0, and during a fault occurrence, there will be asymmetry and non-linearity in the half-cycles and D<sub>KL</sub> &#x2260; 0. During the HIF, the third harmonic current will be greater than the fifth harmonic current. The occurrence of an HIF is when <inline-formula id="inf6">
<mml:math id="m11">
<mml:mrow>
<mml:mo>&#x3e;</mml:mo>
<mml:msub>
<mml:mi>&#x3be;</mml:mi>
<mml:mrow>
<mml:mi>t</mml:mi>
<mml:mi>h</mml:mi>
</mml:mrow>
</mml:msub>
</mml:mrow>
</mml:math>
</inline-formula>, where <inline-formula id="inf7">
<mml:math id="m12">
<mml:mrow>
<mml:msub>
<mml:mi>&#x3be;</mml:mi>
<mml:mrow>
<mml:mi>t</mml:mi>
<mml:mi>h</mml:mi>
</mml:mrow>
</mml:msub>
</mml:mrow>
</mml:math>
</inline-formula> is the disturbance detection threshold. A small threshold will decrease the accuracy of the system and a high value will reduce the detection speed. The method effectively detects the presence of an HIF.</p>
</sec>
<sec id="s3-4-2">
<title>3.4.2 IEEE 34-node test system</title>
<p>
<xref ref-type="bibr" rid="B92">Moravej et al. (2015</xref>) used an IEEE 34-node test feeder for testing, as given in <xref ref-type="fig" rid="F7">Figure 7D</xref>, and simulated it in EMTP-RV software. There are four different conductors, in which the system is characterized by heavily and lightly loaded with a feeder voltage of 24.9&#xa0;kV. Two-line regulators and one transformer (24.9/4.16&#xa0;kV) are present in the feeder. There are single-phase and three-phase feeders and two shunt capacitors in the system. Dual-tree complex wavelet transforms is used for feature extraction and PNN for classifying the faulty and healthy conditions. In the method, various steps involved in HIF detection include disturbance detection, disturbance feature extraction, HIF detection, frequency tracking, over-current protection, and the main feeder break detection. In the first step, the fundamental frequency current of the three-phase current is calculated using the DFT algorithm. The post-disturbance and pre-disturbance data windows are saved in memory, and both are decomposed into five levels by DT-CWT. The detailed components of the post-disturbance data window are subtracted from those of the pre-disturbance, and after obtaining the detailed component of the disturbance signal, the proper feature is selected. The SD and normalized energy of the detailed coefficients of level 2&#x2013;level 5 three-phase currents and residual current were selected as the features for the HIF detection algorithm. The algorithm is fast and detects the disturbance in 1.88&#xa0;ms, giving an accuracy of 98.88%. <xref ref-type="bibr" rid="B123">Sekar and Mohanty (2017</xref>) proposed that MM extracts features, such as energy, mean, and SD, which train the DT (data mining based). The three-phase current signal is pre-processed by a dilation and erosion morphological filter. The data mining-based DT using software package &#x201c;R&#x201d; is used, as well as post-disturbance data window length of current signals at feeder processed through the MM filter and chosen data window. The IEEE 34-node test system with light loads is also used. The total number of cases considered is 300, of which 70% are used for training and 30% for testing. The accuracy is 98.83%, dependability is 98.88%, and security is 100%, with a detection time of 30&#xa0;ms. The proposed method is also tested using the IEEE 13-node system, in which the total cases considered are 300, of which 70% are used for training and 30% for testing. The accuracy is 98.83%, dependability is 98.88%, and security is 100%, with a detection time of 30&#xa0;ms.</p>
<p>
<xref ref-type="bibr" rid="B47">Fan and Yin (2019</xref>) used a convolutional neural network and transfer learning-based approach for HIF detection. The method is tested with 5,000 data sets, of which 2,500 are HIF data and 2,500 are non-HIF conditions in an IEEE 34-node feeder. From the data set, 80% was taken for training and 20% for testing. The sampling rate was 15&#xa0;kHz, and there were 300 samples in the input data. Among the four layers of the CNN, each layer of the CNN model has convolution, rectified linear unit (ReLU), and max-pooling functions. The accuracy of the CNN obtained was 99.52%, and the computational cost was low compared with the traditional MLPNN (91.13%). Fewer data sets (&#x3c;300) were in the IEEE 13-node system with 50% training and 50% testing data. The accuracy obtained for the CNN was 95.06% compared to CNNs, with 74.69%.</p>
</sec>
<sec id="s3-4-3">
<title>3.4.3 IEEE four-node test feeder</title>
<p>The test system used is the IEEE four-node system, as shown in <xref ref-type="fig" rid="F7">Figure 7B</xref>. Three-phase load switching, capacitor switching, no-load transformer switching (energizing and de-energizing the transformer at various cycle times), harmonic loads (e.g., an unregulated four-pulse rectifier and induction motors), arc furnaces, and down-conductor and undowned conductor HIFs are discriminated using this method. The method of HIF detection (<xref ref-type="bibr" rid="B113">Sarlak and Shahrtash, 2008</xref>) uses PCA and LDA and is used along with SVM to detect the HIF, which gives 97.5% accuracy. PCA refers to the linear feature extraction method that computes <italic>m</italic> eigenvectors corresponding to <italic>n</italic>-dimensional patterns. PCA extracts uncorrelated features. Hence, it is more appropriate compared to other classification techniques. LDA measures the Fisher criterion that finds the <italic>m</italic> eigenvectors of the scatter matrix that discriminates HIFs from non-HIFs. The extracted features are sampled at the rate of 12.5&#xa0;kHz. The feature set is divided into a training set of 66% and a testing set of 34%. The polynomial and radial bias function of SVM is used, in which the linear kernel function has the best classification accuracy.</p>
</sec>
<sec id="s3-4-4">
<title>3.4.4 IEEE-123 distribution feeder</title>
<p>An IEEE-123 distribution feeder as a test system is illustrated, characterized by unbalanced phases modeled with EMTP-RV software. <xref ref-type="fig" rid="F7">Figure 7</xref>D displays the IEEE-123 distribution feeder. Some of the feeder buses are connected to smart meters in three-phase sections and not in single- and two-phase sections. <xref ref-type="bibr" rid="B144">Tonelli-Neto et al. (2017</xref>) found that the method uses WT along with ANN and fuzzy interference systems for HIF detection. Three-phase current signals are analyzed and sampled at a frequency of 15.36&#xa0;kHz. An application of DWT, multi-resolution analysis extracts the features from the current signals using Daubechies mother wavelet with fourth-order filter (db4). An energy concept is applied to the features to increase efficiency and minimize the number of coefficients. The energy concept is used for the third-level detail coefficients because of the high number of coefficients created in MRA. Fuzzy ARTMAP neural networks and fuzzy interface systems are used for HIF classification. Each bus, where the signals are obtained, has a FIS responsible for identifying and qualifying the feeder operating condition in the detection based on FIS. The results combine a normal case, HIF phase a, HIF phase b, and HIF phase c. The detection method based on the fuzzy art neural network (FANN) is as follows: the vectors obtained are normalized for use as inputs to multiple neural networks. This normalization is performed by identifying the maximum current value of each analyzed vector. Comparing both FANN and FIS, the accuracy of FANN is 97.69%, and that of FIS is 99.25%.</p>
</sec>
</sec>
<sec id="s3-5">
<title>3.5 Test microgrid system</title>
<p>The test microgrid system is used for HIF detection (<xref ref-type="bibr" rid="B68">Kar and Samantaray, 2017</xref>), as shown in <xref ref-type="fig" rid="F8">Figure 8A</xref>. The base power of the test system is chosen as 10&#xa0;MVA. The rated short-circuit of the utility is 1,000&#xa0;MVA with <italic>f</italic> &#x3d; 60&#xa0;Hz, rated 120&#xa0;kV. Distribution generations, DG1 and DG3, are rated as follows: synchronous generator rated at 9&#xa0;MW and rated voltage of 2.4&#xa0;kV, and DG2 is a wind farm consisting of three wind turbines (2&#xa0;MW each), rated kV &#x3d; 575&#xa0;V. The transformer ratings used in this study are as follows: Transformer 1: 15&#xa0;MVA, 120/25&#xa0;kV. Transformers 2 and 4 are rated at 12, kV &#x3d; 2.4&#xa0;kV/25&#xa0;kV, while Transformer 3 is rated at 2.5, kV &#x3d; 575&#xa0;V/25&#xa0;kV. The distribution lines (DL) are DL1, DL2, DL3, and DL4: PI-Section, 20&#xa0;km each. The total load is 20 MW, 10&#xa0;MVAR, a sum of L1&#x2013;L5. The MODWT is the feature extraction technique, and DT is the classifier used. The proposed method is tested in both grid-connected and islanded modes. The MODWT scaling filter and the wavelet filter related to the DWT filter are calculated, and the scaling coefficients of MODWT are obtained. The detailed approximation coefficient is obtained from the MODWT, and DT does accurate classification. The total cases are 1,493, of which 973 are HIF cases and 520 are faulty conditions. In the method proposed, 12 feature sets are considered, among which five were taken for classification. The training set (70%) and testing (30%) assess the performance. The software package &#x201c;R&#x201d; generates data mining for the DT. The detection accuracy, dependability, and security are 100% for the grid-connected mode, whereas for the islanded mode, the accuracy is 99.23%, security is 98.23%, and dependability is 100%.</p>
<fig id="F8" position="float">
<label>FIGURE 8</label>
<caption>
<p>
<bold>(A)</bold> Test microgrid system. <bold>(B)</bold> Representation of CERTS microgrid system structure. <bold>(C)</bold> Single-line representation of IEC microgrid.</p>
</caption>
<graphic xlink:href="fenrg-11-1114230-g008.tif"/>
</fig>
<p>Microgrid is considered while integrating distributed energy systems (<xref ref-type="bibr" rid="B3">Abdelgayed et al., 2017</xref>). The Consortium for Electric Reliability Technology Solutions (CERTS) was used for the case study of microgrids in this article. The microgrid system has two modes of operation: grid-connected and islanded mode of operation. CERTS microgrid consists of a distribution system fed from three-phase distribution transformers rated at 13.8/0.48&#xa0;kV, consisting of two solar photovoltaic sources and one battery energy storage source. Four loads are considered long in the distribution system. The method employs a semi-supervised machine learning strategy to handle labeled and unlabeled data. DWT extracts the hidden properties of voltage and current and applies them to a harmony search algorithm to find the HIF parameters. The DT and KNN classifiers are used to discriminate the HIF events. The overall accuracy of the DT is 100%, and that of the KNN is 95%.</p>
<p>The test system is a CERTS microgrid with two inverter-interfaced DG units and one synchronous generator-based DG unit (<xref ref-type="bibr" rid="B50">Gadanayak and Mallick, 2019</xref>). The representation CERT microgrid system is shown in <xref ref-type="fig" rid="F8">Figure 8B</xref>. For HIF detection, the test system consists of five distribution lines and five relay units. MATLAB-SIMULINK is used to simulate the model, with a simulation sampling rate of 0.5&#xa0;MHz. The MODWT approach for feature extraction and knot-based empirical mode decomposition is included in the methodology. The program recognized 855 cases of HIFs and 801 cases of non-HIFs. The average time to detect a fault was 0.12175&#xa0;s. The test system used by <xref ref-type="bibr" rid="B52">Gashteroodkhani et al. (2020</xref>) was performed in a 25-kV IEC standard microgrid that gave high accuracy and robustness in noisy environments. The single-line representation of the IEC microgrid is represented in <xref ref-type="fig" rid="F8">Figure 8C</xref>. A deep-belief neural network with TT-transform is employed where an intelligent relaying scheme-based real-time digital simulator is used, integrated with MATLAB. The process involves the measurement of three-phase currents at both ends and the feature extraction by Clark&#x2019;s transformation and TTT, which is sent to the DBNN. Six features are used for feature extraction, including energy, SD, and median absolute deviation. Microgrid models with grid-connected, islanded, radial, and mesh topologies are used to test the approach. With 3,600 fault situations and 3,125 no-fault cases, the sampling rate was set to 1.2&#xa0;kHz. The proposed method gives 99.74% and 99.46% accuracy for a radial network with grid-connected and islanded modes, respectively, and 100% for mesh topology in both modes of operation.</p>
</sec>
<sec id="s3-6">
<title>3.6 JMARTY model test system</title>
<p>
<xref ref-type="bibr" rid="B41">Eldin et al. (2007</xref>) considered the JMARTY model with Egyptian transmission line parameters, such as a transmission line length of 125&#xa0;km and a resistive load of 600&#xa0;MW, as shown in <xref ref-type="fig" rid="F9">Figure 9A</xref>. DWT&#x2019;s feature extraction technique with classifier moving window pattern recognition is used in HIF detection in extra-high voltage transmission. The sampling rate is 250 samples/cycle at 50&#xa0;Hz. In order to distinguish HIF from non-HIF events, the proposed technique uses high-frequency information from wavelet analysis db4. The effect of fault location, fault interception angle, fault type, switching of loads, switching of the HIF, and sudden load rejection is studied. The algorithm can be added to the existing digital relay microprocessor; it is fast, accurate, and simple.</p>
<fig id="F9" position="float">
<label>FIGURE 9</label>
<caption>
<p>
<bold>(A)</bold> Single-line representation of the JMARTY model transmission line test system. <bold>(B)</bold> Single-line representation of TAI-16 feeder distribution networks. <bold>(C)</bold> Single-line diagram of the 38-node test system. <bold>(D)</bold> Single-line representation of the benchmark system.</p>
</caption>
<graphic xlink:href="fenrg-11-1114230-g009.tif"/>
</fig>
<p>
<xref ref-type="bibr" rid="B62">Ibrahim et al. (2008</xref>) described two approaches: the first uses DWT analysis and the second analyses three-phase voltages using a high-frequency tap coupling capacitor voltage transformer. The chosen sampling rate is 20,000&#xa0;Hz. A 100-m-long 345-kV double-end transmission line system is considered. The effect of fault location, fault type, fault interception angle, switching of loads, and switching of HIF are studied. The method is independent of load variations and unbalanced conditions. The algorithm is fast, accurate, and simple; it can be added to an existing digital relay microprocessor (<xref ref-type="bibr" rid="B41">Eldin et al., 2007</xref>).</p>
</sec>
<sec id="s3-7">
<title>3.7 TAI-16 feeder</title>
<p>In <xref ref-type="bibr" rid="B155">Yang et al.&#x2019;s method (2006</xref>), the HIF was tested in a real-time Tai-16 feeder, Taishi substation near Mailiao, as shown in <xref ref-type="fig" rid="F9">Figure 9B</xref>. The fault was staged at pole &#x23;61 under grounded and ungrounded conditions, with dry and wet ground conditions. Data from the Shand-Ding substation and the She-Zi substation were considered to train the NN. The analog-to-digital recorder ADX-3000 was installed to monitor the neutral line current of the faulted feeder in the substation. A cross-linked polyethylene-covered conductor, a bare copper conductor, and ACSR conductors are used. A wavelet transform and pattern recognition-based feature extraction scheme is used and applied to backpropagation ANN for HIF detection. The detection of the HIF is carried out by introducing an intelligent HIF detector applied to a neutral line current, giving an 81% detection rate. A self-tuning algorithm based on the chi-square algorithm is applied to find the variations in neural current. A statistical confidence scheme is applied for neutral current estimation. For calculating the threshold of neutral current, a 95% confidence interval is applied.</p>
</sec>
<sec id="s3-8">
<title>3.8 Test system&#x2014;38 nodes</title>
<p>A typical 11-kV distribution network in Malaysia is composed of 38 nodes serving 34-line sections, as shown in <xref ref-type="fig" rid="F9">Figure 9C</xref>, displaying the single-line diagram of a 132/11-kV distribution network. The test unit has a frequency of 50&#xa0;Hz, with a sampling frequency of 6.4&#xa0;kHz, and delivers 128 samples/cycle. The feeder bus is simulated using the PSCAD program. <xref ref-type="bibr" rid="B6">Ali et al. (2014</xref>) proposed that DWT-based MRA is the feature extraction technique, and a matching approach technique is used for classification in the underground distribution system. The simulation tests of the three-phase voltage signal are obtained at a measurement point using the DWT-based multi-resolution technique. The voltage signal was decomposed into 128 samples and analyzed by Daubechies fourth order of DWT. The first level of the detailed coefficient, d1, detects the HIF by observing changes in the characteristics taken from three-phase voltage data. The sum of the first-level approximation coefficients obtained from the normal cycle, known as the approximation ratio, is divided by the sum of first-level approximation coefficients obtained from the normal cycle to classify the fault:<disp-formula id="e6">
<mml:math id="m13">
<mml:mrow>
<mml:mi mathvariant="normal">A</mml:mi>
<mml:mi mathvariant="normal">p</mml:mi>
<mml:mi mathvariant="normal">p</mml:mi>
<mml:mi mathvariant="normal">r</mml:mi>
<mml:mi mathvariant="normal">o</mml:mi>
<mml:mi mathvariant="normal">x</mml:mi>
<mml:mi mathvariant="normal">i</mml:mi>
<mml:mi mathvariant="normal">m</mml:mi>
<mml:mi mathvariant="normal">a</mml:mi>
<mml:mi mathvariant="normal">t</mml:mi>
<mml:mi mathvariant="normal">i</mml:mi>
<mml:mi mathvariant="normal">o</mml:mi>
<mml:mi mathvariant="normal">n</mml:mi>
<mml:mtext>&#x2009;</mml:mtext>
<mml:mi mathvariant="normal">R</mml:mi>
<mml:mi mathvariant="normal">a</mml:mi>
<mml:mi mathvariant="normal">t</mml:mi>
<mml:mi mathvariant="normal">i</mml:mi>
<mml:mi mathvariant="normal">o</mml:mi>
<mml:mo>&#x3d;</mml:mo>
<mml:mfrac>
<mml:mrow>
<mml:mo>&#x2211;</mml:mo>
<mml:mi>a</mml:mi>
<mml:mrow>
<mml:mfenced open="(" close=")" separators="|">
<mml:mrow>
<mml:mi>H</mml:mi>
<mml:mi>I</mml:mi>
<mml:mi>F</mml:mi>
</mml:mrow>
</mml:mfenced>
</mml:mrow>
</mml:mrow>
<mml:mrow>
<mml:mo>&#x2211;</mml:mo>
<mml:mi>a</mml:mi>
<mml:mrow>
<mml:mfenced open="(" close=")" separators="|">
<mml:mrow>
<mml:mi>n</mml:mi>
<mml:mi>o</mml:mi>
<mml:mi>r</mml:mi>
<mml:mi>m</mml:mi>
<mml:mi>a</mml:mi>
<mml:mi>l</mml:mi>
</mml:mrow>
</mml:mfenced>
</mml:mrow>
</mml:mrow>
</mml:mfrac>
<mml:mo>.</mml:mo>
</mml:mrow>
</mml:math>
<label>(6)</label>
</disp-formula>
</p>
<p>The approximation ratio is considered for distinguishing SLGF, LLGF, LLLF, and LLF. If the ratio is less than 1 for one phase and greater for the other two phases, then an SLG fault has occurred. The three-phase ratios will be the same for LLLF. For locating the HIF, a matching technique based on the shortest distance is used. For each line section, the SD between the measured signal and the line section is computed. The summation of the detailed coefficients of voltage signals is done in three coordinate systems and represented in three-dimensional space. The SD of each section is calculated, and the average value is calculated. The average value is compared with the SD values of each section. Each section is then arranged in ascending order of its SD values, which list the possibility of a faulty section. The method successfully located the fault after four or five iterations.</p>
</sec>
<sec id="s3-9">
<title>3.9 Benchmark system</title>
<p>In <xref ref-type="bibr" rid="B37">Cui et al. (2017</xref>), the test system chosen is a benchmark system in a remote Canadian community with 25&#xa0;kV 60&#xa0;Hz, distribution feeders that serve an 11-MW load built by McGill Power Laboratory, as shown in <xref ref-type="fig" rid="F9">Figure 9D</xref>. An L-G HIF at <italic>t</italic> &#x3d; 0.3&#xa0;s is implemented in a hybrid distribution system. The feeder&#x2019;s PCC (CB-1) will collect all the data where the HIF detector is located, two DGs at locations A and B, respectively. Three types of distribution systems are also possible to model: 1) the synchronous generator (SG) system is constructed by connecting the SG to location A without DG in location B; 2) the inverter-interfaced system is connected to location B with only type 4 wind turbines at location A and without DG; and 3) the hybrid DG system has an SG connected to location A and wind turbine generators at location B. The rated voltage is 4.17&#xa0;kV for the SG, and 9&#xa0;MVA is the power. Three wind turbine generators provide wind power, each rated at 575&#xa0;V and 2.2 MVA. The proposed method was tested in hybrid systems, and inverter-based systems are grounded, as well as ungrounded conditions. HIF and non-HIF events of 1,944 cases each have been considered for testing and training. The method proposes an algorithm to rank the effective feature sets using a signal processing technique of DFT and Kalman filtering estimation. The effective feature set is derived from information gain or entropy. The information gain of each feature is calculated, and a calculation variable is obtained. Such calculated variables are compared and then ranked for further assessment in HIF detection. By measuring the currents and voltages at the point of the common coupling, 246 electrical features are obtained. Classifiers, such as Native Bayer&#x2019;s, SVM (Gaussian kernel), k-nearest neighbor (KNN), RF, and J48, are compared, among which RF and J48 proved to be the best with 99% accuracy for both.</p>
</sec>
<sec id="s3-10">
<title>3.10 Modeling of HIF</title>
<p>Researchers provide numerous HIF models because of stochastic behavior and complicated properties. In order to acquire a good representation of the HIF, it is necessary to develop a model that specifies the features and the harmonic content of the HIF. Because arcing, which has yet to be fully modeled, is involved in most HIF events, an HIF is a difficult example to model. HIFs are non-linear and asymmetric, according to some earlier studies, and random and dynamic arcing features should be used in modeling (<xref ref-type="bibr" rid="B160">Zamanan and Sykulski, 2014</xref>). The arc is a continuous luminous discharge of electricity in which many free electrons and ions in an insulating medium are converted into a conducting medium. The arc was first studied as a continuous luminous discharge of electricity through an insulating medium that becomes a conducting medium due to the presence of a large number of free electrons and ions. The arc was first researched about circuit breaker disruption capabilities, with arc models used to improve circuit breaker testing (<xref ref-type="bibr" rid="B45">Elkalashy, 2007</xref>). The Emanuel model replicates zero periods of arcing and asymmetry by connecting two DC sources anti-parallel with two diodes (see <xref ref-type="fig" rid="F10">Figure 10</xref>). Variable resistors vary the fault resistance, and a voltage supply with random values mimics HIF unpredictability. Some of the other HIF models are, two-time varying series resistors with different characteristics (<xref ref-type="bibr" rid="B94">Nam et al., 2001</xref>), Kizilcay&#x2019;s model (<xref ref-type="bibr" rid="B161">Zhang et al., 2016</xref>; <xref ref-type="bibr" rid="B89">Mishra and Panigrahi, 2019</xref>) and Matthews arc model (<xref ref-type="bibr" rid="B51">Gammon and Matthews, 2001</xref>).</p>
<fig id="F10" position="float">
<label>FIGURE 10</label>
<caption>
<p>Emmanuel arc model of HIF. The Vn, Vp, Rn, and Rp values of wet sand are 4.5&#xa0;V, 2.5&#xa0;V, 400 &#xb1; 5&#xa0;&#x2126;, and 350 &#xb1; 5&#xa0;&#x2126;, respectively. For dry sod, the values are 4&#xa0;V, 2 V, 300 &#xb1; 5&#xa0;&#x2126;, and Rp 250 &#xb1; 5&#xa0;&#x2126;. The wet grass Vn, Vp, Rn, and Rp values are 2.75&#xa0;V, 1 V, 150 &#xb1; 5&#xa0;&#x2126;, and 125 &#xb1; 5&#xa0;&#x2126;, respectively. The Vn, Vp, Rn, and Rp values are 2.5&#xa0;V, 0.75&#xa0;V, 100 &#xb1; 5&#xa0;&#x2126;, and 75 &#xb1; 5&#xa0;&#x2126;, respectively, for reinforced concrete.</p>
</caption>
<graphic xlink:href="fenrg-11-1114230-g010.tif"/>
</fig>
</sec>
</sec>
<sec id="s4">
<title>4 Classifiers for identifying the healthy and faulty conductors</title>
<p>This section discusses classifiers, which distinguish between faulty and non-faulty conditions. Classifiers set a boundary between healthy and faulty conductors. In the classification process, two types of data are to be considered: training data consisting of information relating to known patterns and testing data, which are a collection of information relating to unknown patterns. <xref ref-type="table" rid="T3">Table 3</xref> presents the performance evaluation of various classifiers with various criteria, such as accuracy, dependability, security, sensibility, speed, and safety.</p>
<table-wrap id="T3" position="float">
<label>TABLE 3</label>
<caption>
<p>Performance evaluation of classifiers.</p>
</caption>
<table>
<thead valign="top">
<tr>
<th align="left">Criterion</th>
<th align="left">Equation</th>
<th align="left">Function</th>
</tr>
</thead>
<tbody valign="top">
<tr>
<td align="left">Accuracy (A)</td>
<td align="left">
<inline-graphic xlink:href="FENRG_fenrg-2023-1114230_wc_tfx1.tif"/> </td>
<td align="left">Overall precision</td>
</tr>
<tr>
<td align="left">Dependability (D)</td>
<td align="left">
<inline-graphic xlink:href="FENRG_fenrg-2023-1114230_wc_tfx2.tif"/> </td>
<td align="left">Faulty state detection precision</td>
</tr>
<tr>
<td align="left">Security (S)</td>
<td align="left">
<inline-graphic xlink:href="FENRG_fenrg-2023-1114230_wc_tfx3.tif"/> </td>
<td align="left">Healthy state detection precision</td>
</tr>
<tr>
<td align="left">Safety (S)</td>
<td align="left">
<inline-graphic xlink:href="FENRG_fenrg-2023-1114230_wc_tfx4.tif"/> </td>
<td align="left">Safety-related criterion</td>
</tr>
<tr>
<td align="left">Sensibility (SN)</td>
<td align="left">
<inline-graphic xlink:href="FENRG_fenrg-2023-1114230_wc_tfx5.tif"/> </td>
<td align="left">Sensitive load-related criterion</td>
</tr>
<tr>
<td align="left">Speed (v)</td>
<td align="left">
<inline-graphic xlink:href="FENRG_fenrg-2023-1114230_wc_tfx6.tif"/> </td>
<td align="left">Detection speed</td>
</tr>
</tbody>
</table>
<table-wrap-foot>
<fn>
<p>Note: TP, true positive; TN, true negative; FN, false negative; FP, false positive; Tonecycle, time for one cycle; TDetection, time for detection.</p>
</fn>
</table-wrap-foot>
</table-wrap>
<p>The appropriate classifier is chosen depending on the application where it is being used. The various classification conditions are capacitor switching, load switching, noises (<xref ref-type="bibr" rid="B36">Christie et al., 1993</xref>), disturbances (<xref ref-type="bibr" rid="B104">Russell and Benner, 1995</xref>), and voltage spikes. Faulty conditions include L-L, L-G, L-L-L, LIF, HIF (<xref ref-type="bibr" rid="B20">Barnard and Pahwa, 1993</xref>), and non-linear load conditions (<xref ref-type="bibr" rid="B138">Sultan and Swift, 1992</xref>). A knowledge-based system (<xref ref-type="bibr" rid="B121">Sedighizadeh et al., 2010</xref>), microprocessor (<xref ref-type="bibr" rid="B74">Kwon et al., 1991</xref>), signature-based detection (<xref ref-type="bibr" rid="B152">Wester, 1998</xref>), mechanical detection (<xref ref-type="bibr" rid="B17">Balser et al., 1986</xref>), burst noise signals (<xref ref-type="bibr" rid="B12">Aucoin and Russell, 1987</xref>), and DSP were previously used in classification. Different classifiers, such as neural networks (<xref ref-type="bibr" rid="B148">Vyshnavi and Prasad, 2018</xref>), SVM (<xref ref-type="bibr" rid="B90">Mishra et al., 2016</xref>), fuzzy logic, ANN (<xref ref-type="bibr" rid="B19">Baqui et al., 2011</xref>), GA (<xref ref-type="bibr" rid="B159">Zamanan et al., 2007</xref>), PNN (<xref ref-type="bibr" rid="B110">Samantaray et al., 2008</xref>), ELM (<xref ref-type="bibr" rid="B101">Reddy et al., 2013</xref>), ANFIS (<xref ref-type="bibr" rid="B2">Abdel Aziz et al., 2011</xref>), and DT (<xref ref-type="bibr" rid="B68">Kar and Samantaray, 2017</xref>) are compared and discussed.</p>
<sec id="s4-1">
<title>4.1 Neural networks</title>
<p>NN (<xref ref-type="bibr" rid="B133">Snider and Yuen, 1998</xref>) models are grouped according to their architecture (<xref ref-type="bibr" rid="B137">Sultan et al., 1992</xref>) (which gives the neural connection), processing (describes the production of output corresponding to weight and input), and training (explains the adaption of NN weight for every training vector). The architecture consists of the input, hidden, and output layers. The processed information of the NN is obtained at the output layer. NN architecture types are single-layer networks, such as an MLPNN (<xref ref-type="bibr" rid="B114">Sarlak and Shahrtash, 2011</xref>), a Hopfield network, and a Kohonen network (<xref ref-type="bibr" rid="B40">Ebron et al., 1990</xref>). ANN implementation is easy but is subject to the amount and quality of trained data. The ANN algorithm needs to be re-trained when there is a change in the data set, and the number of neurons and learning rate are found by the trial-and-error method.</p>
<p>An NN using a relay mechanism with HIF detection is described by <xref ref-type="bibr" rid="B128">Sharaf et al. (1993</xref>). The approach of a feed-forward network with backpropagation of one hidden layer and 15 neurons is used, which employs the discriminant vector of negative and zero sequence current and voltage in the substation. Twenty-two cases were taken for training and 10 cases for validation. They are noise-tolerant, require less detection time, and are economical. NN algorithm-based relaying scheme, implemented using NN hardware chips or software, promptly detects HIFs using Fourier analysis of lower-order harmonic vectors of measurements used as the input to the perceptron feed-forward network (<xref ref-type="bibr" rid="B132">Snider and Shan, 1998</xref>). The Emanual arc model is used as the HIF model. Logsigmoid hidden layers of three numbers with 10 neurons make the structure. As only lower-order harmonics are utilized for detection, the scheme is more feasible and flexible and has a high detection rate. The scheme is tested using simulation and real-time field measurements. A microprocessor-based pattern recognition technique is developed (<xref ref-type="bibr" rid="B5">Al-Dabbagh and Al-Dabbagh, 1999</xref>), which uses DFT to analyze signals. The scheme describes a sensitive Earth fault protection that is comparatively slow but gives better performance. The scheme is not tested with real-time data; only relaying current and voltage signals from the ATP simulation package are tested. <xref ref-type="bibr" rid="B70">Keyhani et al. (2001</xref>) used a subband decomposition method for current, which uses the energy of the subband to feed the input vector to the NN. The system is less noise-sensitive and can detect HIFs efficiently at high noise levels. The SNR chosen was 0&#x2013;14&#xa0;db. Emanuel and Gulachenski&#x2019;s HIF model is used for testing. A total of 800 cases were taken, and 16 neurons were used for fault analysis. Two NNs, namely, perceptron and FNN, are used; both give similar results with close to 100% accuracy. The scaling and translation characteristics of DWT are used to discriminate the transient and stable features of current signals (<xref ref-type="bibr" rid="B156">Yang et al., 2004</xref>). The extracted features of voltage and current signals and dissimilarity of wavelet component coefficients are calculated, which is used to train the NN and determine HIFs from the switching operations. The SD and mean are the features considered, with 20 neurons in the first hidden layer and 10 in the second hidden layer. A total of 600 events were taken, of which 500 are used for training and 100 for testing. The combination of the NN with DWT gives a good performance. <xref ref-type="bibr" rid="B18">Bansal and Pillai (2007</xref>) explained that FFT is the feature extraction technique used for 320 events taken. The magnitude of the third and fifth current harmonics is used for feature vector LVQ network classifiers for HIF detection. The output layer of LVQ contains two linear neurons. In comparison with the feed-forward network with backpropagation, LVQ gives a quicker response. LVQ gives the best results in random and selected subclasses if the subclass chosen is 10.</p>
<p>ANN and DWT are used for HIF detection (<xref ref-type="bibr" rid="B145">Vahidi et al., 2010</xref>). Distorted waveforms similar to fault current waveforms are generated, and DWT is used to denoise the signal and obtain signals with a high SNR. Sym8 wavelet function is used for detection, which gives 99% accuracy. The Levenberg&#x2013;Marquardt algorithm is used for training the network, with 8-5-3-1 <xref ref-type="bibr" rid="B19">Baqui et al. (2011)</xref>. The method is robust; it uses modified HIF models and discriminates between a wide range of signals, such as HIFs. The PNN model uses a probabilistic model, such as Bayesian classifiers and a supervised learning network, a type of feedforward network (FFN) that uses exponential activation functions. The PNN structure has four layers: the input layer, pattern layer (hidden layer), summation layer, and output layer. In the network used, the initial weights and the learning process are not required (<xref ref-type="bibr" rid="B33">Chen et al., 2016</xref>). <xref ref-type="bibr" rid="B47">Fan and Yin (2019</xref>) used the convolutional neural network that overcomes the disadvantages of conventional MLPNN; for example, the spatial structure of data is not considered, and large data sets are not required for training purposes. The four layers of CNN are convolution, rectified linear unit, and max-pooling functions. Here, the classic HIF model with two anti-parallel DC sources, diodes, and variable resistors is used. Two separate conditions were studied using the proposed system: the first was tested with 5,000 data sets, of which 2,500 are HIF data sets and 2,500 are non-HIF conditions in an IEEE 34-node feeder. From the data set, 80% was taken for training and 20% for testing. The sampling rate was 15&#xa0;kHz, and the input data contained 300 samples. The accuracy of the CNN obtained was 99.52% compared with the traditional MLPNN of 91.13%. The second case was performed with fewer data sets (&#x3c;300) in the IEEE 13-node system with 50% training and 50% testing data. The accuracy obtained was 95.06% compared to conventional neural networks, with 74.69%. ELM is extracted from neural networks that improve feed-forward neural networks&#x2019; efficiency. ELM is a single-layer neural network, which is hidden and does not need be tuned. In ELM, input weights and biases of hidden layers are selected randomly, and the output weights are chosen analytically (<xref ref-type="bibr" rid="B91">Mishra et al., 2017</xref>). FFT extracts the third and fifth harmonics current and voltage magnitudes and trains the ELM (<xref ref-type="bibr" rid="B101">Reddy et al., 2013</xref>). The number of events is 320, and 20 neurons with unipolar sigmoidal activation functions are used for training the algorithm. Here, ELM is used for fault classification and section identification. The scheme is faster with less human intervention and gives accurate classification and less training time compared to neural networks such as LVQ and MLP. DWT is the feature extraction technique that studies the cross-countryside HIF detection applied to the transmission and distribution systems (<xref ref-type="bibr" rid="B9">AsghariGovar et al., 2019</xref>). Three-phase current signals are extracted at both ends of the line for fault detection and identification. The Emanual arc model is used as the HIF model, and the IEEE 13-node system is tested. The hidden layer contains 20 nodes, with the number of inputs and outputs as one. Faulty conditions and other power system disturbances are classified by ELM. The novel protection algorithm is independent of interception angle, power swing, fault location, power system topology, and noise.</p>
</sec>
<sec id="s4-2">
<title>4.2 Genetic algorithm</title>
<p>A GA is an intelligent technology that detects faults (<xref ref-type="bibr" rid="B71">Kim et al., 1990</xref>). The behavior of the HIF is affected by many environmental parameters, and hence, a parameter-based generic technique method can be used. Detection of the HIF in a distribution system using a real coded genetic algorithm (RCGA) to analyze the tracking harmonics and current phase angles of the fault current signals was proposed by <xref ref-type="bibr" rid="B159">Zamanan et al. (2007</xref>). A fitness function is used by the GA that differentiates the performance between different strings. The scheme gives accurate results in differentiating harmonics and current angles of HIF. For GA, the simulation time is high, and as the processes are random, this cannot be used for fault location. GA cannot be used for online analysis because there is a possibility of inaccurate results.</p>
<p>Two methods for HIF detection have been compared (<xref ref-type="bibr" rid="B120">Sedighi et al., 2005b</xref>): the first method is the GA and Bayes classifier, where GA is used for feature vector reduction and Bayes for classification. The second method uses PCA and a NN for HIF identification. PCA and wavelet transform are used for feature extraction, for which GA gives the best results compared to the NN. The mother wavelet used is rbior3, with a sampling frequency of 24.67&#xa0;kHz. It discriminates HIFs from non-HIFs, such as isolator leakage current, capacitor switching, and load switching. The tests were conducted 8.20 and 8.44&#xa0;km from the source at different types of surfaces. The overall success rate of the Bayes classifier is 98.33%.</p>
</sec>
<sec id="s4-3">
<title>4.3 Support vector machine</title>
<p>SVM is a significant classifier commonly used in issues related to different power systems and environmental fields that find application in regression analysis, prediction, and classification. SVM is a non-linear kernel-based function that maps data from one space region to another (<xref ref-type="bibr" rid="B146">Veerasamy et al., 2018</xref>). Different types of kernel functions are the linear kernel, polynomial kernel, radial basis kernel, and sigmoid kernel. SVM provides a distinctive training algorithm to optimize the boundaries between different groups. Optimal parameter selection is highly important to obtain successful classification outcomes. The classifier of the support vector is mainly a binary linear classifier. Theoretically, SVM was derived from the principle of statistical learning. The linear classification algorithm for the SVM applies the training set to find the segregated hyperplane. The SVM algorithm calculates the number of support vectors for SVM (no training is required), which makes SVM a better algorithm for classification than ANNs (<xref ref-type="bibr" rid="B59">Gururajapathy et al., 2017</xref>). The elements of the training sets that characterize the dividing hyperplane are support vectors. Even for a large data set, SVM is quick in classification with fewer heuristics. <xref ref-type="bibr" rid="B54">Gashteroodkhani et al. (2019</xref>) proposed a method that uses TT transform and ST for feature extraction from the transient voltage signal measured at one end. The classification is conducted using SVM optimized by a particular swan optimization and is tested over the headline and underground cable. Bewley&#x2019;s lattice diagram identifies the fault location. The total number of cases was 2,376, of which 70% were used for training and 30% for testing the SVM. Compared with ST, the TT transform achieves 99.8% accuracy. <xref ref-type="bibr" rid="B106">Sahoo and Baran&#x2019;s method (2014</xref>) uses the DWT technique for feature extraction, which considers the SD and is tested in the radial distribution feeder at 138&#xa0;kV. Maximum value and energy are decomposed into two parts. Mary&#x2019;s model for HIFs is used. Various classifiers, such as fuzzy, Bayes ANFIS, SVM (Kernel trick function is used), and MLPNN, are compared, among which ANFIS and SVM give the best results. A data-driven technique includes PCA, Fisher discriminant analysis, and binary and multi-class SVM for HIF detection. Compared with PCA, FDA can classify and locate HIFs successfully (<xref ref-type="bibr" rid="B117">Sarwar et al., 2020</xref>). PCA utilizes Hotelling&#x2019;s T<sup>2</sup> statistics for HIF discrimination. The IEEE 13-node system is used for testing. Diode-resistance source is the HIF model used, with opposite polarity. Vp &#x3d; 1&#xa0;kV and Vn &#x3d; 0.5&#xa0;kV with &#xb1;10%. Rp and Rn range from 1,000 to 1,500&#xa0;&#x2126;, with random variation. In the proposed method, multiclass-SVM gives the best results. MM is the feature extraction (<xref ref-type="bibr" rid="B115">Sarlak and Shahrtash, 2013</xref>) and was tested on the Palash feeder in the Southwestern Tehran distribution network. An HIF indicator is installed in various poles that detect HIFs at various locations. The dependability and security of the proposed system are best above the 20&#xa0;db SNR. To evaluate the proposed method, a DST, DTT is used along with PNN, as well as DWT along with SVM. The proposed algorithm has 96.9% security and 97.2% dependability.</p>
</sec>
<sec id="s4-4">
<title>4.4 Adaptive neuro-fuzzy inference system</title>
<p>ANFIS includes the benefits of ANN and fuzzy logic principles in a single platform. ANFIS trains the fuzzy inference system to create fuzzy rules for IF-THEN and evaluate membership features for input and output variables. A NN trains the membership functions to minimize the error in fault classification. <xref ref-type="bibr" rid="B140">Tawafan et al. (2012</xref>) and <xref ref-type="bibr" rid="B2">Abdel Aziz et al. (2011</xref>) used the FFT for feature extraction, which was then tested in a radial 13.8-kV distribution feeder. Third harmonics, the magnitude of current, and phase of current are extracted, of which the first parameter is essential for HIF detection and the latter for HIF classification. It is noted that the HIF current is &#x3c; 0.05 for NCs and &#x3e;0.9 for HIF conditions. The main disadvantage is determining the global minimum using the membership function and enhancing feature extraction using the algorithm. The SD values drawn from the DWT are used to train fuzzy, Bayes, MLPNN, ANFIS, and SVM and compare the performances in <xref ref-type="bibr" rid="B147">Veerasamy et al. (2019</xref>). DWT with ANFIS and SVM classifiers discriminates between HIFs, SLGF, LLF, and DLGF, giving superior results. Apart from this, certain performance indices, such as absolute error, root mean square error, kappa statistic, success rate, and discrimination rate, were compared. In <xref ref-type="bibr" rid="B146">Veerasamy et al. (2018</xref>), DWT extracts SD features from a three-phase current and is used to train ANFIS. For fault analysis, a sampling rate of 20&#xa0;kHz is considered. The mother wavelet used is Daubichies&#x2019;s wavelet (Db9). A radial distribution system is used for testing in MATLAB/SIMULINK. The fuzzy logic system discrimination rate is 66.6%, but ANFIS gives 100%. When discrimination rates of the fuzzy logic system and ANFIS are compared, ANFIS proves to be superior by 33.3%. The fundamental component (e.g., magnitude and phase) of current is used (<xref ref-type="bibr" rid="B13">Aziz et al., 2012</xref>; <xref ref-type="bibr" rid="B1">Abdel Aziz et al., 2012</xref>) for HIF detection, classification (LG, LL, LLG, LLLG, and HIF), and location. The fundamental component, such as third harmonics, plays an essential role in HIF detection and location. The ANFIS classifier unit gives correct output for faulty and non-faulty conditions. In fuzzy logic, the concept of possibility is used rather than the concept of probability. <xref ref-type="bibr" rid="B65">Jota and Jota (1999</xref>) explained the application of neo-fuzzy neurons trained to identify the SD responses where FFT is used for feature vector extraction. After the training, the neuron set becomes a decision core of the supervisory system. The method identifies the HIF in a real-time feeder, which works better for not very close fault instants. The correction index is 100% for very close faults and 81% for faults at a distance of less than 10&#xa0;m. The field chosen is Caratinga in Brazil for data analysis. <xref ref-type="bibr" rid="B130">Silva et al. (1995</xref>) explained the HIF testing in both real-time feeders and simulation. The real-time feeder chosen was Caratinga in Brazil. The method is based on the traveling wave technique. Detection with fuzzy rules in normal and faulty cases was carried out, and faults within 10&#xa0;m were identified. The SD of noise was identified to input the fuzzy. The method is focused on passive faults, which effectively work with harmonic frequencies. The feature extraction technique DWT (<xref ref-type="bibr" rid="B131">Silva et al., 2020</xref>) with neuro-fuzzy classifier is tested in the IEEE distribution test 13-bus feeder and the IEEE distribution test 34-bus feeder, which incorporates an evolving fuzzy neural network (EuFNN) that has an &#x201c;adapt itself&#x201d; ability and is excellent in terms of accuracy and robustness. Wavelet packet-based feature extraction is used with a neuro-fuzzy classifier. Different families of wavelet packet transform, namely, Haar, Symlet, Daubechies, Biorthogonal, and Coiflet, were used to extract features from a one-cycle time window of current signals. LVQ, MLP, SVM, and evolving fuzzy neural networks are compared with RMS and entropy values coefficients. Apart from other advantages, EuFNN gives a membership function for the possibility of fault occurrence. The method will not identify the fault location. DWT with a fuzzy interference system and Fuzzy ARTMAP neural network combination based on Dempster&#x2013;Shafer evidence theory is tested in the IEEE-123 distribution feeder (<xref ref-type="bibr" rid="B144">Tonelli-Neto et al., 2017</xref>). The classification results show that the system is robust, efficient, and reliable. The Emanuel arc model is used for HIF modeling, where V<sub>p</sub> ranges from 500 to 2,000&#xa0;V and V<sub>n</sub> from 2,000 to 2,500&#xa0;V. Any new type of fault can be included in the classifier with ease. The method gives a classification efficiency of 97.69%. FFT extracts features from the signal, and fuzzy logic classifies HIF and non-HIF events (<xref ref-type="bibr" rid="B135">Suliman and Ghazal, 2019</xref>). The detection is performed by analyzing the third and fifth harmonics of magnitude and phase angle. The method is tested in three phase-4 wires of a 400-V radial distribution feeder in a downed conductor and wet sand. The third and fifth harmonics are extracted to train the classifier. The classifier is trained with real-time data from the practical test performed in the laboratory. By using a neuro-fuzzy interference system, tuning of the algorithm is performed.</p>
</sec>
<sec id="s4-5">
<title>4.5 Decision tree</title>
<p>DT represents the learned function in DT learning, which is a technique for approximating discrete-valued target functions. One of the possible values of this attribute corresponds to each branch that descends from the node. The DT-based method uses phase current (in RMS) and second, third, and fifth harmonic magnitudes to detect HIF (<xref ref-type="bibr" rid="B109">Samantaray, 2012</xref>). <xref ref-type="bibr" rid="B126">Shahrtash and Sarlak (2006</xref>) used pattern recognition with the DT algorithm, which has efficient training time and gives excellent results in even, odd, and between harmonics up to 400&#xa0;Hz. Two cases are considered for HIFs: the first is when a broken conductor touches the ground and the other is when an energized conductor touches another object. The specified tree is constructed using the J48 algorithm in WEKA software. The classification factor is considered based on entropy that gives the variations in the data set. This study concludes that a 2-kHz sampling frequency and 30-cycle time interval using a small energy DT can give accurate results. EKF is used for feature extraction and ensemble DT (RF) for fault classification, compared with the DT algorithm (<xref ref-type="bibr" rid="B109">Samantaray, 2012</xref>). The method is tested in radial and mesh networks. The reliability and accuracy of RF is compared and is best in the two cycle window. The method is also tested in one- and three-cycle windows. For data with SNR 20, the reliability is more than 99%. The DT algorithm (<xref ref-type="bibr" rid="B129">Sheng and Rovnyak, 2004</xref>) can differentiate between the HIFs from normal switching, such as capacitor switching and transformer inrush currents. FFT is used for feature extraction and is tested in a radial distribution feeder. DT discriminates the extracted features for classification, which, compared with other pattern recognition tools, gives better results. Current signals of each phase are sampled at 1,920 Hz, with a total number of cases of 5,700. The Emmanuel arc model is used, and the system is simulated in EMTP.</p>
</sec>
<sec id="s4-6">
<title>4.6 Miscellaneous HIF detection schemes</title>
<p>Several other HIF detection schemes, aside from these methods, play a crucial role in HIF detection. Using signal processing and pattern recognition techniques in the device relaying architecture with expert systems, <xref ref-type="bibr" rid="B39">Don Russell (1990)</xref> explained low current faults. <xref ref-type="bibr" rid="B85">Mamishev et al. (1996)</xref> suggested using fractal geometry to analyze the chaotic properties of high-impedance defects and RMS current values are used to classify the behavior of the temporal system, resulting in a relatively short time series usable for study. <xref ref-type="bibr" rid="B127">Sharaf et al. (1996</xref>) used a relay-based mechanism for HIF detection. The scheme utilizes the ripple frequencies and sub- and super-harmonics usually associated with the HIF phenomenon. <xref ref-type="bibr" rid="B41">Eldin et al. (2007</xref>) introduced two methods for detecting HIFs in extra-high-voltage transmission lines. Both approaches investigated the origins and dynamics of HIF-related arcing. The former employs DWT analysis, whereas the latter employs the coupling capacitor voltage transformer&#x2019;s high-frequency tap. The effects of fault location, interception angle, fault type, switch-off, and operations are analyzed. Both approaches are accurate and require less time.</p>
</sec>
</sec>
<sec id="s5">
<title>5 Locating high impendence faults</title>
<p>HIF detection and identification are essential, and locating the fault accurately is the next step. Many methods are used for locating HIFs, such as the matching technique (<xref ref-type="bibr" rid="B6">Ali et al., 2014</xref>), intelligent algorithms (<xref ref-type="bibr" rid="B33">Chen et al., 2016</xref>), synchronized harmonic phasors (<xref ref-type="bibr" rid="B48">Farajollahi et al., 2017</xref>), phase shift measurement of a high-frequency magnetic field (<xref ref-type="bibr" rid="B14">Bahador et al., 2018</xref>), the advanced distortion detection technique (<xref ref-type="bibr" rid="B22">Bhandia et al., 2020</xref>), smart meters (<xref ref-type="bibr" rid="B100">Radhakrishnan, 2019</xref>), power line communication systems (<xref ref-type="bibr" rid="B88">Milioudis et al., 2012</xref>), and power line carriers (<xref ref-type="bibr" rid="B35">Chen et al., 2010</xref>), which will be elaborated in this section. A transient power direction-based method is used for locating HIFs in MV distribution systems, as proposed by <xref ref-type="bibr" rid="B43">Elkalashy et al. (2008</xref>). DWT extracts the features of the residual current and voltage of the measuring nodes. The product of DWT detailed coefficient d3 of residual current and voltage will give the polarity of the frequency band power (12.5&#x2013;6.25&#xa0;kHz). Wireless sensors placed at the measuring nodes will process the detailed coefficients of DWT in the distribution network. Daubechies wavelet 14 (db14) is effectively located at the fault. An unearthed 20-kV distribution system is simulated using ATP and HIFs because leaning trees are mimicked using a universal arc model to test the proposed method. <xref ref-type="bibr" rid="B6">Ali et al. (2014</xref>) used the matching technique and analyzed the three-phase voltage signals using DWT-based MRA. Approximately 128 samples are taken and analyzed using Daubechies&#x2019; fourth order (Daub4). The fault location is identified by the smallest SD values. By iteration, the exact location can be found. A surge generator is used to pinpoint the exact location that injects a high-voltage DC pulse of 30&#xa0;kV. The highest amplitude flash over with acoustic noise gives the exact location of a fault.</p>
<p>HIF detection by measurement of voltage imbalance in primary distribution feeder by smart energy meter was illustrated by <xref ref-type="bibr" rid="B79">Leite (2019</xref>). The proposed method is tested in a typical distribution feeder of 13.8&#xa0;kV that gave accurate and robust results when tested in broken and unbroken conductors at the load or source side. The faulty section is identified by a parameter &#x201c;K&#x201d; factor when a situation of voltage unbalance threshold is crossed. The three-phase smart meters will calculate the voltage imbalance and locate the presence of the HIF. The voltage across the distribution feeder is measured by <xref ref-type="bibr" rid="B143">Thomas et al. (2016</xref>), as well as the voltage sequence components. Three HIF models were investigated (a high resistance model, a simpler two-diode model, and an arcing model), as well as several grounding options, such as a securely grounded network, a resistive grounded network, an ungrounded network, and a resonant grounded network. The method is tested in two identical feeders of 16&#xa0;km in length and divided into four identical sections. The detection is based on the positive sequence voltage drop and the percentage of negative and zero sequences voltage drop. <xref ref-type="bibr" rid="B30">Chakraborty and Das (2019</xref>) found that the detection is based on the even harmonics present in the voltage waveform using smart meters called the even harmonic distortion index and evaluated in a PSCAD simulation and experimental setup. The communication interface of the smart meter will inform the detection of the HIF to the nearby substation. The two-diode model of the HIF is used, and the test system used is IEEE 13-node feeder. The performance of the proposed system is compared with the existing schemes based on MM, wavelet transform, and harmonics-based detection, in which the proposed method gives satisfactory results with an execution time of 3.98&#xa0;ms. A two-terminal-based numerical algorithm for location estimation and arcing voltage calculation with synchronous phasors is proposed by <xref ref-type="bibr" rid="B17">Balser et al. (1986</xref>). Phasor measurement units are installed at either end of the transmission lines at a distance of 100&#xa0;km. In the study, a 10-km fault distance along with an arcing voltage of 4.5&#xa0;kV is calculated, and after 20&#xa0;ms of fault inception, the synchronous phasors detect the location. ETP simulation is used for testing the algorithm. <xref ref-type="bibr" rid="B63">Ibrahim et al. (2010b</xref>) located the fault by computing the system offline zero and negative-sequence impedance as a function of fault location, which is dependent on the unsynchronized root mean square (RMS) value of the sending and receiving end zero-sequence currents for ground faults or the RMS value of the sending and receiving end negative-sequence currents for line faults. The method is independent of any HIF model, and the test system for evaluation chosen is a 345-kV double-end transmission-line system. The accuracy error does not exceed &#xb1;2% for accurate line parameters with different fault conditions, such as LG, LLG, LL, and LLLG. <xref ref-type="bibr" rid="B100">Radhakrishnan (2019</xref>) proposed installing smart meters for locating HIFs in the distribution system, including distribution systems, power electronic loads, and electric arc furnaces. Smart meters are introduced in each load point that measures the load current and second harmonic content of load voltage. The method is tested on the LV 906-bus European distribution network and IEEE 39-bus system using PSCAD simulation to evaluate the performance of the smart meters under various grid conditions. The method proposed gives satisfactory results in all the investigated conditions. As an HIF alarm is generated, test signals are fed into the power grid, and the location of the fault can be calculated using impulse responses recorded by PLC devices (<xref ref-type="bibr" rid="B88">Milioudis et al., 2012</xref>). A frequency range of 3&#x2013;95&#xa0;kHz is used, and the method accurately locates the fault throughout the line. <xref ref-type="bibr" rid="B83">Lin et al. (2004</xref>) used a phasor measurement unit-based detection and locating system for permanent and arcing nature faults. PMUs installed on both terminal sides simultaneously monitor three-phase voltage and current phasors. The study proposes a communication link from the fault location. The measured phasors are communicated <italic>via</italic> communication channels to a central computer. However, only harmonic phasors are transmitted to the central computer after fault detection to reduce the burden of the communication channels. <xref ref-type="bibr" rid="B112">Santos et al. (2013</xref>) proposed the traveling wave method, which sends a high-frequency signal from one end of the terminal and is received at the other end. The amount of equipment required is high, and the method is expensive. A 90-bus feeder is used to test the proposed method.</p>
</sec>
<sec sec-type="conclusion" id="s6">
<title>6 Conclusion</title>
<p>This study reviewed most of the methods for feature extraction, classification, location, and test systems that have been produced over time, repeatedly, and the latest research developments used to detect HIFs in power distribution systems. Approximately 161 studies from the major referenced journals in the field of HIF detection have been discussed with primary importance on various test systems with different signal processing techniques and classification techniques. The feature extraction techniques using signal processing techniques include FFT, DWT, LWT, MODWT, LDA, PCA, MM, CWT, EKF, TT, DTWT, ST, and MODWPT. Different classifiers used to discriminate the HIF from non-HIF events, such as ANN, SVM, GA, ELM, PNN, FLC, ART, ANFIS, DT, RF, and CNN, are discussed. Various test systems, such as radial and mesh distribution networks, IEEE 4-, 13-, 34-, 39-, 123-node systems, Palash feeder, test microgrid, JMARTY, and Tai-16, are discussed in <xref ref-type="sec" rid="s3">Section 3</xref>, with IEEE standards. Fault locating techniques are discussed, such as the traveling wave method, phasor measurement unit method, and the matching technique. This review also highlighted the basic principles, advantages, and disadvantages of frequently used works related to HIFs. We also highlight that the conventional HIF detection methods are simple, have easy measurement setups, and consume less computation time. Still, they are inaccurate when used in large power system networks. Overall, we suggest a combination of signal processing techniques along with an intelligent classifier for the HIF detection scheme as they improve system reliability and power quality in distribution systems.</p>
</sec>
</body>
<back>
<sec id="s7">
<title>Author contributions</title>
<p>Conceptualization was performed by RV along with the support of MS and NK. The first draft was written by RV with inputs from MS, SG, NK, ES, and SD. Supervision was carried out by MS and NK. All the authors were involved in revising the draft.</p>
</sec>
<sec sec-type="COI-statement" id="s8">
<title>Conflict of interest</title>
<p>The authors declare that the research was conducted in the absence of any commercial or financial relationships that could be construed as a potential conflict of interest.</p>
</sec>
<sec sec-type="disclaimer" id="s9">
<title>Publisher&#x2019;s note</title>
<p>All claims expressed in this article are solely those of the authors and do not necessarily represent those of their affiliated organizations or those of the publisher, the editors, and the reviewers. Any product that may be evaluated in this article, or claim that may be made by its manufacturer, is not guaranteed or endorsed by the publisher.</p>
</sec>
<ref-list>
<title>References</title>
<ref id="B1">
<citation citation-type="journal">
<person-group person-group-type="author">
<name>
<surname>Abdel Aziz</surname>
<given-names>M. S.</given-names>
</name>
<name>
<surname>Hassan</surname>
<given-names>M. A. M.</given-names>
</name>
<name>
<surname>El-Zahab</surname>
<given-names>E. A.</given-names>
</name>
</person-group> (<year>2012</year>). <article-title>An artificial intelligence based approach for high impedance faults analysis in distribution networks</article-title>. <source>Int. J. Syst. Dyn. Appl.</source> <volume>1</volume> (<issue>2</issue>), <fpage>44</fpage>&#x2013;<lpage>59</lpage>. <pub-id pub-id-type="doi">10.4018/ijsda.2012040104</pub-id>
</citation>
</ref>
<ref id="B2">
<citation citation-type="book">
<person-group person-group-type="author">
<name>
<surname>Abdel Aziz</surname>
<given-names>M. S.</given-names>
</name>
<name>
<surname>Moustafa Hassan</surname>
<given-names>M. A.</given-names>
</name>
<name>
<surname>Zahab</surname>
<given-names>E. A.</given-names>
</name>
</person-group> (<year>2011</year>). <source>Applications of ANFIS in high impedance faults detection and classification in distribution networks,&#x201d; SDEMPED 2011 - 8th IEEE Symp. Diagnostics Electr</source> <publisher-loc>Bologna, Italy</publisher-loc>: <publisher-name>Mach. Power Electron. Drives</publisher-name>, <fpage>612</fpage>&#x2013;<lpage>619</lpage>. <pub-id pub-id-type="doi">10.1109/DEMPED.2011.6063687</pub-id>
</citation>
</ref>
<ref id="B3">
<citation citation-type="journal">
<person-group person-group-type="author">
<name>
<surname>Abdelgayed</surname>
<given-names>T. S.</given-names>
</name>
<name>
<surname>Morsi</surname>
<given-names>W. G.</given-names>
</name>
<name>
<surname>Sidhu</surname>
<given-names>T. S.</given-names>
</name>
</person-group> (<year>2017</year>). <article-title>Fault detection and classification based on co-training of semisupervised machine learning</article-title>. <source>IEEE Trans. Ind. Electron.</source> <volume>65</volume> (<issue>2</issue>), <fpage>1595</fpage>&#x2013;<lpage>1605</lpage>. <pub-id pub-id-type="doi">10.1109/TIE.2017.2726961</pub-id>
</citation>
</ref>
<ref id="B4">
<citation citation-type="journal">
<person-group person-group-type="author">
<name>
<surname>Akorede</surname>
<given-names>M. F.</given-names>
</name>
<name>
<surname>Katende</surname>
<given-names>J.</given-names>
</name>
</person-group> (<year>2010</year>). <article-title>Wavelet transform based algorithm for high-impedance faults detection in distribution feeders</article-title>. <source>Eur. J. Sci. Res.</source> <volume>41</volume> (<issue>2</issue>), <fpage>238</fpage>&#x2013;<lpage>248</lpage>.</citation>
</ref>
<ref id="B5">
<citation citation-type="journal">
<person-group person-group-type="author">
<name>
<surname>Al-Dabbagh</surname>
<given-names>M.</given-names>
</name>
<name>
<surname>Al-Dabbagh</surname>
<given-names>L.</given-names>
</name>
</person-group> (<year>1999</year>). <article-title>Neural networks based algorithm for detecting high impedance faults on power distribution lines</article-title>. <source>Proc. Int. Jt. Conf. Neural Netw.</source> <volume>5</volume>, <fpage>3386</fpage>&#x2013;<lpage>3390</lpage>. <pub-id pub-id-type="doi">10.1109/ijcnn.1999.836206</pub-id>
</citation>
</ref>
<ref id="B6">
<citation citation-type="journal">
<person-group person-group-type="author">
<name>
<surname>Ali</surname>
<given-names>M. S.</given-names>
</name>
<name>
<surname>Abu Bakar</surname>
<given-names>A. H.</given-names>
</name>
<name>
<surname>Mokhlis</surname>
<given-names>H.</given-names>
</name>
<name>
<surname>Arof</surname>
<given-names>H.</given-names>
</name>
<name>
<surname>Azil Illias</surname>
<given-names>H.</given-names>
</name>
</person-group> (<year>2014</year>). <article-title>High-impedance fault location using matching technique and wavelet transform for underground cable distribution network</article-title>. <source>IEEJ Trans. Electr. Electron. Eng.</source> <volume>9</volume> (<issue>2</issue>), <fpage>176</fpage>&#x2013;<lpage>182</lpage>. <pub-id pub-id-type="doi">10.1002/tee.21953</pub-id>
</citation>
</ref>
<ref id="B7">
<citation citation-type="journal">
<person-group person-group-type="author">
<name>
<surname>Aljohani</surname>
<given-names>A.</given-names>
</name>
<name>
<surname>Habiballah</surname>
<given-names>I.</given-names>
</name>
</person-group> (<year>2020</year>). <article-title>High-impedance fault diagnosis: A review</article-title>. <source>Energies</source> <volume>13</volume> (<issue>23</issue>), <fpage>6447</fpage>. <pub-id pub-id-type="doi">10.3390/en13236447</pub-id>
</citation>
</ref>
<ref id="B9">
<citation citation-type="journal">
<person-group person-group-type="author">
<name>
<surname>AsghariGovar</surname>
<given-names>S.</given-names>
</name>
<name>
<surname>Pourghasem</surname>
<given-names>P.</given-names>
</name>
<name>
<surname>Seyedi</surname>
<given-names>H.</given-names>
</name>
</person-group> (<year>2019</year>). <article-title>High impedance fault protection scheme for smart grids based on WPT and ELM considering evolving and cross-country faults</article-title>. <source>Int. J. Electr. Power Energy Syst.</source> <volume>107</volume> (<issue>7</issue>), <fpage>412</fpage>&#x2013;<lpage>421</lpage>. <pub-id pub-id-type="doi">10.1016/j.ijepes.2018.12.019</pub-id>
</citation>
</ref>
<ref id="B10">
<citation citation-type="journal">
<person-group person-group-type="author">
<name>
<surname>Ashok</surname>
<given-names>V.</given-names>
</name>
<name>
<surname>Yadav</surname>
<given-names>A.</given-names>
</name>
</person-group> (<year>2021</year>). <article-title>Fault diagnosis scheme for cross-country faults in dual-circuit line with emphasis on high-impedance fault syndrome</article-title>. <source>IEEE Syst. J.</source> <volume>15</volume> (<issue>2</issue>), <fpage>2087</fpage>&#x2013;<lpage>2097</lpage>. <pub-id pub-id-type="doi">10.1109/JSYST.2020.2991770</pub-id>
</citation>
</ref>
<ref id="B11">
<citation citation-type="journal">
<person-group person-group-type="author">
<name>
<surname>Aucoin</surname>
<given-names>B. M.</given-names>
</name>
<name>
<surname>Russell</surname>
<given-names>B. D.</given-names>
</name>
</person-group> (<year>1982</year>). <article-title>Distribution high impedance fault detection utilizing high frequency current components</article-title>. <source>IEEE Trans. Power Appar. Syst.</source> (<issue>6</issue>), <fpage>1596</fpage>&#x2013;<lpage>1606</lpage>. <comment>PAS-101</comment>. <pub-id pub-id-type="doi">10.1109/TPAS.1982.317209</pub-id>
</citation>
</ref>
<ref id="B12">
<citation citation-type="journal">
<person-group person-group-type="author">
<name>
<surname>Aucoin</surname>
<given-names>M.</given-names>
</name>
<name>
<surname>Russell</surname>
<given-names>B. D.</given-names>
</name>
</person-group> (<year>1987</year>). <article-title>Detection of distribution high impedance faults using burst noise signals near 60 hz</article-title>. <source>IEEE Trans. Power Deliv.</source> <volume>2</volume> (<issue>2</issue>), <fpage>342</fpage>&#x2013;<lpage>348</lpage>. <pub-id pub-id-type="doi">10.1109/TPWRD.1987.4308114</pub-id>
</citation>
</ref>
<ref id="B13">
<citation citation-type="journal">
<person-group person-group-type="author">
<name>
<surname>Aziz</surname>
<given-names>M. S. A.</given-names>
</name>
<name>
<surname>Hassan</surname>
<given-names>M. A. M.</given-names>
</name>
<name>
<surname>Zahab</surname>
<given-names>E. A.</given-names>
</name>
</person-group> (<year>2012</year>). <article-title>High-impedance faults analysis in distribution networks using an adaptive neuro fuzzy inference system</article-title>. <source>Electr. Power Components Syst.</source> <volume>40</volume> (<issue>11</issue>), <fpage>1300</fpage>&#x2013;<lpage>1318</lpage>. <pub-id pub-id-type="doi">10.1080/15325008.2012.689418</pub-id>
</citation>
</ref>
<ref id="B14">
<citation citation-type="journal">
<person-group person-group-type="author">
<name>
<surname>Bahador</surname>
<given-names>N.</given-names>
</name>
<name>
<surname>Namdari</surname>
<given-names>F.</given-names>
</name>
<name>
<surname>Matinfar</surname>
<given-names>H. R.</given-names>
</name>
</person-group> (<year>2018</year>). <article-title>Tree-related high impedance fault location using phase shift measurement of high frequency magnetic field</article-title>. <source>Int. J. Electr. Power Energy Syst.</source> <volume>100</volume> (<issue>3</issue>), <fpage>531</fpage>&#x2013;<lpage>539</lpage>. <pub-id pub-id-type="doi">10.1016/j.ijepes.2018.03.008</pub-id>
</citation>
</ref>
<ref id="B15">
<citation citation-type="journal">
<person-group person-group-type="author">
<name>
<surname>Bakar</surname>
<given-names>A. H. A.</given-names>
</name>
<name>
<surname>Ali</surname>
<given-names>M. S.</given-names>
</name>
<name>
<surname>Tan</surname>
<given-names>C.</given-names>
</name>
<name>
<surname>Mokhlis</surname>
<given-names>H.</given-names>
</name>
<name>
<surname>Arof</surname>
<given-names>H.</given-names>
</name>
<name>
<surname>Illias</surname>
<given-names>H. A.</given-names>
</name>
</person-group> (<year>2014</year>). <article-title>High impedance fault location in 11 kV underground distribution systems using wavelet transforms</article-title>. <source>Int. J. Electr. Power Energy Syst.</source> <volume>55</volume>, <fpage>723</fpage>&#x2013;<lpage>730</lpage>. <pub-id pub-id-type="doi">10.1016/j.ijepes.2013.10.003</pub-id>
</citation>
</ref>
<ref id="B16">
<citation citation-type="book">
<person-group person-group-type="author">
<name>
<surname>Balser</surname>
<given-names>S. J.</given-names>
</name>
<name>
<surname>Clements</surname>
<given-names>K. A.</given-names>
</name>
<name>
<surname>Kallaur</surname>
<given-names>E.</given-names>
</name>
</person-group> (<year>1982</year>). <source>Detection of high impedance faults</source> <publisher-loc>Washington, DC, United States of America</publisher-loc>: <publisher-name>Electr. Power Res. Institute, EPRI EL</publisher-name>, <fpage>1</fpage>&#x2013;<lpage>6</lpage>.</citation>
</ref>
<ref id="B17">
<citation citation-type="journal">
<person-group person-group-type="author">
<name>
<surname>Balser</surname>
<given-names>S. J.</given-names>
</name>
<name>
<surname>Lawrence</surname>
<given-names>D. J.</given-names>
</name>
<name>
<surname>Clements</surname>
<given-names>K. A.</given-names>
</name>
</person-group> (<year>1986</year>). <article-title>A microprocessor-based technique for detection of high impedance faults</article-title>. <source>IEEE Power Eng. Rev.</source> <volume>6</volume> (<issue>7</issue>), <fpage>59</fpage>&#x2013;<lpage>60</lpage>. <pub-id pub-id-type="doi">10.1109/MPER.1986.5527876</pub-id>
</citation>
</ref>
<ref id="B18">
<citation citation-type="journal">
<person-group person-group-type="author">
<name>
<surname>Bansal</surname>
<given-names>A.</given-names>
</name>
<name>
<surname>Pillai</surname>
<given-names>G. N.</given-names>
</name>
</person-group> (<year>2007</year>). <article-title>High Impedance Fault detection using LVQ neural networks</article-title>. <source>Int. J. Electr. Comput. Energy Electron. Commun. Engg</source> <volume>1</volume> (<issue>4</issue>), <fpage>693</fpage>&#x2013;<lpage>697</lpage>.</citation>
</ref>
<ref id="B19">
<citation citation-type="journal">
<person-group person-group-type="author">
<name>
<surname>Baqui</surname>
<given-names>I.</given-names>
</name>
<name>
<surname>Zamora</surname>
<given-names>I.</given-names>
</name>
<name>
<surname>Maz&#xf3;n</surname>
<given-names>J.</given-names>
</name>
<name>
<surname>Buigues</surname>
<given-names>G.</given-names>
</name>
</person-group> (<year>2011</year>). <article-title>High impedance fault detection methodology using wavelet transform and artificial neural networks</article-title>. <source>Electr. Power Syst. Res.</source> <volume>81</volume> (<issue>7</issue>), <fpage>1325</fpage>&#x2013;<lpage>1333</lpage>. <pub-id pub-id-type="doi">10.1016/j.epsr.2011.01.022</pub-id>
</citation>
</ref>
<ref id="B20">
<citation citation-type="journal">
<person-group person-group-type="author">
<name>
<surname>Barnard</surname>
<given-names>J.</given-names>
</name>
<name>
<surname>Pahwa</surname>
<given-names>A.</given-names>
</name>
</person-group> (<year>1993</year>). <article-title>Determination of the impacts of high impedance faults on protection of power distribution systems using a probabilistic model</article-title>. <source>Electr. Power Syst. Res.</source> <volume>28</volume> (<issue>1</issue>), <fpage>11</fpage>&#x2013;<lpage>18</lpage>. <pub-id pub-id-type="doi">10.1016/0378-7796(93)90074-O</pub-id>
</citation>
</ref>
<ref id="B21">
<citation citation-type="journal">
<person-group person-group-type="author">
<name>
<surname>Benner</surname>
<given-names>C.</given-names>
</name>
<name>
<surname>Carswell</surname>
<given-names>P.</given-names>
</name>
<name>
<surname>Don Russell</surname>
<given-names>B.</given-names>
</name>
</person-group> (<year>1989</year>). <article-title>Improved algorithm for detecting arcing faults using random fault behavior</article-title>. <source>Electr. Power Syst. Res.</source> <volume>17</volume> (<issue>1</issue>), <fpage>49</fpage>&#x2013;<lpage>56</lpage>. <pub-id pub-id-type="doi">10.1016/0378-7796(89)90059-X</pub-id>
</citation>
</ref>
<ref id="B22">
<citation citation-type="journal">
<person-group person-group-type="author">
<name>
<surname>Bhandia</surname>
<given-names>R.</given-names>
</name>
<name>
<surname>Chavez</surname>
<given-names>J. D. J.</given-names>
</name>
<name>
<surname>Cvetkovic</surname>
<given-names>M.</given-names>
</name>
<name>
<surname>Palensky</surname>
<given-names>P.</given-names>
</name>
</person-group> (<year>2020</year>). <article-title>High Impedance Fault detection using advanced distortion detection technique</article-title>. <source>IEEE Trans. Power Deliv.</source> <volume>35</volume> (<issue>6</issue>), <fpage>1</fpage>&#x2013;<lpage>2611</lpage>. <pub-id pub-id-type="doi">10.1109/TPWRD.2020.2973829</pub-id>
</citation>
</ref>
<ref id="B23">
<citation citation-type="journal">
<person-group person-group-type="author">
<name>
<surname>Bhongade</surname>
<given-names>S.</given-names>
</name>
<name>
<surname>Golhani</surname>
<given-names>S.</given-names>
</name>
</person-group> (<year>2016</year>). <article-title>HIF detection using wavelet transform, travelling wave and support vector machine</article-title>. <source>Int. Conf. Electr. Power Energy Syst. ICEPES</source>, <fpage>151</fpage>&#x2013;<lpage>156</lpage>. <pub-id pub-id-type="doi">10.1109/ICEPES.2016.7915922</pub-id>
</citation>
</ref>
<ref id="B24">
<citation citation-type="journal">
<person-group person-group-type="author">
<name>
<surname>Bin Sulaiman</surname>
<given-names>M.</given-names>
</name>
<name>
<surname>Tawafan</surname>
<given-names>A. H.</given-names>
</name>
<name>
<surname>Bin Ibrahim</surname>
<given-names>Z.</given-names>
</name>
</person-group> (<year>2017</year>). <article-title>High Impedance Fault detection on power distribution feeder using subtractive clustering fuzzy system</article-title>. <source>Int. Rev. Model. Simulations</source> <volume>15</volume> (<issue>5</issue>), <fpage>`168</fpage>&#x2013;<lpage>181</lpage>.</citation>
</ref>
<ref id="B25">
<citation citation-type="journal">
<person-group person-group-type="author">
<name>
<surname>Biswal</surname>
<given-names>M.</given-names>
</name>
<name>
<surname>Mishra</surname>
<given-names>M.</given-names>
</name>
<name>
<surname>Sood</surname>
<given-names>V. K.</given-names>
</name>
<name>
<surname>Bansal</surname>
<given-names>R. C.</given-names>
</name>
<name>
<surname>Abdelaziz</surname>
<given-names>A. Y.</given-names>
</name>
</person-group> (<year>2022</year>). <article-title>Savitzky-Golay Filter integrated matrix pencil method to identify high impedance fault in a renewable penetrated distribution system</article-title>. <source>Electr. Power Syst. Res.</source> <volume>210</volume> (<issue>5</issue>), <fpage>108056</fpage>. <pub-id pub-id-type="doi">10.1016/j.epsr.2022.108056</pub-id>
</citation>
</ref>
<ref id="B26">
<citation citation-type="journal">
<person-group person-group-type="author">
<name>
<surname>Calhoun</surname>
<given-names>H.</given-names>
</name>
<name>
<surname>Bishop</surname>
<given-names>M. T.</given-names>
</name>
<name>
<surname>Eichler</surname>
<given-names>C. H.</given-names>
</name>
<name>
<surname>Lee</surname>
<given-names>R. E.</given-names>
</name>
</person-group> (<year>1982</year>). <article-title>Development and testing of an electro-mechanical relay to detect fallen distribution conductors</article-title>. <source>IEEE Power Eng. Rev.</source> <volume>2</volume> (<issue>6</issue>), <fpage>50</fpage>&#x2013;<lpage>51</lpage>. <pub-id pub-id-type="doi">10.1109/MPER.1982.5521008</pub-id>
</citation>
</ref>
<ref id="B27">
<citation citation-type="journal">
<person-group person-group-type="author">
<name>
<surname>Carpenter</surname>
<given-names>M.</given-names>
</name>
<name>
<surname>Hoad</surname>
<given-names>R. F.</given-names>
</name>
<name>
<surname>Bruton</surname>
<given-names>T. D.</given-names>
</name>
<name>
<surname>Das</surname>
<given-names>R.</given-names>
</name>
<name>
<surname>Kunsman</surname>
<given-names>S. A.</given-names>
</name>
<name>
<surname>Peterson</surname>
<given-names>J. M.</given-names>
</name>
</person-group> (<year>2005</year>). <article-title>Staged-fault testing for high impedance fault data collection</article-title>. <source>2005 58th Annu. Conf. Prot. Relay Eng.</source> <volume>2005</volume>, <fpage>9</fpage>&#x2013;<lpage>17</lpage>. <pub-id pub-id-type="doi">10.1109/CPRE.2005.1430417</pub-id>
</citation>
</ref>
<ref id="B28">
<citation citation-type="journal">
<person-group person-group-type="author">
<name>
<surname>Carr</surname>
<given-names>J.</given-names>
</name>
</person-group> (<year>1981</year>). <article-title>Detection of high impedance faults on multi-grounded primary distribution systems</article-title>. <source>IEEE Trans. Power Appar. Syst.</source> <volume>100</volume> (<issue>4</issue>), <fpage>2008</fpage>&#x2013;<lpage>2016</lpage>. <pub-id pub-id-type="doi">10.1109/TPAS.1981.316556</pub-id>
</citation>
</ref>
<ref id="B29">
<citation citation-type="journal">
<person-group person-group-type="author">
<name>
<surname>Chaitanya</surname>
<given-names>B. K.</given-names>
</name>
<name>
<surname>Yadav</surname>
<given-names>A.</given-names>
</name>
<name>
<surname>Pazoki</surname>
<given-names>M.</given-names>
</name>
</person-group> (<year>2020</year>). <article-title>An intelligent detection of high-impedance faults for distribution lines integrated with distributed generators</article-title>. <source>IEEE Syst. J.</source> <volume>14</volume> (<issue>1</issue>), <fpage>870</fpage>&#x2013;<lpage>879</lpage>. <pub-id pub-id-type="doi">10.1109/JSYST.2019.2911529</pub-id>
</citation>
</ref>
<ref id="B30">
<citation citation-type="journal">
<person-group person-group-type="author">
<name>
<surname>Chakraborty</surname>
<given-names>S.</given-names>
</name>
<name>
<surname>Das</surname>
<given-names>S.</given-names>
</name>
</person-group> (<year>2019</year>). <article-title>Application of smart meters in high Impedance Fault detection on distribution systems</article-title>. <source>IEEE Trans. Smart Grid</source> <volume>10</volume> (<issue>3</issue>), <fpage>3465</fpage>&#x2013;<lpage>3473</lpage>. <pub-id pub-id-type="doi">10.1109/TSG.2018.2828414</pub-id>
</citation>
</ref>
<ref id="B31">
<citation citation-type="journal">
<person-group person-group-type="author">
<name>
<surname>Chen</surname>
<given-names>J. C.</given-names>
</name>
<name>
<surname>Phung</surname>
<given-names>B. T.</given-names>
</name>
<name>
<surname>Wu</surname>
<given-names>H. W.</given-names>
</name>
<name>
<surname>Zhang</surname>
<given-names>D. M.</given-names>
</name>
<name>
<surname>Blackburn</surname>
<given-names>T.</given-names>
</name>
</person-group> (<year>2014</year>). <article-title>Detection of high impedance faults using wavelet transform</article-title>. <source>Australas. Univ. Power Eng. Conf. AUPEC 2014 - Proc.</source> (<issue>10</issue>), <fpage>1</fpage>&#x2013;<lpage>6</lpage>. <pub-id pub-id-type="doi">10.1109/AUPEC.2014.6966629</pub-id>
</citation>
</ref>
<ref id="B32">
<citation citation-type="journal">
<person-group person-group-type="author">
<name>
<surname>Chen</surname>
<given-names>J. C.</given-names>
</name>
<name>
<surname>Phung</surname>
<given-names>B. T.</given-names>
</name>
<name>
<surname>Zhang</surname>
<given-names>D. M.</given-names>
</name>
<name>
<surname>Blackburn</surname>
<given-names>T.</given-names>
</name>
<name>
<surname>Ambikairajah</surname>
<given-names>E.</given-names>
</name>
</person-group> (<year>2013</year>). <article-title>Study on high impedance fault arcing current characteristics</article-title>. <source>Australas. Univ. Power Eng. Conf. AUPEC</source> <volume>2013</volume>. <pub-id pub-id-type="doi">10.1109/aupec.2013.6725439</pub-id>
</citation>
</ref>
<ref id="B33">
<citation citation-type="journal">
<person-group person-group-type="author">
<name>
<surname>Chen</surname>
<given-names>K.</given-names>
</name>
<name>
<surname>Huang</surname>
<given-names>C.</given-names>
</name>
<name>
<surname>He</surname>
<given-names>J.</given-names>
</name>
</person-group> (<year>2016</year>). <article-title>fault detection, classification and location for transmission lines and distribution systems: A review on the methods</article-title>. <source>High. Volt.</source> <volume>1</volume> (<issue>1</issue>), <fpage>25</fpage>&#x2013;<lpage>33</lpage>. <pub-id pub-id-type="doi">10.1049/hve.2016.0005</pub-id>
</citation>
</ref>
<ref id="B34">
<citation citation-type="journal">
<person-group person-group-type="author">
<name>
<surname>Chen</surname>
<given-names>M. T.</given-names>
</name>
<name>
<surname>Chu</surname>
<given-names>H. Y.</given-names>
</name>
<name>
<surname>Huang</surname>
<given-names>C. L.</given-names>
</name>
<name>
<surname>Wu</surname>
<given-names>F. R.</given-names>
</name>
</person-group> (<year>1990</year>). <article-title>Performance evaluation of high impedance fault detection algorithms based on staged fault tests</article-title>. <source>Electr. Power Syst. Res.</source> <volume>18</volume> (<issue>1</issue>), <fpage>75</fpage>&#x2013;<lpage>82</lpage>. <pub-id pub-id-type="doi">10.1016/0378-7796(90)90048-8</pub-id>
</citation>
</ref>
<ref id="B35">
<citation citation-type="journal">
<person-group person-group-type="author">
<name>
<surname>Chen</surname>
<given-names>M. Y.</given-names>
</name>
<name>
<surname>Zhai</surname>
<given-names>J. Q.</given-names>
</name>
<name>
<surname>Lang</surname>
<given-names>Z. Q.</given-names>
</name>
<name>
<surname>Liao</surname>
<given-names>J. C.</given-names>
</name>
<name>
<surname>Fan</surname>
<given-names>Z. Y.</given-names>
</name>
</person-group> (<year>2010</year>). <article-title>High impedance fault location in transmission line using nonlinear frequency analysis</article-title>. <source>Lect. Notes Comput. Sci. Incl. Subser. Lect. Notes Artif. Intell. Lect. Notes Bioinforma.</source> <volume>6328</volume> (<issue>1</issue>), <fpage>104</fpage>&#x2013;<lpage>111</lpage>. <pub-id pub-id-type="doi">10.1007/978-3-642-15621-2_13</pub-id>
</citation>
</ref>
<ref id="B36">
<citation citation-type="journal">
<person-group person-group-type="author">
<name>
<surname>Christie</surname>
<given-names>R. D.</given-names>
</name>
<name>
<surname>Zadehgol</surname>
<given-names>H.</given-names>
</name>
<name>
<surname>Habib</surname>
<given-names>M. M.</given-names>
</name>
</person-group> (<year>1993</year>). <article-title>High Impedance Fault detection in low voltage networks</article-title>. <source>IEEE Trans. Power Deliv.</source> <volume>8</volume> (<issue>4</issue>), <fpage>1829</fpage>&#x2013;<lpage>1836</lpage>. <pub-id pub-id-type="doi">10.1109/61.248291</pub-id>
</citation>
</ref>
<ref id="B37">
<citation citation-type="journal">
<person-group person-group-type="author">
<name>
<surname>Cui</surname>
<given-names>Q.</given-names>
</name>
<name>
<surname>El-Arroudi</surname>
<given-names>K.</given-names>
</name>
<name>
<surname>Joos</surname>
<given-names>G.</given-names>
</name>
</person-group> (<year>2017</year>). <article-title>An effective feature extraction method in pattern recognition based high impedance fault detection</article-title>. <source>2017 19th Int. Conf. Intell. Syst. Appl. Power Syst. ISAP</source>, <fpage>2017</fpage>. <pub-id pub-id-type="doi">10.1109/ISAP.2017.8071380</pub-id>
</citation>
</ref>
<ref id="B38">
<citation citation-type="journal">
<person-group person-group-type="author">
<name>
<surname>De Alvarenga Ferreira</surname>
<given-names>G.</given-names>
</name>
<name>
<surname>Mariano Lessa Assis</surname>
<given-names>T.</given-names>
</name>
</person-group> (<year>2019</year>). <article-title>A novel high impedance arcing fault detection based on the discrete wavelet transform for smart distribution grids</article-title>. <source>IEEE PES Conf. Innov. Smart Grid Technol. ISGT Lat. Am.</source>, <fpage>1</fpage>&#x2013;<lpage>6</lpage>. <pub-id pub-id-type="doi">10.1109/ISGT-LA.2019.8895264</pub-id>
</citation>
</ref>
<ref id="B39">
<citation citation-type="journal">
<person-group person-group-type="author">
<name>
<surname>Don Russell</surname>
<given-names>B.</given-names>
</name>
</person-group> (<year>1990</year>). <article-title>Computer relaying and expert systems: New tools for detecting high impedance faults</article-title>. <source>Electr. Power Syst. Res.</source> <volume>20</volume> (<issue>1</issue>), <fpage>31</fpage>&#x2013;<lpage>37</lpage>. <pub-id pub-id-type="doi">10.1016/0378-7796(90)90023-V</pub-id>
</citation>
</ref>
<ref id="B40">
<citation citation-type="journal">
<person-group person-group-type="author">
<name>
<surname>Ebron</surname>
<given-names>S.</given-names>
</name>
<name>
<surname>Lubkeman</surname>
<given-names>D. L.</given-names>
</name>
<name>
<surname>White</surname>
<given-names>M.</given-names>
</name>
</person-group> (<year>1990</year>). <article-title>A neural network approach to the detection of incipient faults on power distribution feeders</article-title>. <source>IEEE Trans. Power Deliv.</source> <volume>5</volume> (<issue>2</issue>), <fpage>905</fpage>&#x2013;<lpage>914</lpage>. <pub-id pub-id-type="doi">10.1109/61.53101</pub-id>
</citation>
</ref>
<ref id="B41">
<citation citation-type="book">
<person-group person-group-type="author">
<name>
<surname>Eldin</surname>
<given-names>E. S. T.</given-names>
</name>
<name>
<surname>Ibrahim</surname>
<given-names>D. K.</given-names>
</name>
<name>
<surname>Aboul-Zahab</surname>
<given-names>E. M.</given-names>
</name>
<name>
<surname>Saleh</surname>
<given-names>S. M.</given-names>
</name>
</person-group> (<year>2007</year>). &#x201c;<article-title>High impedance faults detection in EHV transmission lines using the wavelet transforms</article-title>,&#x201d; in <source>2007 IEEE power eng. Soc. Gen. Meet. PES</source>. <pub-id pub-id-type="doi">10.1109/PES.2007.385458</pub-id>
</citation>
</ref>
<ref id="B42">
<citation citation-type="book">
<person-group person-group-type="author">
<name>
<surname>Elkalashy</surname>
<given-names>N. I.</given-names>
</name>
<name>
<surname>Lehtonen</surname>
<given-names>M.</given-names>
</name>
<name>
<surname>Darwish</surname>
<given-names>H. A.</given-names>
</name>
<name>
<surname>Izzularab</surname>
<given-names>M. A.</given-names>
</name>
<name>
<surname>Taalab</surname>
<given-names>A. M. I.</given-names>
</name>
</person-group> (<year>2007</year>). &#x201c;<article-title>DWT-based investigation of phase currents for detecting high impedance faults due to leaning trees in unearthed MV networks</article-title>,&#x201d; in <source>2007 IEEE power eng. Soc. Gen. Meet. PES</source>, <fpage>1</fpage>. <comment>&#x2013;7</comment>. <pub-id pub-id-type="doi">10.1109/PES.2007.385652</pub-id>
</citation>
</ref>
<ref id="B43">
<citation citation-type="journal">
<person-group person-group-type="author">
<name>
<surname>Elkalashy</surname>
<given-names>N. I.</given-names>
</name>
<name>
<surname>Lehtonen</surname>
<given-names>M.</given-names>
</name>
<name>
<surname>Darwish</surname>
<given-names>H. A.</given-names>
</name>
<name>
<surname>Taalab</surname>
<given-names>A. M. I.</given-names>
</name>
<name>
<surname>Izzularab</surname>
<given-names>M. A.</given-names>
</name>
</person-group> (<year>2008</year>). <article-title>DWT-based detection and transient power direction-based location of high-impedance faults due to leaning trees in unearthed MV networks</article-title>. <source>IEEE Trans. Power Deliv.</source> <volume>23</volume> (<issue>1</issue>), <fpage>94</fpage>&#x2013;<lpage>101</lpage>. <pub-id pub-id-type="doi">10.1109/TPWRD.2007.911168</pub-id>
</citation>
</ref>
<ref id="B44">
<citation citation-type="book">
<person-group person-group-type="author">
<name>
<surname>Elkalashy</surname>
<given-names>N. I.</given-names>
</name>
<name>
<surname>Lehtonen</surname>
<given-names>M.</given-names>
</name>
<name>
<surname>Darwish</surname>
<given-names>H. A.</given-names>
</name>
<name>
<surname>Taalab</surname>
<given-names>A. M. I.</given-names>
</name>
<name>
<surname>Izzularab</surname>
<given-names>M. A.</given-names>
</name>
</person-group> (<year>2007</year>). &#x201c;<article-title>Feature extraction of high impedance arcing faults in compensated MV networks. Part I: DWT-based analysis of phase quantities</article-title>,&#x201d; in <source>IEEE PES PowerAfrica 2007 conf. Expo. PowerAfrica</source>, <fpage>16</fpage>&#x2013;<lpage>20</lpage>. <pub-id pub-id-type="doi">10.1109/PESAFR.2007.4498084</pub-id>
</citation>
</ref>
<ref id="B45">
<citation citation-type="book">
<person-group person-group-type="author">
<name>
<surname>Elkalashy</surname>
<given-names>N. I.</given-names>
</name>
</person-group> (<year>2007</year>). <source>Modelling and detection of high impedance arcing fault in medium voltage networks</source>.</citation>
</ref>
<ref id="B46">
<citation citation-type="journal">
<person-group person-group-type="author">
<name>
<surname>Emanuel</surname>
<given-names>A. E.</given-names>
</name>
<name>
<surname>Cyganski</surname>
<given-names>D.</given-names>
</name>
<name>
<surname>Orr</surname>
<given-names>J. A.</given-names>
</name>
<name>
<surname>Shiller</surname>
<given-names>S.</given-names>
</name>
<name>
<surname>Gulachenski</surname>
<given-names>E. M.</given-names>
</name>
</person-group> (<year>1990</year>). <article-title>High impedance fault arcing on sandy soil in 15kV distribution feeders: Contributions to the evaluation of the low frequency spectrum</article-title>. <source>IEEE Trans. Power Deliv.</source> <volume>5</volume> (<issue>2</issue>), <fpage>676</fpage>&#x2013;<lpage>686</lpage>. <pub-id pub-id-type="doi">10.1109/61.53070</pub-id>
</citation>
</ref>
<ref id="B47">
<citation citation-type="book">
<person-group person-group-type="author">
<name>
<surname>Fan</surname>
<given-names>R.</given-names>
</name>
<name>
<surname>Yin</surname>
<given-names>T.</given-names>
</name>
</person-group> (<year>2019</year>). <source>Convolutional neural network and transfer learning for high Impedance Fault detection</source>, <fpage>1</fpage>&#x2013;<lpage>3</lpage>. <comment>[Online]. Available at: <ext-link ext-link-type="uri" xlink:href="http://arxiv.org/abs/1904.08863">http://arxiv.org/abs/1904.08863</ext-link>.</comment>
</citation>
</ref>
<ref id="B48">
<citation citation-type="book">
<person-group person-group-type="author">
<name>
<surname>Farajollahi</surname>
<given-names>M.</given-names>
</name>
<name>
<surname>Shahsavari</surname>
<given-names>A.</given-names>
</name>
<name>
<surname>Mohsenian-Rad</surname>
<given-names>H.</given-names>
</name>
</person-group> (<year>2017</year>). &#x201c;<article-title>Location identification of high impedance faults using synchronized harmonic phasors</article-title>,&#x201d; in <source>2017 IEEE power energy soc. Innov. Smart grid technol. Conf. ISGT</source>, <fpage>2017</fpage>. <pub-id pub-id-type="doi">10.1109/ISGT.2017.8086048</pub-id>
</citation>
</ref>
<ref id="B49">
<citation citation-type="book">
<person-group person-group-type="author">
<name>
<surname>Faridnia</surname>
<given-names>N.</given-names>
</name>
<name>
<surname>Samet</surname>
<given-names>H.</given-names>
</name>
<name>
<surname>Doostani Dezfuli</surname>
<given-names>B.</given-names>
</name>
</person-group> (<year>2012</year> <article-title>A new approach to high impedance fault detection based on correlation functions</article-title> <source>IFIP Adv. Inf. Commun. Technol.</source>).<volume>381</volume> (<issue>1</issue>). <publisher-name>AICT</publisher-name>, <fpage>453</fpage>&#x2013;<lpage>462</lpage>. <pub-id pub-id-type="doi">10.1007/978-3-642-33409-2_47</pub-id>
</citation>
</ref>
<ref id="B50">
<citation citation-type="journal">
<person-group person-group-type="author">
<name>
<surname>Gadanayak</surname>
<given-names>D. A.</given-names>
</name>
<name>
<surname>Mallick</surname>
<given-names>R. K.</given-names>
</name>
</person-group> (<year>2019</year>). <article-title>Interharmonics based high impedance fault detection in distribution systems using maximum overlap wavelet packet transform and a modified empirical mode decomposition</article-title>. <source>Int. J. Electr. Power Energy Syst.</source> <volume>112</volume> (<issue>5</issue>), <fpage>282</fpage>&#x2013;<lpage>293</lpage>. <pub-id pub-id-type="doi">10.1016/j.ijepes.2019.04.050</pub-id>
</citation>
</ref>
<ref id="B51">
<citation citation-type="journal">
<person-group person-group-type="author">
<name>
<surname>Gammon</surname>
<given-names>T.</given-names>
</name>
<name>
<surname>Matthews</surname>
<given-names>J.</given-names>
</name>
</person-group> (<year>2001</year>). <article-title>Instantaneous arcing-fault models developed for building system analysis</article-title>. <source>IEEE Trans. Ind. Appl.</source> <volume>37</volume> (<issue>1</issue>), <fpage>197</fpage>&#x2013;<lpage>203</lpage>. <pub-id pub-id-type="doi">10.1109/28.903147</pub-id>
</citation>
</ref>
<ref id="B52">
<citation citation-type="journal">
<person-group person-group-type="author">
<name>
<surname>Gashteroodkhani</surname>
<given-names>O. A.</given-names>
</name>
<name>
<surname>Majidi</surname>
<given-names>M.</given-names>
</name>
<name>
<surname>Etezadi-Amoli</surname>
<given-names>M.</given-names>
</name>
</person-group> (<year>2020</year>). <article-title>A combined deep belief network and time-time transform based intelligent protection Scheme for microgrids</article-title>. <source>Electr. Power Syst. Res.</source> <volume>182</volume> (<issue>1</issue>), <fpage>106239</fpage>. <pub-id pub-id-type="doi">10.1016/j.epsr.2020.106239</pub-id>
</citation>
</ref>
<ref id="B53">
<citation citation-type="journal">
<person-group person-group-type="author">
<name>
<surname>Gashteroodkhani</surname>
<given-names>O. A.</given-names>
</name>
<name>
<surname>Majidi</surname>
<given-names>M.</given-names>
</name>
<name>
<surname>Etezadi-Amoli</surname>
<given-names>M.</given-names>
</name>
</person-group> (<year>2021</year>). <article-title>Fire hazard mitigation in distribution systems through high impedance fault detection</article-title>. <source>Electr. Power Syst. Res.</source> <volume>192</volume> (<issue>11</issue>), <fpage>106928</fpage>. <pub-id pub-id-type="doi">10.1016/j.epsr.2020.106928</pub-id>
</citation>
</ref>
<ref id="B54">
<citation citation-type="journal">
<person-group person-group-type="author">
<name>
<surname>Gashteroodkhani</surname>
<given-names>O. A.</given-names>
</name>
<name>
<surname>Majidi</surname>
<given-names>M.</given-names>
</name>
<name>
<surname>Etezadi-Amoli</surname>
<given-names>M.</given-names>
</name>
<name>
<surname>Nematollahi</surname>
<given-names>A. F.</given-names>
</name>
<name>
<surname>Vahidi</surname>
<given-names>B.</given-names>
</name>
</person-group> (<year>2019</year>). <article-title>A hybrid SVM-TT transform-based method for fault location in hybrid transmission lines with underground cables</article-title>. <source>Electr. Power Syst. Res.</source> <volume>170</volume> (<issue>1</issue>), <fpage>205</fpage>&#x2013;<lpage>214</lpage>. <pub-id pub-id-type="doi">10.1016/j.epsr.2019.01.023</pub-id>
</citation>
</ref>
<ref id="B55">
<citation citation-type="journal">
<person-group person-group-type="author">
<name>
<surname>Gautam</surname>
<given-names>S.</given-names>
</name>
<name>
<surname>Brahma</surname>
<given-names>S. M.</given-names>
</name>
</person-group> (<year>2013</year>). <article-title>Detection of high impedance fault in power distribution systems using mathematical morphology</article-title>. <source>IEEE Trans. Power Syst.</source> <volume>28</volume> (<issue>2</issue>), <fpage>1226</fpage>&#x2013;<lpage>1234</lpage>. <pub-id pub-id-type="doi">10.1109/TPWRS.2012.2215630</pub-id>
</citation>
</ref>
<ref id="B56">
<citation citation-type="journal">
<person-group person-group-type="author">
<name>
<surname>Ghaderi</surname>
<given-names>A.</given-names>
</name>
<name>
<surname>Ginn</surname>
<given-names>H. L.</given-names>
</name>
<name>
<surname>Mohammadpour</surname>
<given-names>H. A.</given-names>
</name>
</person-group> (<year>2017</year>). <article-title>High impedance fault detection: A review</article-title>. <source>Electr. Power Syst. Res.</source> <volume>143</volume>, <fpage>376</fpage>&#x2013;<lpage>388</lpage>. <pub-id pub-id-type="doi">10.1016/j.epsr.2016.10.021</pub-id>
</citation>
</ref>
<ref id="B57">
<citation citation-type="journal">
<person-group person-group-type="author">
<name>
<surname>Ghaderi</surname>
<given-names>A.</given-names>
</name>
<name>
<surname>Mohammadpour</surname>
<given-names>H. A.</given-names>
</name>
<name>
<surname>Ginn</surname>
<given-names>H. L.</given-names>
</name>
<name>
<surname>Shin</surname>
<given-names>Y. J.</given-names>
</name>
</person-group> (<year>2015</year>). <article-title>High-impedance fault detection in the distribution network using the time-frequency-based algorithm</article-title>. <source>IEEE Trans. Power Deliv.</source> <volume>30</volume> (<issue>3</issue>), <fpage>1260</fpage>&#x2013;<lpage>1268</lpage>. <pub-id pub-id-type="doi">10.1109/TPWRD.2014.2361207</pub-id>
</citation>
</ref>
<ref id="B58">
<citation citation-type="journal">
<person-group person-group-type="author">
<name>
<surname>Girgis</surname>
<given-names>A. A.</given-names>
</name>
<name>
<surname>Chang</surname>
<given-names>W.</given-names>
</name>
<name>
<surname>Makram</surname>
<given-names>E. B.</given-names>
</name>
</person-group> (<year>1990</year>). <article-title>Analysis of high-impedance fault generated signals using a kalman filtering approach</article-title>. <source>IEEE Trans. Power Deliv.</source> <volume>5</volume> (<issue>4</issue>), <fpage>1714</fpage>&#x2013;<lpage>1724</lpage>. <pub-id pub-id-type="doi">10.1109/61.103666</pub-id>
</citation>
</ref>
<ref id="B59">
<citation citation-type="book">
<person-group person-group-type="author">
<name>
<surname>Gururajapathy</surname>
<given-names>S. S.</given-names>
</name>
<name>
<surname>Mokhlis</surname>
<given-names>H.</given-names>
</name>
<name>
<surname>Illias</surname>
<given-names>H. A.</given-names>
</name>
</person-group> (<year>2017</year> <article-title>fault location and detection techniques in power distribution systems with distributed generation: A review</article-title> <source>Renew. Sustain. Energy Rev.</source>)., <volume>74</volume>. <publisher-name>March</publisher-name>, <fpage>949</fpage>&#x2013;<lpage>958</lpage>. <pub-id pub-id-type="doi">10.1016/j.rser.2017.03.021</pub-id>
</citation>
</ref>
<ref id="B60">
<citation citation-type="journal">
<person-group person-group-type="author">
<name>
<surname>Huang</surname>
<given-names>S. J.</given-names>
</name>
<name>
<surname>Hsieh</surname>
<given-names>C. T.</given-names>
</name>
</person-group> (<year>1999</year>). <article-title>High-impedance fault detection utilizing a Morlet wavelet transform approach</article-title>. <source>IEEE Trans. Power Deliv.</source> <volume>14</volume> (<issue>4</issue>), <fpage>1401</fpage>&#x2013;<lpage>1410</lpage>. <pub-id pub-id-type="doi">10.1109/61.796234</pub-id>
</citation>
</ref>
<ref id="B61">
<citation citation-type="journal">
<person-group person-group-type="author">
<name>
<surname>Hubana</surname>
<given-names>T.</given-names>
</name>
<name>
<surname>Saric</surname>
<given-names>M.</given-names>
</name>
<name>
<surname>Avdakovic</surname>
<given-names>S.</given-names>
</name>
</person-group> (<year>2018</year>). <article-title>Approach for identification and classification of HIFs in medium voltage distribution networks</article-title>. <source>IET Gener. Transm. Distrib.</source> <volume>12</volume> (<issue>5</issue>), <fpage>1145</fpage>&#x2013;<lpage>1152</lpage>. <pub-id pub-id-type="doi">10.1049/iet-gtd.2017.0883</pub-id>
</citation>
</ref>
<ref id="B62">
<citation citation-type="journal">
<person-group person-group-type="author">
<name>
<surname>Ibrahim</surname>
<given-names>D. K.</given-names>
</name>
<name>
<surname>Eldin</surname>
<given-names>E. S. T.</given-names>
</name>
<name>
<surname>Aboul-Zahab</surname>
<given-names>E. M.</given-names>
</name>
<name>
<surname>Saleh</surname>
<given-names>S. M.</given-names>
</name>
</person-group> (<year>2008</year>). <article-title>High-impedance fault detection in EHV transmission lines</article-title>. <source>2008 12th Int. Middle East Power Syst. Conf. MEPCON</source> <volume>1</volume> (<issue>1</issue>), <fpage>192</fpage>&#x2013;<lpage>199</lpage>. <pub-id pub-id-type="doi">10.1109/MEPCON.2008.4562363</pub-id>
</citation>
</ref>
<ref id="B63">
<citation citation-type="journal">
<person-group person-group-type="author">
<name>
<surname>Ibrahim</surname>
<given-names>D. K.</given-names>
</name>
<name>
<surname>Eldin</surname>
<given-names>E. S. T.</given-names>
</name>
<name>
<surname>El-Din Abou El-Zahab</surname>
<given-names>E.</given-names>
</name>
<name>
<surname>Saleh</surname>
<given-names>S. M.</given-names>
</name>
</person-group> (<year>2010</year>). <article-title>Unsynchronized fault - location scheme for nonlinear hif in transmission lines</article-title>. <source>IEEE Trans. Power Deliv.</source> <volume>25</volume> (<issue>2</issue>), <fpage>631</fpage>&#x2013;<lpage>637</lpage>. <pub-id pub-id-type="doi">10.1109/TPWRD.2009.2036182</pub-id>
</citation>
</ref>
<ref id="B64">
<citation citation-type="journal">
<person-group person-group-type="author">
<name>
<surname>Ibrahim</surname>
<given-names>D. K.</given-names>
</name>
<name>
<surname>Tag Eldin</surname>
<given-names>E. S.</given-names>
</name>
<name>
<surname>Aboul-Zahab</surname>
<given-names>E. M.</given-names>
</name>
<name>
<surname>Saleh</surname>
<given-names>S. M.</given-names>
</name>
</person-group> (<year>2010</year>). <article-title>Real time evaluation of DWT-based high impedance fault detection in EHV transmission</article-title>. <source>Electr. Power Syst. Res.</source> <volume>80</volume> (<issue>8</issue>), <fpage>907</fpage>&#x2013;<lpage>914</lpage>. <pub-id pub-id-type="doi">10.1016/j.epsr.2009.12.019</pub-id>
</citation>
</ref>
<ref id="B65">
<citation citation-type="journal">
<person-group person-group-type="author">
<name>
<surname>Jota</surname>
<given-names>P. R. S.</given-names>
</name>
<name>
<surname>Jota</surname>
<given-names>F. G.</given-names>
</name>
</person-group> (<year>1999</year>). <article-title>Fuzzy detection of high impedance faults in radial distribution feeders</article-title>. <source>Electr. Power Syst. Res.</source> <volume>49</volume> (<issue>3</issue>), <fpage>169</fpage>&#x2013;<lpage>174</lpage>. <pub-id pub-id-type="doi">10.1016/s0378-7796(98)00116-3</pub-id>
</citation>
</ref>
<ref id="B66">
<citation citation-type="book">
<person-group person-group-type="author">
<name>
<surname>K Chaitanya</surname>
<given-names>M. P. B.</given-names>
</name>
<name>
<surname>Yadav</surname>
<given-names>A.</given-names>
</name>
</person-group> (<year>2020</year>). &#x201c;<article-title>High impedance fault detection Scheme for active distribution network using Empirical wavelet transform and support vector machine</article-title>,&#x201d; in <source>IEEE explor. 15th int. Conf. Prot. Autom. Power syst</source> (<publisher-loc>IRAN</publisher-loc>: <publisher-name>Shiraz Univ.</publisher-name>), <fpage>30</fpage>&#x2013;<lpage>31</lpage>.</citation>
</ref>
<ref id="B67">
<citation citation-type="journal">
<person-group person-group-type="author">
<name>
<surname>Kannan</surname>
<given-names>A. N.</given-names>
</name>
<name>
<surname>Rathinam</surname>
<given-names>A.</given-names>
</name>
</person-group> (<year>2012</year>). <article-title>High impedance fault classification using wavelet transform and artificial neural network</article-title>. <source>Proc. - 4th Int. Conf. Comput. Intell. Commun. Netw. CICN</source>, <fpage>831</fpage>&#x2013;<lpage>837</lpage>. <pub-id pub-id-type="doi">10.1109/CICN.2012.122</pub-id>
</citation>
</ref>
<ref id="B68">
<citation citation-type="journal">
<person-group person-group-type="author">
<name>
<surname>Kar</surname>
<given-names>S.</given-names>
</name>
<name>
<surname>Samantaray</surname>
<given-names>S. R.</given-names>
</name>
</person-group> (<year>2017</year>). <article-title>High impedance fault detection in microgrid using maximal overlapping discrete wavelet transform and decision tree</article-title>. <source>Int. Conf. Electr. Power Energy Syst. ICEPES</source>, <fpage>258</fpage>&#x2013;<lpage>263</lpage>. <pub-id pub-id-type="doi">10.1109/ICEPES.2016.7915940</pub-id>
</citation>
</ref>
<ref id="B69">
<citation citation-type="journal">
<person-group person-group-type="author">
<name>
<surname>Kavaskar</surname>
<given-names>S.</given-names>
</name>
<name>
<surname>Mohanty</surname>
<given-names>N. K.</given-names>
</name>
</person-group> (<year>2019</year>). <article-title>Detection of high Impedance Fault in distribution networks</article-title>. <source>Ain Shams Eng. J.</source> <volume>10</volume> (<issue>1</issue>), <fpage>5</fpage>&#x2013;<lpage>13</lpage>. <pub-id pub-id-type="doi">10.1016/j.asej.2018.04.006</pub-id>
</citation>
</ref>
<ref id="B70">
<citation citation-type="journal">
<person-group person-group-type="author">
<name>
<surname>Keyhani</surname>
<given-names>R.</given-names>
</name>
<name>
<surname>Deriche</surname>
<given-names>M.</given-names>
</name>
<name>
<surname>Palmer</surname>
<given-names>E.</given-names>
</name>
</person-group> (<year>2001</year>). <article-title>A high impedance fault detector using a neural network and subband decomposition</article-title>. <source>6th Int. Symp. Signal Process. Its Appl. ISSPA 2001 - Proc. 6 Tutorials Commun. Image Process. Signal Anal.</source> <volume>2</volume>, <fpage>458</fpage>&#x2013;<lpage>461</lpage>. <pub-id pub-id-type="doi">10.1109/ISSPA.2001.950179</pub-id>
</citation>
</ref>
<ref id="B71">
<citation citation-type="journal">
<person-group person-group-type="author">
<name>
<surname>Kim</surname>
<given-names>C. J.</given-names>
</name>
<name>
<surname>Don Russell</surname>
<given-names>B.</given-names>
</name>
<name>
<surname>Watson</surname>
<given-names>K.</given-names>
</name>
</person-group> (<year>1990</year>). <article-title>A parameter-based process for selecting high impedance fault detection techniques using decision making under incomplete knowledge</article-title>. <source>IEEE Trans. Power Deliv.</source> <volume>5</volume> (<issue>3</issue>), <fpage>1314</fpage>&#x2013;<lpage>1320</lpage>. <pub-id pub-id-type="doi">10.1109/61.57972</pub-id>
</citation>
</ref>
<ref id="B72">
<citation citation-type="book">
<person-group person-group-type="author">
<name>
<surname>Kistler</surname>
<given-names>M.</given-names>
</name>
<name>
<surname>Kistler</surname>
<given-names>M.</given-names>
</name>
<name>
<surname>Utilities</surname>
<given-names>P. P. L. E.</given-names>
</name>
</person-group> (<year>2019</year>). <source>Practical experience with high-impedance fault detection in distribution systems practical experience with high-impedance fault detection in distribution systems</source>. <comment>[Online]. Available at: <ext-link ext-link-type="uri" xlink:href="https://selinc.com/mktg/132137/?creative=350703817639&amp;keyword=high%20impedance%20fault&amp;matchtype=b&amp;network=g&amp;device=c&amp;gclid=CjwKCAjwg4-EBhBwEiwAzYAlskrXp7M7oe_lGPdSEsFOWnpfE_JnaEV-4mKZTz82xCNGy4Bn2S0sbhoCkKcQAvD_BwE">https://selinc.com/mktg/132137/?creative&#x3d;350703817639&#x26;keyword&#x3d;high impedance fault&#x26;matchtype&#x3d;b&#x26;network&#x3d;g&#x26;device&#x3d;c&#x26;gclid&#x3d;CjwKCAjwg4-EBhBwEiwAzYAlskrXp7M7oe_lGPdSEsFOWnpfE_JnaEV-4mKZTz82xCNGy4Bn2S0sbhoCkKcQAvD_BwE</ext-link>.</comment>
</citation>
</ref>
<ref id="B73">
<citation citation-type="book">
<person-group person-group-type="author">
<name>
<surname>Kj&#xf8;lle</surname>
<given-names>G. H.</given-names>
</name>
<name>
<surname>Gjerde</surname>
<given-names>O.</given-names>
</name>
<name>
<surname>Hjartsjo</surname>
<given-names>B. T.</given-names>
</name>
<name>
<surname>Engen</surname>
<given-names>H.</given-names>
</name>
<name>
<surname>Haarla</surname>
<given-names>L.</given-names>
</name>
<name>
<surname>Koivisto</surname>
<given-names>L.</given-names>
</name>
<etal/>
</person-group> (<year>2006</year>). &#x201c;<article-title>Protection system faults - a comparative review of fault statistics</article-title>,&#x201d; in <source>2006 9th int. Conf. Probabilistic methods appl. To power syst. PMAPS</source>, <fpage>1</fpage>&#x2013;<lpage>7</lpage>. <pub-id pub-id-type="doi">10.1109/PMAPS.2006.360319</pub-id>
</citation>
</ref>
<ref id="B74">
<citation citation-type="journal">
<person-group person-group-type="author">
<name>
<surname>Kwon</surname>
<given-names>W. H.</given-names>
</name>
<name>
<surname>Lee</surname>
<given-names>G. W.</given-names>
</name>
<name>
<surname>Park</surname>
<given-names>Y.</given-names>
</name>
<name>
<surname>Yoon</surname>
<given-names>M.</given-names>
</name>
<name>
<surname>Yoo</surname>
<given-names>M.</given-names>
</name>
</person-group> (<year>1991</year>). <article-title>High impedance fault detection utilizing incremental varianc</article-title>. <source>IEEE Power Eng. Rev.</source> <volume>11</volume> (<issue>4</issue>), <fpage>58</fpage>&#x2013;<lpage>59</lpage>. <pub-id pub-id-type="doi">10.1109/MPER.1991.88839</pub-id>
</citation>
</ref>
<ref id="B75">
<citation citation-type="journal">
<person-group person-group-type="author">
<name>
<surname>Lai</surname>
<given-names>T. M.</given-names>
</name>
<name>
<surname>Snider</surname>
<given-names>L. A.</given-names>
</name>
<name>
<surname>Lo</surname>
<given-names>E.</given-names>
</name>
<name>
<surname>Sutanto</surname>
<given-names>D.</given-names>
</name>
</person-group> (<year>2005</year>). <article-title>High-impedance fault detection using discrete wavelet transform and frequency range and RMS conversion</article-title>. <source>IEEE Trans. Power Deliv.</source> <volume>20</volume> (<issue>1</issue>), <fpage>397</fpage>&#x2013;<lpage>407</lpage>. <pub-id pub-id-type="doi">10.1109/TPWRD.2004.837836</pub-id>
</citation>
</ref>
<ref id="B76">
<citation citation-type="journal">
<person-group person-group-type="author">
<name>
<surname>Langeroudi</surname>
<given-names>A. T.</given-names>
</name>
<name>
<surname>Abdelaziz</surname>
<given-names>M. M. A.</given-names>
</name>
</person-group> (<year>2020</year>). <article-title>Preventative high impedance fault detection using distribution system state estimation</article-title>. <source>Electr. Power Syst. Res.</source> <volume>186</volume> (<issue>4</issue>), <fpage>106394</fpage>. <pub-id pub-id-type="doi">10.1016/j.epsr.2020.106394</pub-id>
</citation>
</ref>
<ref id="B77">
<citation citation-type="journal">
<person-group person-group-type="author">
<name>
<surname>Lazkano</surname>
<given-names>A.</given-names>
</name>
<name>
<surname>Ruiz</surname>
<given-names>J.</given-names>
</name>
<name>
<surname>Aramendi</surname>
<given-names>E.</given-names>
</name>
<name>
<surname>Leturiondo</surname>
<given-names>L. A.</given-names>
</name>
</person-group> (<year>2004</year>). <article-title>Evaluation of a new proposal for an arcing fault detection method based on wavelet packet analysis</article-title>. <source>Eur. Trans. Electr. Power</source> <volume>14</volume> (<issue>3</issue>), <fpage>161</fpage>&#x2013;<lpage>174</lpage>.</citation>
</ref>
<ref id="B78">
<citation citation-type="journal">
<person-group person-group-type="author">
<name>
<surname>Lee</surname>
<given-names>R. E.</given-names>
</name>
<name>
<surname>Bishop</surname>
<given-names>M. T.</given-names>
</name>
</person-group> (<year>1985</year>). <article-title>A comparison of measured high Impedance Fault data to digital computer modeling results</article-title>. <source>IEEE Power Eng. Rev.</source> <volume>5</volume> (<issue>10</issue>), <fpage>35</fpage>&#x2013;<lpage>36</lpage>. <pub-id pub-id-type="doi">10.1109/MPER.1985.5528688</pub-id>
</citation>
</ref>
<ref id="B79">
<citation citation-type="book">
<person-group person-group-type="author">
<name>
<surname>Leite</surname>
<given-names>M. P.</given-names>
</name>
</person-group> (<year>2019</year>). <source>A voltage-based approach for series high impedance using smart meters</source>.</citation>
</ref>
<ref id="B80">
<citation citation-type="journal">
<person-group person-group-type="author">
<name>
<surname>Li</surname>
<given-names>W. J.</given-names>
</name>
<name>
<surname>Li</surname>
<given-names>Y. C.</given-names>
</name>
</person-group> (<year>2005</year>). <article-title>Arc fault detection based on wavelet packet</article-title>. <source>Int. Conf. Mach. Learn. Cybern. ICMLC</source> <volume>2</volume> (<issue>8</issue>), <fpage>1783</fpage>&#x2013;<lpage>1788</lpage>. <pub-id pub-id-type="doi">10.1109/icmlc.2005.1527234</pub-id>
</citation>
</ref>
<ref id="B81">
<citation citation-type="journal">
<person-group person-group-type="author">
<name>
<surname>Lima</surname>
<given-names>&#xc9;. M.</given-names>
</name>
<name>
<surname>Brito</surname>
<given-names>N. S. D.</given-names>
</name>
<name>
<surname>de Souza</surname>
<given-names>B. A.</given-names>
</name>
</person-group> (<year>2019</year>). <article-title>High impedance fault detection based on Stockwell transform and third harmonic current phase angle</article-title>. <source>Electr. Power Syst. Res.</source> <volume>175</volume> (<issue>6</issue>), <fpage>105931</fpage>. <pub-id pub-id-type="doi">10.1016/j.epsr.2019.105931</pub-id>
</citation>
</ref>
<ref id="B82">
<citation citation-type="journal">
<person-group person-group-type="author">
<name>
<surname>Lima</surname>
<given-names>&#xc9;. M.</given-names>
</name>
<name>
<surname>Junqueira</surname>
<given-names>C. M. dos S.</given-names>
</name>
<name>
<surname>Brito</surname>
<given-names>N. S. D.</given-names>
</name>
<name>
<surname>de Souza</surname>
<given-names>B. A.</given-names>
</name>
<name>
<surname>Coelho</surname>
<given-names>R. de A.</given-names>
</name>
<name>
<surname>de Medeiros</surname>
<given-names>H. G. M. S.</given-names>
</name>
</person-group> (<year>2018</year>). <article-title>High impedance fault detection method based on the short-time Fourier transform</article-title>. <source>IET Gener. Transm. Distrib.</source> <volume>12</volume> (<issue>11</issue>), <fpage>2577</fpage>&#x2013;<lpage>2584</lpage>. <pub-id pub-id-type="doi">10.1049/iet-gtd.2018.0093</pub-id>
</citation>
</ref>
<ref id="B83">
<citation citation-type="journal">
<person-group person-group-type="author">
<name>
<surname>Lin</surname>
<given-names>Y. H.</given-names>
</name>
<name>
<surname>Liu</surname>
<given-names>C. W.</given-names>
</name>
<name>
<surname>Chen</surname>
<given-names>C. S.</given-names>
</name>
</person-group> (<year>2004</year>). <article-title>A new PMU-based fault detection/location technique for transmission lines with consideration of arcing fault discrimination - Part I: Theory and algorithms</article-title>. <source>IEEE Trans. Power Deliv.</source> <volume>19</volume> (<issue>4</issue>), <fpage>1587</fpage>&#x2013;<lpage>1593</lpage>. <pub-id pub-id-type="doi">10.1109/TPWRD.2004.832407</pub-id>
</citation>
</ref>
<ref id="B84">
<citation citation-type="book">
<person-group person-group-type="author">
<name>
<surname>Louis</surname>
<given-names>H. W.</given-names>
</name>
</person-group> (<year>2015</year>). <source>Study of high Impedance Fault characteristics and detection methods</source>. <comment>Master thesis</comment>, <volume>150</volume> <publisher-loc>New South Wales, Sydney, Australia</publisher-loc>: <publisher-name>Sch. Electr. Eng. Telecommun. Univ.</publisher-name>
</citation>
</ref>
<ref id="B85">
<citation citation-type="journal">
<person-group person-group-type="author">
<name>
<surname>Mamishev</surname>
<given-names>A. V.</given-names>
</name>
<name>
<surname>Russell</surname>
<given-names>B.</given-names>
</name>
<name>
<surname>Benner</surname>
<given-names>C.</given-names>
</name>
</person-group> (<year>1996</year>). <article-title>Analysis of high impedance faults using fractal techniques</article-title>. <source>IEEE Trans. Power Syst.</source> <volume>11</volume> (<issue>1</issue>), <fpage>435</fpage>&#x2013;<lpage>440</lpage>. <pub-id pub-id-type="doi">10.1109/59.486130</pub-id>
</citation>
</ref>
<ref id="B86">
<citation citation-type="journal">
<person-group person-group-type="author">
<name>
<surname>Michalik</surname>
<given-names>M.</given-names>
</name>
<name>
<surname>Lukowicz</surname>
<given-names>M.</given-names>
</name>
<name>
<surname>Rebizant</surname>
<given-names>W.</given-names>
</name>
<name>
<surname>Lee</surname>
<given-names>S. J.</given-names>
</name>
<name>
<surname>Kang</surname>
<given-names>S. H.</given-names>
</name>
</person-group> (<year>2007</year>). <article-title>Verification of the wavelet-based HIF detecting algorithm performance in solidly grounded MV networks</article-title>. <source>IEEE Trans. Power Deliv.</source> <volume>22</volume> (<issue>4</issue>), <fpage>2057</fpage>&#x2013;<lpage>2064</lpage>. <pub-id pub-id-type="doi">10.1109/TPWRD.2007.905283</pub-id>
</citation>
</ref>
<ref id="B87">
<citation citation-type="journal">
<person-group person-group-type="author">
<name>
<surname>Michalik</surname>
<given-names>M.</given-names>
</name>
<name>
<surname>Rebizant</surname>
<given-names>W.</given-names>
</name>
<name>
<surname>Lukowicz</surname>
<given-names>M. R.</given-names>
</name>
<name>
<surname>Lee</surname>
<given-names>S. J.</given-names>
</name>
<name>
<surname>Kang</surname>
<given-names>S. H.</given-names>
</name>
</person-group> (<year>2006</year>). <article-title>High-impedance fault detection in distribution networks with use of wavelet-based algorithm</article-title>. <source>IEEE Trans. Power Deliv.</source> <volume>21</volume> (<issue>4</issue>), <fpage>1793</fpage>&#x2013;<lpage>1802</lpage>. <pub-id pub-id-type="doi">10.1109/TPWRD.2006.874581</pub-id>
</citation>
</ref>
<ref id="B88">
<citation citation-type="journal">
<person-group person-group-type="author">
<name>
<surname>Milioudis</surname>
<given-names>A. N.</given-names>
</name>
<name>
<surname>Member</surname>
<given-names>S.</given-names>
</name>
<name>
<surname>Andreou</surname>
<given-names>G. T.</given-names>
</name>
<name>
<surname>Labridis</surname>
<given-names>D. P.</given-names>
</name>
<name>
<surname>Member</surname>
<given-names>S.</given-names>
</name>
</person-group> (<year>2012</year>). <article-title>Enhanced protection scheme for smart grids using power line communications techniques&#x2014;Part II: Location of high Impedance Fault position</article-title>. <source>Locat. High Impedance Fault Position</source> <volume>3</volume> (<issue>4</issue>), <fpage>1631</fpage>&#x2013;<lpage>1640</lpage>. <pub-id pub-id-type="doi">10.1109/tsg.2012.2208988</pub-id>
</citation>
</ref>
<ref id="B89">
<citation citation-type="journal">
<person-group person-group-type="author">
<name>
<surname>Mishra</surname>
<given-names>M.</given-names>
</name>
<name>
<surname>Panigrahi</surname>
<given-names>R. R.</given-names>
</name>
</person-group> (<year>2019</year>). <article-title>Taxonomy of high impedance fault detection algorithm</article-title>. <source>Meas. J. Int. Meas. Confed.</source> <volume>148</volume>, <fpage>106955</fpage>. <pub-id pub-id-type="doi">10.1016/j.measurement.2019.106955</pub-id>
</citation>
</ref>
<ref id="B90">
<citation citation-type="journal">
<person-group person-group-type="author">
<name>
<surname>Mishra</surname>
<given-names>M.</given-names>
</name>
<name>
<surname>Routray</surname>
<given-names>P.</given-names>
</name>
<name>
<surname>kumar Rout</surname>
<given-names>P.</given-names>
</name>
</person-group> (<year>2016</year>). <article-title>A universal high Impedance Fault detection technique for distribution system using S-transform and pattern recognition</article-title>. <source>Technol. Econ. Smart Grids Sustain. Energy</source> <volume>1</volume> (<issue>9</issue>), <fpage>1</fpage>. <pub-id pub-id-type="doi">10.1007/s40866-016-0011-4</pub-id>
</citation>
</ref>
<ref id="B91">
<citation citation-type="journal">
<person-group person-group-type="author">
<name>
<surname>Mishra</surname>
<given-names>M.</given-names>
</name>
<name>
<surname>Sahani</surname>
<given-names>M.</given-names>
</name>
<name>
<surname>Rout</surname>
<given-names>P. K.</given-names>
</name>
</person-group> (<year>2017</year>). <article-title>An islanding detection algorithm for distributed generation based on Hilbert&#x2013;Huang transform and extreme learning machine</article-title>. <source>Sustain. Energy, Grids Netw.</source> <volume>9</volume>, <fpage>13</fpage>&#x2013;<lpage>26</lpage>. <pub-id pub-id-type="doi">10.1016/j.segan.2016.11.002</pub-id>
</citation>
</ref>
<ref id="B92">
<citation citation-type="journal">
<person-group person-group-type="author">
<name>
<surname>Moravej</surname>
<given-names>Z.</given-names>
</name>
<name>
<surname>Mortazavi</surname>
<given-names>S. H.</given-names>
</name>
<name>
<surname>Shahrtash</surname>
<given-names>S. M.</given-names>
</name>
</person-group> (<year>2015</year>). <article-title>DT-CWT based event feature extraction for high impedance faults detection in distribution system</article-title>. <source>Int. Trans. Electr. Energy Syst.</source> <volume>25</volume> (<issue>12</issue>), <fpage>3288</fpage>&#x2013;<lpage>3303</lpage>. <pub-id pub-id-type="doi">10.1002/etep.2035</pub-id>
</citation>
</ref>
<ref id="B93">
<citation citation-type="book">
<person-group person-group-type="author">
<name>
<surname>Naik</surname>
<given-names>V. K.</given-names>
</name>
<name>
<surname>Yadav</surname>
<given-names>A.</given-names>
</name>
</person-group> (<year>2018</year>). &#x201c;<article-title>High impedance fault detection and classification on IEEE-15 bus radial distribution system by using fuzzy inference system</article-title>,&#x201d; in <source>2018 2nd int. Conf. Power, energy environ. Towar. Smart technol</source>, <fpage>1</fpage>&#x2013;<lpage>6</lpage>.</citation>
</ref>
<ref id="B94">
<citation citation-type="journal">
<person-group person-group-type="author">
<name>
<surname>Nam</surname>
<given-names>S. R.</given-names>
</name>
<name>
<surname>Park</surname>
<given-names>J. K.</given-names>
</name>
<name>
<surname>Kang</surname>
<given-names>Y. C.</given-names>
</name>
<name>
<surname>Kim</surname>
<given-names>T. H.</given-names>
</name>
</person-group> (<year>2001</year>). <article-title>A modeling method of a high impedance fault in a distribution system using two series time-varying resistances in EMTP</article-title>. <source>Proc. IEEE Power Eng. Soc. Transm. Distrib. Conf.</source> <volume>2</volume> (<issue>5</issue>), <fpage>1175</fpage>&#x2013;<lpage>1180</lpage>. <pub-id pub-id-type="doi">10.1109/pess.2001.970231</pub-id>
</citation>
</ref>
<ref id="B95">
<citation citation-type="journal">
<person-group person-group-type="author">
<name>
<surname>Narasimhulu</surname>
<given-names>N.</given-names>
</name>
<name>
<surname>Kumar</surname>
<given-names>D. V. A.</given-names>
</name>
<name>
<surname>Kumar</surname>
<given-names>M. V.</given-names>
</name>
</person-group> (<year>2020</year>). <article-title>LWT based ANN with ant lion optimizer for detection and classification of high impedance faults in distribution system</article-title>. <source>J. Electr. Eng. Technol.</source> <volume>15</volume> (<issue>4</issue>), <fpage>1631</fpage>&#x2013;<lpage>1650</lpage>. <pub-id pub-id-type="doi">10.1007/s42835-020-00456-z</pub-id>
</citation>
</ref>
<ref id="B96">
<citation citation-type="journal">
<person-group person-group-type="author">
<name>
<surname>Nezamzadeh-Ejieh</surname>
<given-names>S.</given-names>
</name>
<name>
<surname>Sadeghkhani</surname>
<given-names>I.</given-names>
</name>
</person-group> (<year>2020</year>). <article-title>HIF detection in distribution networks based on Kullback-Leibler divergence</article-title>. <source>IET Gener. Transm. Distrib.</source> <volume>14</volume> (<issue>1</issue>), <fpage>29</fpage>&#x2013;<lpage>36</lpage>. <pub-id pub-id-type="doi">10.1049/iet-gtd.2019.0001</pub-id>
</citation>
</ref>
<ref id="B97">
<citation citation-type="journal">
<person-group person-group-type="author">
<name>
<surname>Nikoofekr</surname>
<given-names>I.</given-names>
</name>
<name>
<surname>Sarlak</surname>
<given-names>M.</given-names>
</name>
<name>
<surname>Shahrtash</surname>
<given-names>S. M.</given-names>
</name>
</person-group> (<year>2013</year>). <article-title>Detection and classification of high impedance faults in power distribution networks using ART neural networks</article-title>. <source>2013 21st Iran. Conf. Electr. Eng. ICEE</source>, <fpage>1</fpage>&#x2013;<lpage>6</lpage>. <pub-id pub-id-type="doi">10.1109/IranianCEE.2013.6599760</pub-id>
</citation>
</ref>
<ref id="B98">
<citation citation-type="journal">
<person-group person-group-type="author">
<name>
<surname>Panigrahi</surname>
<given-names>R. R.</given-names>
</name>
<name>
<surname>Mishra</surname>
<given-names>M.</given-names>
</name>
<name>
<surname>Rajan</surname>
<given-names>A.</given-names>
</name>
<name>
<surname>Mohapatra</surname>
<given-names>S.</given-names>
</name>
</person-group> (<year>2018</year>). <article-title>High Impedance Fault detection based on mathematical morphology for radial distribution network</article-title>. <source>2018 Int. Conf. Appl. Electromagn. Signal Process. Commun. AESPC</source> <volume>2018</volume>. <pub-id pub-id-type="doi">10.1109/AESPC44649.2018.9033309</pub-id>
</citation>
</ref>
<ref id="B99">
<citation citation-type="journal">
<person-group person-group-type="author">
<name>
<surname>Prasad</surname>
<given-names>C. D.</given-names>
</name>
<name>
<surname>Biswal</surname>
<given-names>M.</given-names>
</name>
<name>
<surname>Mishra</surname>
<given-names>M.</given-names>
</name>
<name>
<surname>Guerrero</surname>
<given-names>J. M.</given-names>
</name>
<name>
<surname>Malik</surname>
<given-names>O. P.</given-names>
</name>
</person-group> (<year>2022</year>). <article-title>Optimal threshold-based high impedance arc fault detection approach for renewable penetrated distribution system</article-title>. <source>IEEE Syst. J.</source>, <fpage>1</fpage>&#x2013;<lpage>11</lpage>. <pub-id pub-id-type="doi">10.1109/JSYST.2022.3202809</pub-id>
</citation>
</ref>
<ref id="B100">
<citation citation-type="book">
<person-group person-group-type="author">
<name>
<surname>Radhakrishnan</surname>
<given-names>A.</given-names>
</name>
</person-group> (<year>2019</year>). <source>Location of high impedance faults using smart meters in distribution systems with DGs, power electronic loads and Electric Arc furnaces</source>. <publisher-name>IEEE Milan PowerTech</publisher-name>, <fpage>1</fpage>&#x2013;<lpage>6</lpage>.</citation>
</ref>
<ref id="B101">
<citation citation-type="journal">
<person-group person-group-type="author">
<name>
<surname>Reddy</surname>
<given-names>S. H.</given-names>
</name>
<name>
<surname>Garg</surname>
<given-names>R.</given-names>
</name>
<name>
<surname>Pillai</surname>
<given-names>G. N.</given-names>
</name>
</person-group> (<year>2013</year>). <article-title>High Impedance Fault classification and section identification using extreme learning machines (ELM)</article-title>. <source>Ripublication. Com.</source> <volume>3</volume> (<issue>7</issue>), <fpage>839</fpage>&#x2013;<lpage>846</lpage>.</citation>
</ref>
<ref id="B102">
<citation citation-type="journal">
<person-group person-group-type="author">
<name>
<surname>Roberts</surname>
<given-names>J.</given-names>
</name>
<name>
<surname>Altuve</surname>
<given-names>H. J.</given-names>
</name>
<name>
<surname>Hou</surname>
<given-names>D.</given-names>
</name>
</person-group> (<year>2001</year>). <article-title>Review of ground fault protection methods for grounded, ungrounded, and compensated distribution systems</article-title>. <source>27th Annu. West. Prot. Relay Conf.</source> <volume>40</volume>.</citation>
</ref>
<ref id="B103">
<citation citation-type="journal">
<person-group person-group-type="author">
<name>
<surname>Routray</surname>
<given-names>P.</given-names>
</name>
<name>
<surname>Mishra</surname>
<given-names>M.</given-names>
</name>
<name>
<surname>Rout</surname>
<given-names>P. K.</given-names>
</name>
</person-group> (<year>2016</year>). <article-title>High Impedance Fault detection in radial distribution system using S-Transform and neural network</article-title>. <source>2015 IEEE Power, Commun. Inf. Technol. Conf. PCITC 2015 - Proc.</source>, <fpage>545</fpage>&#x2013;<lpage>551</lpage>. <pub-id pub-id-type="doi">10.1109/PCITC.2015.7438225</pub-id>
</citation>
</ref>
<ref id="B104">
<citation citation-type="journal">
<person-group person-group-type="author">
<name>
<surname>Russell</surname>
<given-names>B. D.</given-names>
</name>
<name>
<surname>Benner</surname>
<given-names>C. L.</given-names>
</name>
</person-group> (<year>1995</year>). <article-title>Arcing Fault detection for distribution feeders: Security assessment in long term field trials</article-title>. <source>IEEE Trans. Power Deliv.</source> <volume>10</volume> (<issue>2</issue>), <fpage>676</fpage>&#x2013;<lpage>683</lpage>. <pub-id pub-id-type="doi">10.1109/61.400864</pub-id>
</citation>
</ref>
<ref id="B105">
<citation citation-type="journal">
<person-group person-group-type="author">
<name>
<surname>Russell</surname>
<given-names>B. D.</given-names>
</name>
<name>
<surname>Chinchali</surname>
<given-names>R. P.</given-names>
</name>
<name>
<surname>Kim</surname>
<given-names>C. J.</given-names>
</name>
</person-group> (<year>1988</year>). <article-title>Behaviour of low frequency spectra during arcing fault and switching events</article-title>. <source>IEEE Trans. Power Deliv.</source> <volume>3</volume> (<issue>4</issue>), <fpage>1485</fpage>&#x2013;<lpage>1492</lpage>. <pub-id pub-id-type="doi">10.1109/61.193947</pub-id>
</citation>
</ref>
<ref id="B106">
<citation citation-type="journal">
<person-group person-group-type="author">
<name>
<surname>Sahoo</surname>
<given-names>S.</given-names>
</name>
<name>
<surname>Baran</surname>
<given-names>M. E.</given-names>
</name>
</person-group> (<year>2014</year>). <article-title>A method to detect high impedance faults in distribution feeders</article-title>. <source>Proc. IEEE Power Eng. Soc. Transm. Distrib. Conf.</source>, <fpage>1</fpage>&#x2013;<lpage>6</lpage>. <pub-id pub-id-type="doi">10.1109/tdc.2014.6863531</pub-id>
</citation>
</ref>
<ref id="B107">
<citation citation-type="journal">
<person-group person-group-type="author">
<name>
<surname>Samantaray</surname>
<given-names>P. K. D. S. R.</given-names>
</name>
<name>
<surname>Gouvea</surname>
<given-names>M.</given-names>
</name>
<name>
<surname>Lacerda</surname>
<given-names>A.</given-names>
</name>
<name>
<surname>Alves</surname>
<given-names>F.</given-names>
</name>
<name>
<surname>Leite</surname>
<given-names>D.</given-names>
</name>
</person-group> (<year>2009</year>). <article-title>High impedance fault detection in power distribution systems using wavelet transform and evolving neural network</article-title>. <source>Electr. Power Syst. Res.</source> <volume>154</volume> (<issue>2</issue>), <fpage>474</fpage>&#x2013;<lpage>483</lpage>. <pub-id pub-id-type="doi">10.1016/j.epsr.2017.08.039</pub-id>
</citation>
</ref>
<ref id="B108">
<citation citation-type="journal">
<person-group person-group-type="author">
<name>
<surname>Samantaray</surname>
<given-names>S. R.</given-names>
</name>
<name>
<surname>Dash</surname>
<given-names>P. K.</given-names>
</name>
<name>
<surname>Upadhyay</surname>
<given-names>S. K.</given-names>
</name>
</person-group> (<year>2009</year>). <article-title>Adaptive Kalman filter and neural network based high impedance fault detection in power distribution networks</article-title>. <source>Int. J. Electr. Power Energy Syst.</source> <volume>31</volume> (<issue>4</issue>), <fpage>167</fpage>&#x2013;<lpage>172</lpage>. <pub-id pub-id-type="doi">10.1016/j.ijepes.2009.01.001</pub-id>
</citation>
</ref>
<ref id="B109">
<citation citation-type="journal">
<person-group person-group-type="author">
<name>
<surname>Samantaray</surname>
<given-names>S. R.</given-names>
</name>
</person-group> (<year>2012</year>). <article-title>Ensemble decision trees for high impedance fault detection in power distribution network</article-title>. <source>Int. J. Electr. Power Energy Syst.</source> <volume>43</volume> (<issue>1</issue>), <fpage>1048</fpage>&#x2013;<lpage>1055</lpage>. <pub-id pub-id-type="doi">10.1016/j.ijepes.2012.06.006</pub-id>
</citation>
</ref>
<ref id="B110">
<citation citation-type="journal">
<person-group person-group-type="author">
<name>
<surname>Samantaray</surname>
<given-names>S. R.</given-names>
</name>
<name>
<surname>Panigrahi</surname>
<given-names>B. K.</given-names>
</name>
<name>
<surname>Dash</surname>
<given-names>P. K.</given-names>
</name>
</person-group> (<year>2008</year>). <article-title>High impedance fault detection in power distribution networks using time-frequency transform and probabilistic neural network</article-title>. <source>IET Gener. Transm. Distrib.</source> <volume>2</volume> (<issue>2</issue>), <fpage>261</fpage>&#x2013;<lpage>270</lpage>. <pub-id pub-id-type="doi">10.1049/iet-gtd:20070319</pub-id>
</citation>
</ref>
<ref id="B111">
<citation citation-type="journal">
<person-group person-group-type="author">
<name>
<surname>Santos</surname>
<given-names>W. C.</given-names>
</name>
<name>
<surname>Lopes</surname>
<given-names>F. V.</given-names>
</name>
<name>
<surname>Brito</surname>
<given-names>N. S. D.</given-names>
</name>
<name>
<surname>Souza</surname>
<given-names>B. A.</given-names>
</name>
</person-group> (<year>2017</year>). <article-title>High-impedance fault identification on distribution networks</article-title>. <source>IEEE Trans. Power Deliv.</source> <volume>32</volume> (<issue>1</issue>), <fpage>23</fpage>&#x2013;<lpage>32</lpage>. <pub-id pub-id-type="doi">10.1109/TPWRD.2016.2548942</pub-id>
</citation>
</ref>
<ref id="B112">
<citation citation-type="journal">
<person-group person-group-type="author">
<name>
<surname>Santos</surname>
<given-names>W. C.</given-names>
</name>
<name>
<surname>V Lopes</surname>
<given-names>F.</given-names>
</name>
<name>
<surname>Brito</surname>
<given-names>N. S. D.</given-names>
</name>
<name>
<surname>Souza</surname>
<given-names>B. A.</given-names>
</name>
<name>
<surname>Fernandes.</surname>
<given-names>J. D.</given-names>
</name>
<name>
<surname>Neves</surname>
<given-names>W. L. A.</given-names>
</name>
</person-group> (<year>2013</year>). <article-title>High Impedance Fault detection and location based on electromagnetic transient analysis</article-title>. <source>Int. Conf. Power Syst. Transients</source>. <comment>[Online]. Available at: <ext-link ext-link-type="uri" xlink:href="http://www.ipstconf.org/papers/Proc_IPST2013/13IPST135.pdf">http://www.ipstconf.org/papers/Proc_IPST2013/13IPST135.pdf</ext-link>.</comment>
</citation>
</ref>
<ref id="B113">
<citation citation-type="book">
<person-group person-group-type="author">
<name>
<surname>Sarlak</surname>
<given-names>M.</given-names>
</name>
<name>
<surname>Shahrtash</surname>
<given-names>S. M.</given-names>
</name>
</person-group> (<year>2008</year>). &#x201c;<article-title>High impedance fault detection in distribution networks using support vector machines based on wavelet transform</article-title>,&#x201d; in <source>2008 IEEE electr. Power energy conf. - energy innov</source>, <fpage>1</fpage>&#x2013;<lpage>6</lpage>. <pub-id pub-id-type="doi">10.1109/EPC.2008.4763380</pub-id>
</citation>
</ref>
<ref id="B114">
<citation citation-type="journal">
<person-group person-group-type="author">
<name>
<surname>Sarlak</surname>
<given-names>M.</given-names>
</name>
<name>
<surname>Shahrtash</surname>
<given-names>S. M.</given-names>
</name>
</person-group> (<year>2011</year>). <article-title>High impedance fault detection using combination of multi-layer perceptron neural networks based on multi-resolution morphological gradient features of current waveform</article-title>. <source>IET Gener. Transm. Distrib.</source> <volume>5</volume> (<issue>5</issue>), <fpage>588</fpage>&#x2013;<lpage>595</lpage>. <pub-id pub-id-type="doi">10.1049/iet-gtd.2010.0702</pub-id>
</citation>
</ref>
<ref id="B115">
<citation citation-type="journal">
<person-group person-group-type="author">
<name>
<surname>Sarlak</surname>
<given-names>M.</given-names>
</name>
<name>
<surname>Shahrtash</surname>
<given-names>S. M.</given-names>
</name>
</person-group> (<year>2013</year>). <article-title>High-impedance faulted branch identification using magnetic-field signature analysis</article-title>. <source>IEEE Trans. Power Deliv.</source> <volume>28</volume> (<issue>1</issue>), <fpage>67</fpage>&#x2013;<lpage>74</lpage>. <pub-id pub-id-type="doi">10.1109/TPWRD.2012.2222056</pub-id>
</citation>
</ref>
<ref id="B116">
<citation citation-type="journal">
<person-group person-group-type="author">
<name>
<surname>Sarwagya</surname>
<given-names>K.</given-names>
</name>
<name>
<surname>De</surname>
<given-names>S.</given-names>
</name>
<name>
<surname>Nayak</surname>
<given-names>P. K.</given-names>
</name>
</person-group> (<year>2018</year>). <article-title>High-impedance fault detection in electrical power distribution systems using moving sum approach</article-title>. <source>IET Sci. Meas. Technol.</source> <volume>12</volume> (<issue>1</issue>), <fpage>1</fpage>&#x2013;<lpage>8</lpage>. <pub-id pub-id-type="doi">10.1049/iet-smt.2017.0231</pub-id>
</citation>
</ref>
<ref id="B117">
<citation citation-type="journal">
<person-group person-group-type="author">
<name>
<surname>Sarwar</surname>
<given-names>M.</given-names>
</name>
<name>
<surname>Mehmood</surname>
<given-names>F.</given-names>
</name>
<name>
<surname>Abid</surname>
<given-names>M.</given-names>
</name>
<name>
<surname>Khan</surname>
<given-names>A. Q.</given-names>
</name>
<name>
<surname>Gul</surname>
<given-names>S. T.</given-names>
</name>
<name>
<surname>Khan</surname>
<given-names>A. S.</given-names>
</name>
</person-group> (<year>2020</year>). <article-title>High impedance fault detection and isolation in power distribution networks using support vector machines</article-title>. <source>J. King Saud. Univ. - Eng. Sci.</source> <volume>32</volume> (<issue>8</issue>), <fpage>524</fpage>&#x2013;<lpage>535</lpage>. <pub-id pub-id-type="doi">10.1016/j.jksues.2019.07.001</pub-id>
</citation>
</ref>
<ref id="B118">
<citation citation-type="book">
<person-group person-group-type="author">
<name>
<surname>Scott</surname>
<given-names>J. A.</given-names>
</name>
</person-group> (<year>1994</year>). <source>Impulse response analysis of a real feeder</source>. <publisher-name>Ieee Explor.</publisher-name>, <fpage>276</fpage>&#x2013;<lpage>283</lpage>.</citation>
</ref>
<ref id="B119">
<citation citation-type="journal">
<person-group person-group-type="author">
<name>
<surname>Sedighi</surname>
<given-names>A. R.</given-names>
</name>
<name>
<surname>Haghifam</surname>
<given-names>M. R.</given-names>
</name>
<name>
<surname>Malik</surname>
<given-names>O. P.</given-names>
</name>
<name>
<surname>Ghassemian</surname>
<given-names>M. H.</given-names>
</name>
</person-group> (<year>2005</year>). <article-title>High impedance fault detection based on wavelet transform and statistical pattern recognition</article-title>. <source>IEEE Trans. Power Deliv.</source> <volume>20</volume> (<issue>4</issue>), <fpage>2414</fpage>&#x2013;<lpage>2421</lpage>. <pub-id pub-id-type="doi">10.1109/TPWRD.2005.852367</pub-id>
</citation>
</ref>
<ref id="B120">
<citation citation-type="journal">
<person-group person-group-type="author">
<name>
<surname>Sedighi</surname>
<given-names>A. R.</given-names>
</name>
<name>
<surname>Haghifam</surname>
<given-names>M. R.</given-names>
</name>
<name>
<surname>Malik</surname>
<given-names>O. P.</given-names>
</name>
</person-group> (<year>2005</year>). <article-title>Soft computing applications in high impedance fault detection in distribution systems</article-title>. <source>Electr. Power Syst. Res.</source> <volume>76</volume> (<issue>1&#x2013;3</issue>), <fpage>136</fpage>&#x2013;<lpage>144</lpage>. <pub-id pub-id-type="doi">10.1016/j.epsr.2005.05.004</pub-id>
</citation>
</ref>
<ref id="B121">
<citation citation-type="journal">
<person-group person-group-type="author">
<name>
<surname>Sedighizadeh</surname>
<given-names>M.</given-names>
</name>
<name>
<surname>Rezazadeh</surname>
<given-names>A.</given-names>
</name>
<name>
<surname>Elkalashy</surname>
<given-names>N. I.</given-names>
</name>
</person-group> (<year>2010</year>). <article-title>Approaches in high impedance fault detection a Chronological review</article-title>. <source>Adv. Electr. Comput. Eng.</source> <volume>10</volume> (<issue>3</issue>), <fpage>114</fpage>&#x2013;<lpage>128</lpage>. <pub-id pub-id-type="doi">10.4316/aece.2010.03019</pub-id>
</citation>
</ref>
<ref id="B122">
<citation citation-type="journal">
<person-group person-group-type="author">
<name>
<surname>Sekar</surname>
<given-names>K.</given-names>
</name>
<name>
<surname>Mohanty</surname>
<given-names>N. K.</given-names>
</name>
</person-group> (<year>2020</year>). <article-title>A fuzzy rule base approach for High Impedance Fault detection in distribution system using Morphology Gradient filter</article-title>. <source>J. King Saud. Univ. - Eng. Sci.</source> <volume>32</volume> (<issue>3</issue>), <fpage>177</fpage>&#x2013;<lpage>185</lpage>. <pub-id pub-id-type="doi">10.1016/j.jksues.2018.12.001</pub-id>
</citation>
</ref>
<ref id="B123">
<citation citation-type="journal">
<person-group person-group-type="author">
<name>
<surname>Sekar</surname>
<given-names>K.</given-names>
</name>
<name>
<surname>Mohanty</surname>
<given-names>N. K.</given-names>
</name>
</person-group> (<year>2017</year>). <article-title>Combined mathematical morphology and data mining based high Impedance Fault detection</article-title>. <source>Energy Procedia</source> <volume>117</volume>, <fpage>417</fpage>&#x2013;<lpage>423</lpage>. <pub-id pub-id-type="doi">10.1016/j.egypro.2017.05.161</pub-id>
</citation>
</ref>
<ref id="B124">
<citation citation-type="journal">
<person-group person-group-type="author">
<name>
<surname>Sekar</surname>
<given-names>K.</given-names>
</name>
<name>
<surname>Mohanty</surname>
<given-names>N. K.</given-names>
</name>
</person-group> (<year>2018</year>). <article-title>Data mining-based high impedance fault detection using mathematical morphology</article-title>. <source>Comput. Electr. Eng.</source> <volume>69</volume> (<issue>5</issue>), <fpage>129</fpage>&#x2013;<lpage>141</lpage>. <pub-id pub-id-type="doi">10.1016/j.compeleceng.2018.05.010</pub-id>
</citation>
</ref>
<ref id="B125">
<citation citation-type="book">
<collab>SEL</collab> (<year>2007</year>). <source>Arc sense technology (AST) detect more faults than ever before</source>.</citation>
</ref>
<ref id="B126">
<citation citation-type="journal">
<person-group person-group-type="author">
<name>
<surname>Shahrtash</surname>
<given-names>S. M.</given-names>
</name>
<name>
<surname>Sarlak</surname>
<given-names>M.</given-names>
</name>
</person-group> (<year>2006</year>). <article-title>High impedance fault detection using harmonics energy decision tree algorithm</article-title>. <source>Int. Conf. Power Syst. Technol. POWERCON2006</source> <volume>00</volume>, <fpage>1</fpage>&#x2013;<lpage>5</lpage>. <pub-id pub-id-type="doi">10.1109/ICPST.2006.321441</pub-id>
</citation>
</ref>
<ref id="B127">
<citation citation-type="journal">
<person-group person-group-type="author">
<name>
<surname>Sharaf</surname>
<given-names>A. M.</given-names>
</name>
<name>
<surname>El-Sharkawy</surname>
<given-names>R. M.</given-names>
</name>
<name>
<surname>Al-Fatih</surname>
<given-names>R.</given-names>
</name>
<name>
<surname>Al-Ketbi</surname>
<given-names>M.</given-names>
</name>
</person-group> (<year>1996</year>). <article-title>High impedance fault detection on radial distribution and utilization systems</article-title>. <source>Can. Conf. Electr. Comput. Eng.</source> <volume>2</volume>, <fpage>1012</fpage>&#x2013;<lpage>1013</lpage>. <pub-id pub-id-type="doi">10.1109/ccece.1996.548326</pub-id>
</citation>
</ref>
<ref id="B128">
<citation citation-type="journal">
<person-group person-group-type="author">
<name>
<surname>Sharaf</surname>
<given-names>A. M.</given-names>
</name>
<name>
<surname>Snider</surname>
<given-names>L. A.</given-names>
</name>
<name>
<surname>Debnath</surname>
<given-names>K.</given-names>
</name>
</person-group> (<year>1993</year>). <article-title>A neural network based relaying scheme for distribution system high impedance fault detection</article-title>. <source>ANNES 1993 - 1st New Zeal. Int. Two-Stream Conf. Artif. Neural Netw. Expert Syst.</source>, <fpage>321</fpage>&#x2013;<lpage>324</lpage>. <pub-id pub-id-type="doi">10.1109/ANNES.1993.323013</pub-id>
</citation>
</ref>
<ref id="B129">
<citation citation-type="journal">
<person-group person-group-type="author">
<name>
<surname>Sheng</surname>
<given-names>Y.</given-names>
</name>
<name>
<surname>Rovnyak</surname>
<given-names>S. M.</given-names>
</name>
</person-group> (<year>2004</year>). <article-title>Decision tree-based methodology for high impedance fault detection</article-title>. <source>IEEE Trans. Power Deliv.</source> <volume>19</volume> (<issue>2</issue>), <fpage>533</fpage>&#x2013;<lpage>536</lpage>. <pub-id pub-id-type="doi">10.1109/TPWRD.2003.820418</pub-id>
</citation>
</ref>
<ref id="B130">
<citation citation-type="journal">
<person-group person-group-type="author">
<name>
<surname>Silva</surname>
<given-names>P. R.</given-names>
</name>
<name>
<surname>Santos</surname>
<given-names>A.</given-names>
</name>
<name>
<surname>Jota</surname>
<given-names>F. G.</given-names>
</name>
</person-group> (<year>1995</year>). <article-title>Intelligent system for automatic detection of high impedance faults in electrical distribution systems</article-title>. <source>Midwest Symp. Circuits Syst.</source> <volume>1</volume>, <fpage>453</fpage>&#x2013;<lpage>456</lpage>. <pub-id pub-id-type="doi">10.1109/mwscas.1995.504474</pub-id>
</citation>
</ref>
<ref id="B131">
<citation citation-type="journal">
<person-group person-group-type="author">
<name>
<surname>Silva</surname>
<given-names>S.</given-names>
</name>
<name>
<surname>Costa</surname>
<given-names>P.</given-names>
</name>
<name>
<surname>Santana</surname>
<given-names>M.</given-names>
</name>
<name>
<surname>Leite</surname>
<given-names>D.</given-names>
</name>
</person-group> (<year>2020</year>). <article-title>Evolving neuro-fuzzy network for real-time high impedance fault detection and classification</article-title>. <source>Neural comput. Appl.</source> <volume>32</volume> (<issue>12</issue>), <fpage>7597</fpage>&#x2013;<lpage>7610</lpage>. <pub-id pub-id-type="doi">10.1007/s00521-018-3789-2</pub-id>
</citation>
</ref>
<ref id="B132">
<citation citation-type="journal">
<person-group person-group-type="author">
<name>
<surname>Snider</surname>
<given-names>L. A.</given-names>
</name>
<name>
<surname>Shan</surname>
<given-names>Y. Y.</given-names>
</name>
</person-group> (<year>1998</year>). <article-title>Artificial neural networks based relay algorithm for distribution system high impedance fault detection</article-title>. <source>IEE Conf. Publ.</source> <volume>46</volume> (<issue>450</issue>), <fpage>100</fpage>&#x2013;<lpage>106</lpage>. <pub-id pub-id-type="doi">10.1049/cp:19971812</pub-id>
</citation>
</ref>
<ref id="B133">
<citation citation-type="journal">
<person-group person-group-type="author">
<name>
<surname>Snider</surname>
<given-names>L. A.</given-names>
</name>
<name>
<surname>Yuen</surname>
<given-names>Y. S.</given-names>
</name>
</person-group> (<year>1998</year>). <article-title>The artificial neural-networks-based relay algorithm for the detection of stochastic high impedance faults</article-title>. <source>Neurocomputing</source> <volume>23</volume> (<issue>1&#x2013;3</issue>), <fpage>243</fpage>&#x2013;<lpage>254</lpage>. <pub-id pub-id-type="doi">10.1016/S0925-2312(98)00068-X</pub-id>
</citation>
</ref>
<ref id="B134">
<citation citation-type="journal">
<person-group person-group-type="author">
<name>
<surname>Soheili</surname>
<given-names>A.</given-names>
</name>
<name>
<surname>Sadeh</surname>
<given-names>J.</given-names>
</name>
<name>
<surname>Bakhshi</surname>
<given-names>R.</given-names>
</name>
</person-group> (<year>2018</year>). <article-title>Modified FFT based high impedance fault detection technique considering distribution non-linear loads: Simulation and experimental data analysis</article-title>. <source>Int. J. Electr. Power Energy Syst.</source> <volume>94</volume>, <fpage>124</fpage>&#x2013;<lpage>140</lpage>. <pub-id pub-id-type="doi">10.1016/j.ijepes.2017.06.035</pub-id>
</citation>
</ref>
<ref id="B135">
<citation citation-type="journal">
<person-group person-group-type="author">
<name>
<surname>Suliman</surname>
<given-names>M. Y.</given-names>
</name>
<name>
<surname>Ghazal</surname>
<given-names>M. T.</given-names>
</name>
</person-group> (<year>2019</year>). <article-title>Detection of high impedance Fault in distribution network using fuzzy logic control</article-title>. <source>2nd Int. Conf. Electr. Commun. Comput. Power Control Eng. ICECCPCE</source>, <fpage>103</fpage>&#x2013;<lpage>108</lpage>. <pub-id pub-id-type="doi">10.1109/ICECCPCE46549.2019.203756</pub-id>
</citation>
</ref>
<ref id="B136">
<citation citation-type="journal">
<person-group person-group-type="author">
<name>
<surname>Sultan</surname>
<given-names>A. F.</given-names>
</name>
<name>
<surname>Swift</surname>
<given-names>G. W.</given-names>
</name>
<name>
<surname>Fedirchuk</surname>
<given-names>D. J.</given-names>
</name>
</person-group> (<year>1994</year>). <article-title>Detecting arcing downed-wires using fault current flicker and half-cycle asymmetry</article-title>. <source>IEEE Trans. Power Deliv.</source> <volume>9</volume> (<issue>1</issue>), <fpage>461</fpage>&#x2013;<lpage>470</lpage>. <pub-id pub-id-type="doi">10.1109/61.277718</pub-id>
</citation>
</ref>
<ref id="B137">
<citation citation-type="journal">
<person-group person-group-type="author">
<name>
<surname>Sultan</surname>
<given-names>A. F.</given-names>
</name>
<name>
<surname>Swift</surname>
<given-names>G. W.</given-names>
</name>
<name>
<surname>Fedirchuk</surname>
<given-names>D. J.</given-names>
</name>
</person-group> (<year>1992</year>). <article-title>Detection of high impedance arcing faults using a multi-layer perceptron</article-title>. <source>IEEE Trans. Power Deliv.</source> <volume>7</volume> (<issue>4</issue>), <fpage>1871</fpage>&#x2013;<lpage>1877</lpage>. <pub-id pub-id-type="doi">10.1109/61.156989</pub-id>
</citation>
</ref>
<ref id="B138">
<citation citation-type="book">
<person-group person-group-type="author">
<name>
<surname>Sultan</surname>
<given-names>A. F.</given-names>
</name>
<name>
<surname>Swift</surname>
<given-names>G. W.</given-names>
</name>
</person-group> (<year>1992</year>). <source>Security testing of high impedance fault detectors</source>, <fpage>191</fpage>&#x2013;<lpage>197</lpage>. <pub-id pub-id-type="doi">10.1109/wescan.1991.160545</pub-id>
</citation>
</ref>
<ref id="B139">
<citation citation-type="journal">
<person-group person-group-type="author">
<name>
<surname>Tag Eldin</surname>
<given-names>E. S.</given-names>
</name>
<name>
<surname>Khalil Ibrahim</surname>
<given-names>D.</given-names>
</name>
<name>
<surname>Aboul-Zahab</surname>
<given-names>E. M.</given-names>
</name>
<name>
<surname>Saleh</surname>
<given-names>S. M.</given-names>
</name>
</person-group> (<year>2009</year>). <article-title>High impedance fault detection in EHV series compensated lines using the wavelet transform</article-title>. <source>IEEE/PES Power Syst. Conf. Expo. PSCE</source>, <fpage>2009</fpage>. <pub-id pub-id-type="doi">10.1109/PSCE.2009.4840082</pub-id>
</citation>
</ref>
<ref id="B140">
<citation citation-type="journal">
<person-group person-group-type="author">
<name>
<surname>Tawafan</surname>
<given-names>A.</given-names>
</name>
<name>
<surname>Bin Sulaiman</surname>
<given-names>M.</given-names>
</name>
<name>
<surname>Bin Ibrahim</surname>
<given-names>Z.</given-names>
</name>
</person-group> (<year>2012</year>). <article-title>Adaptive neural subtractive clustering fuzzy inference system for the detection of high Impedance Fault on distribution power system</article-title>. <source>IAES Int. J. Artif. Intell.</source> <volume>1</volume> (<issue>2</issue>). <pub-id pub-id-type="doi">10.11591/ij-ai.v1i2.425</pub-id>
</citation>
</ref>
<ref id="B141">
<citation citation-type="book">
<person-group person-group-type="author">
<name>
<surname>Tengdin</surname>
<given-names>J.</given-names>
</name>
<name>
<surname>Westfall</surname>
<given-names>R.</given-names>
</name>
<name>
<surname>Stephan</surname>
<given-names>K.</given-names>
</name>
</person-group> (<year>1996</year>). <source>High Impedance Fault detection technology</source> <publisher-loc>Los Angeles, CA, United States of America</publisher-loc>: <publisher-name>Rep. PSRC Work. Gr.</publisher-name>, <fpage>1</fpage>&#x2013;<lpage>4</lpage>. <comment>[Online]. Available at: <ext-link ext-link-type="uri" xlink:href="http://grouper.ieee.org/groups/td/dist/documents/highz.pdf">http://grouper.ieee.org/groups/td/dist/documents/highz.pdf</ext-link>.</comment>
</citation>
</ref>
<ref id="B142">
<citation citation-type="journal">
<person-group person-group-type="author">
<name>
<surname>Theron</surname>
<given-names>J. C. J.</given-names>
</name>
<name>
<surname>Pal</surname>
<given-names>A.</given-names>
</name>
<name>
<surname>Varghese</surname>
<given-names>A.</given-names>
</name>
</person-group> (<year>2018</year>). <article-title>Tutorial on high impedance fault detection</article-title>. <source>71st Annu. Conf. Prot. Relay Eng. CPRE</source> <volume>2018</volume>, <fpage>1</fpage>&#x2013;<lpage>23</lpage>. <pub-id pub-id-type="doi">10.1109/CPRE.2018.8349833</pub-id>
</citation>
</ref>
<ref id="B143">
<citation citation-type="journal">
<person-group person-group-type="author">
<name>
<surname>Thomas</surname>
<given-names>M. S.</given-names>
</name>
<name>
<surname>Bhaskar</surname>
<given-names>N.</given-names>
</name>
<name>
<surname>Prakash</surname>
<given-names>A.</given-names>
</name>
</person-group> (<year>2016</year>). <article-title>Voltage based detection method for high Impedance Fault in a distribution system</article-title>. <source>J. Inst. Eng. Ser. B</source> <volume>97</volume> (<issue>3</issue>), <fpage>413</fpage>&#x2013;<lpage>423</lpage>. <pub-id pub-id-type="doi">10.1007/s40031-015-0203-7</pub-id>
</citation>
</ref>
<ref id="B144">
<citation citation-type="journal">
<person-group person-group-type="author">
<name>
<surname>Tonelli-Neto</surname>
<given-names>M. S.</given-names>
</name>
<name>
<surname>Decanini</surname>
<given-names>J. G. M. S.</given-names>
</name>
<name>
<surname>Lotufo</surname>
<given-names>A. D. P.</given-names>
</name>
<name>
<surname>Minussi</surname>
<given-names>C. R.</given-names>
</name>
</person-group> (<year>2017</year>). <article-title>Fuzzy based methodologies comparison for high-impedance fault diagnosis in radial distribution feeders</article-title>. <source>IET Gener. Transm. Distrib.</source> <volume>11</volume> (<issue>6</issue>), <fpage>1557</fpage>&#x2013;<lpage>1565</lpage>. <pub-id pub-id-type="doi">10.1049/iet-gtd.2016.1409</pub-id>
</citation>
</ref>
<ref id="B145">
<citation citation-type="journal">
<person-group person-group-type="author">
<name>
<surname>Vahidi</surname>
<given-names>B.</given-names>
</name>
<name>
<surname>Ghaffarzadeh</surname>
<given-names>N.</given-names>
</name>
<name>
<surname>Hosseinian</surname>
<given-names>S. H.</given-names>
</name>
<name>
<surname>Ahadi</surname>
<given-names>S. M.</given-names>
</name>
</person-group> (<year>2010</year>). <article-title>An approach to detection of high Impedance Fault using discrete wavelet transform and artificial neural networks</article-title>. <source>Simulation</source> <volume>86</volume> (<issue>4</issue>), <fpage>203</fpage>&#x2013;<lpage>215</lpage>. <pub-id pub-id-type="doi">10.1177/0037549709340823</pub-id>
</citation>
</ref>
<ref id="B146">
<citation citation-type="journal">
<person-group person-group-type="author">
<name>
<surname>Veerasamy</surname>
<given-names>V.</given-names>
</name>
<name>
<surname>Abdul Wahab</surname>
<given-names>N. I.</given-names>
</name>
<name>
<surname>Ramachandran</surname>
<given-names>R.</given-names>
</name>
<name>
<surname>Mansoor</surname>
<given-names>M.</given-names>
</name>
<name>
<surname>Thirumeni</surname>
<given-names>M.</given-names>
</name>
<name>
<surname>Othman</surname>
<given-names>M. L.</given-names>
</name>
</person-group> (<year>2018</year>). <article-title>High impedance fault detection in medium voltage distribution network using discrete wavelet transform and adaptive neuro-fuzzy inference system</article-title>. <source>Energies</source> <volume>11</volume>, <fpage>3330</fpage>. <pub-id pub-id-type="doi">10.3390/en11123330</pub-id>
</citation>
</ref>
<ref id="B147">
<citation citation-type="journal">
<person-group person-group-type="author">
<name>
<surname>Veerasamy</surname>
<given-names>V.</given-names>
</name>
<name>
<surname>Abdul Wahab</surname>
<given-names>N. I.</given-names>
</name>
<name>
<surname>Ramachandran</surname>
<given-names>R.</given-names>
</name>
<name>
<surname>Thirumeni</surname>
<given-names>M.</given-names>
</name>
<name>
<surname>Subramanian</surname>
<given-names>C.</given-names>
</name>
<name>
<surname>Othman</surname>
<given-names>M. L.</given-names>
</name>
<etal/>
</person-group> (<year>2019</year>). <article-title>High-impedance fault detection in medium-voltage distribution network using computational intelligence-based classifiers</article-title>. <source>Neural comput. Appl.</source> <volume>31</volume> (<issue>12</issue>), <fpage>9127</fpage>&#x2013;<lpage>9143</lpage>. <pub-id pub-id-type="doi">10.1007/s00521-019-04445-w</pub-id>
</citation>
</ref>
<ref id="B148">
<citation citation-type="journal">
<person-group person-group-type="author">
<name>
<surname>Vyshnavi</surname>
<given-names>G.</given-names>
</name>
<name>
<surname>Prasad</surname>
<given-names>A.</given-names>
</name>
</person-group> (<year>2018</year>). <article-title>Detection and location of high impedance faults in distribution systems: A review</article-title>. <source>Int. J. Adv. Sci. Technol.</source> <volume>119</volume>, <fpage>53</fpage>&#x2013;<lpage>66</lpage>. <pub-id pub-id-type="doi">10.14257/ijast.2018.119.05</pub-id>
</citation>
</ref>
<ref id="B149">
<citation citation-type="journal">
<person-group person-group-type="author">
<name>
<surname>Wali</surname>
<given-names>M. K.</given-names>
</name>
<name>
<surname>Hussain</surname>
<given-names>A. N.</given-names>
</name>
<name>
<surname>Hani</surname>
<given-names>W. F.</given-names>
</name>
</person-group> (<year>2018</year>). <article-title>High impedance fault detection based on power spectrum technique</article-title>. <source>Proc. 2017 Int. Conf. Eng. Technol. ICET 2017</source> <volume>2018</volume>, <fpage>1</fpage>&#x2013;<lpage>6</lpage>. <pub-id pub-id-type="doi">10.1109/ICEngTechnol.2017.8308169</pub-id>
</citation>
</ref>
<ref id="B150">
<citation citation-type="journal">
<person-group person-group-type="author">
<name>
<surname>Wang</surname>
<given-names>B.</given-names>
</name>
<name>
<surname>Geng</surname>
<given-names>J.</given-names>
</name>
<name>
<surname>Dong</surname>
<given-names>X.</given-names>
</name>
</person-group> (<year>2018</year>). <article-title>High-impedance fault detection based on nonlinear voltage-current characteristic profile identification</article-title>. <source>IEEE Trans. Smart Grid</source> <volume>9</volume> (<issue>4</issue>), <fpage>3783</fpage>&#x2013;<lpage>3791</lpage>. <pub-id pub-id-type="doi">10.1109/TSG.2016.2642988</pub-id>
</citation>
</ref>
<ref id="B151">
<citation citation-type="journal">
<person-group person-group-type="author">
<name>
<surname>Wang</surname>
<given-names>X.</given-names>
</name>
<name>
<surname>Gao</surname>
<given-names>J.</given-names>
</name>
<name>
<surname>Wei</surname>
<given-names>X.</given-names>
</name>
<name>
<surname>Song</surname>
<given-names>G.</given-names>
</name>
<name>
<surname>Wu</surname>
<given-names>L.</given-names>
</name>
<name>
<surname>Liu</surname>
<given-names>J.</given-names>
</name>
<etal/>
</person-group> (<year>2019</year>). <article-title>High impedance fault detection method based on variational mode decomposition and teager-kaiser energy operators for distribution network</article-title>. <source>IEEE Trans. Smart Grid</source> <volume>10</volume> (<issue>6</issue>), <fpage>6041</fpage>&#x2013;<lpage>6054</lpage>. <pub-id pub-id-type="doi">10.1109/TSG.2019.2895634</pub-id>
</citation>
</ref>
<ref id="B152">
<citation citation-type="journal">
<person-group person-group-type="author">
<name>
<surname>Wester</surname>
<given-names>C. G.</given-names>
</name>
</person-group> (<year>1998</year>). <article-title>High impedance fault detection on distribution systems</article-title>. <source>Pap. - Rural. Electr. Power Conf</source>. <pub-id pub-id-type="doi">10.11591/ijaas.v8.i2.pp95-102</pub-id>
</citation>
</ref>
<ref id="B153">
<citation citation-type="journal">
<person-group person-group-type="author">
<name>
<surname>Xie</surname>
<given-names>S.</given-names>
</name>
<name>
<surname>Wang</surname>
<given-names>X.</given-names>
</name>
<name>
<surname>Qu</surname>
<given-names>C.</given-names>
</name>
<name>
<surname>Wang</surname>
<given-names>X.</given-names>
</name>
<name>
<surname>Guo</surname>
<given-names>J.</given-names>
</name>
</person-group> (<year>2013</year>). <article-title>DT-CWT based event feature extraction for high impedance faults detection in distribution system</article-title>. <source>Int. Trans. Electr. energy Syst.</source> <volume>20</volume>, <fpage>1</fpage>&#x2013;<lpage>6</lpage>. <pub-id pub-id-type="doi">10.1002/etep</pub-id>
</citation>
</ref>
<ref id="B154">
<citation citation-type="journal">
<person-group person-group-type="author">
<name>
<surname>Xie</surname>
<given-names>S.</given-names>
</name>
<name>
<surname>Wang</surname>
<given-names>X.</given-names>
</name>
<name>
<surname>Qu</surname>
<given-names>C.</given-names>
</name>
<name>
<surname>Wang</surname>
<given-names>X.</given-names>
</name>
<name>
<surname>Guo</surname>
<given-names>J.</given-names>
</name>
</person-group> (<year>2013</year>). <article-title>High impedance fault detection in distribution feeders using extended kalman filter and support vector machine</article-title>. <source>Int. Trans. Electr. energy Syst.</source> <volume>20</volume>, <fpage>1</fpage>&#x2013;<lpage>6</lpage>. <pub-id pub-id-type="doi">10.1002/etep</pub-id>
</citation>
</ref>
<ref id="B155">
<citation citation-type="journal">
<person-group person-group-type="author">
<name>
<surname>Yang</surname>
<given-names>M. T.</given-names>
</name>
<name>
<surname>Gu</surname>
<given-names>J. C.</given-names>
</name>
<name>
<surname>Guan</surname>
<given-names>J. L.</given-names>
</name>
<name>
<surname>Cheng</surname>
<given-names>C. Y.</given-names>
</name>
</person-group> (<year>2006</year>). <article-title>Evaluation of algorithms for high impedance faults identification based on staged fault tests</article-title>. <source>2006 IEEE Power Eng. Soc. Gen. Meet. PES</source>, <fpage>1</fpage>&#x2013;<lpage>8</lpage>. <pub-id pub-id-type="doi">10.1109/pes.2006.1709122</pub-id>
</citation>
</ref>
<ref id="B156">
<citation citation-type="journal">
<person-group person-group-type="author">
<name>
<surname>Yang</surname>
<given-names>M. T.</given-names>
</name>
<name>
<surname>Gu</surname>
<given-names>J. C.</given-names>
</name>
<name>
<surname>Jeng</surname>
<given-names>C. Y.</given-names>
</name>
<name>
<surname>Kao</surname>
<given-names>W. S.</given-names>
</name>
</person-group> (<year>2004</year>). <article-title>Detection high impedance fault in distribution feeder using wavelet transform and artificial neural networks</article-title>. <source>Int. Conf. Power Syst. Technol. POWERCON</source> <volume>1</volume> (<issue>11</issue>), <fpage>652</fpage>&#x2013;<lpage>657</lpage>. <pub-id pub-id-type="doi">10.1109/icpst.2004.1460075</pub-id>
</citation>
</ref>
<ref id="B157">
<citation citation-type="journal">
<person-group person-group-type="author">
<name>
<surname>Yeh</surname>
<given-names>H. G.</given-names>
</name>
<name>
<surname>Sim</surname>
<given-names>S.</given-names>
</name>
<name>
<surname>Bravo</surname>
<given-names>R. J.</given-names>
</name>
</person-group> (<year>2019</year>). <article-title>Wavelet and denoising techniques for real-time HIF detection in 12-kV distribution circuits</article-title>. <source>IEEE Syst. J.</source> <volume>13</volume> (<issue>4</issue>), <fpage>4365</fpage>&#x2013;<lpage>4373</lpage>. <pub-id pub-id-type="doi">10.1109/JSYST.2019.2942093</pub-id>
</citation>
</ref>
<ref id="B158">
<citation citation-type="journal">
<person-group person-group-type="author">
<name>
<surname>Yeh</surname>
<given-names>H. G.</given-names>
</name>
<name>
<surname>Tran</surname>
<given-names>D. H.</given-names>
</name>
<name>
<surname>Yinger</surname>
<given-names>R.</given-names>
</name>
</person-group> (<year>2014</year>). <article-title>High impedance fault detection using orthogonal transforms</article-title>. <source>2014 IEEE Green Energy Syst. Conf. IGESC</source>, <fpage>67</fpage>&#x2013;<lpage>72</lpage>. <pub-id pub-id-type="doi">10.1109/IGESC.2014.7018642</pub-id>
</citation>
</ref>
<ref id="B159">
<citation citation-type="journal">
<person-group person-group-type="author">
<name>
<surname>Zamanan</surname>
<given-names>N.</given-names>
</name>
<name>
<surname>Sykulski</surname>
<given-names>J.</given-names>
</name>
<name>
<surname>Al-Othman</surname>
<given-names>A. K.</given-names>
</name>
</person-group> (<year>2007</year>). <article-title>Arcing high impedance fault detection using real coded genetic algorithm</article-title>. <source>Proc. 3rd IASTED Asian Conf. Power Energy Syst. AsiaPES</source> <volume>2007</volume>, <fpage>35</fpage>&#x2013;<lpage>39</lpage>.</citation>
</ref>
<ref id="B160">
<citation citation-type="journal">
<person-group person-group-type="author">
<name>
<surname>Zamanan</surname>
<given-names>N.</given-names>
</name>
<name>
<surname>Sykulski</surname>
<given-names>J.</given-names>
</name>
</person-group> (<year>2014</year>). <article-title>The evolution of high impedance fault modeling</article-title>. <source>Proc. Int. Conf. Harmon. Qual. Power, ICHQP</source>, <fpage>77</fpage>&#x2013;<lpage>81</lpage>. <pub-id pub-id-type="doi">10.1109/ICHQP.2014.6842852</pub-id>
</citation>
</ref>
<ref id="B161">
<citation citation-type="journal">
<person-group person-group-type="author">
<name>
<surname>Zhang</surname>
<given-names>W.</given-names>
</name>
<name>
<surname>Jing</surname>
<given-names>Y.</given-names>
</name>
<name>
<surname>Xiao</surname>
<given-names>X.</given-names>
</name>
</person-group> (<year>2016</year>). <article-title>Model-based general arcing fault detection in medium-voltage distribution lines</article-title>. <source>IEEE Trans. Power Deliv.</source> <volume>31</volume> (<issue>5</issue>), <fpage>2231</fpage>&#x2013;<lpage>2241</lpage>. <pub-id pub-id-type="doi">10.1109/TPWRD.2016.2518738</pub-id>
</citation>
</ref>
</ref-list>
<sec id="s10">
<title>Nomenclature</title>
<def-list>
<def-item>
<term id="G1-fenrg.2023.1114230">
<bold>ANFIS</bold>
</term>
<def>
<p>Adaptive neuro-fuzzy inference system</p>
</def>
</def-item>
<def-item>
<term id="G2-fenrg.2023.1114230">
<bold>AEKF</bold>
</term>
<def>
<p>Adaptive extended Kalman filter</p>
</def>
</def-item>
<def-item>
<term id="G3-fenrg.2023.1114230">
<bold>ANN</bold>
</term>
<def>
<p>Artificial neural network</p>
</def>
</def-item>
<def-item>
<term id="G4-fenrg.2023.1114230">
<bold>CWT</bold>
</term>
<def>
<p>Continuous wavelet transform</p>
</def>
</def-item>
<def-item>
<term id="G5-fenrg.2023.1114230">
<bold>CNN</bold>
</term>
<def>
<p>Convolution neural network</p>
</def>
</def-item>
<def-item>
<term id="G6-fenrg.2023.1114230">
<bold>CERTS</bold>
</term>
<def>
<p>Consortium for Electric Reliability Technology Solutions</p>
</def>
</def-item>
<def-item>
<term id="G7-fenrg.2023.1114230">
<bold>DLGF</bold>
</term>
<def>
<p>Double-line-to-ground fault</p>
</def>
</def-item>
<def-item>
<term id="G8-fenrg.2023.1114230">
<bold>DWT</bold>
</term>
<def>
<p>Discrete wavelet transform</p>
</def>
</def-item>
<def-item>
<term id="G9-fenrg.2023.1114230">
<bold>DTWT</bold>
</term>
<def>
<p>Dual-tree complex wavelet transform</p>
</def>
</def-item>
<def-item>
<term id="G10-fenrg.2023.1114230">
<bold>DG</bold>
</term>
<def>
<p>Distributed generators</p>
</def>
</def-item>
<def-item>
<term id="G11-fenrg.2023.1114230">
<bold>DT</bold>
</term>
<def>
<p>Decision tree</p>
</def>
</def-item>
<def-item>
<term id="G12-fenrg.2023.1114230">
<bold>ELM</bold>
</term>
<def>
<p>Extreme learning machines</p>
</def>
</def-item>
<def-item>
<term id="G13-fenrg.2023.1114230">
<bold>EKF</bold>
</term>
<def>
<p>Extended Kalman filter</p>
</def>
</def-item>
<def-item>
<term id="G14-fenrg.2023.1114230">
<bold>FFT</bold>
</term>
<def>
<p>Fast Fourier transform</p>
</def>
</def-item>
<def-item>
<term id="G15-fenrg.2023.1114230">
<bold>FFN</bold>
</term>
<def>
<p>Feedforward network</p>
</def>
</def-item>
<def-item>
<term id="G16-fenrg.2023.1114230">
<bold>FLC</bold>
</term>
<def>
<p>Fuzzy logic control</p>
</def>
</def-item>
<def-item>
<term id="G17-fenrg.2023.1114230">
<bold>FANN</bold>
</term>
<def>
<p>Fuzzy art neural network</p>
</def>
</def-item>
<def-item>
<term id="G18-fenrg.2023.1114230">
<bold>GA</bold>
</term>
<def>
<p>Genetic algorithm</p>
</def>
</def-item>
<def-item>
<term id="G19-fenrg.2023.1114230">
<bold>HT</bold>
</term>
<def>
<p>Hilbert Transform</p>
</def>
</def-item>
<def-item>
<term id="G20-fenrg.2023.1114230">
<bold>HIF</bold>
</term>
<def>
<p>High-impedance fault</p>
</def>
</def-item>
<def-item>
<term id="G21-fenrg.2023.1114230">
<bold>HIL</bold>
</term>
<def>
<p>Hardware-in-loop</p>
</def>
</def-item>
<def-item>
<term id="G22-fenrg.2023.1114230">
<bold>ILC</bold>
</term>
<def>
<p>Insulator leakage current</p>
</def>
</def-item>
<def-item>
<term id="G23-fenrg.2023.1114230">
<bold>IMF</bold>
</term>
<def>
<p>Intrinsic mode functions</p>
</def>
</def-item>
<def-item>
<term id="G24-fenrg.2023.1114230">
<bold>KNN</bold>
</term>
<def>
<p>k-Nearest neighbor</p>
</def>
</def-item>
<def-item>
<term id="G25-fenrg.2023.1114230">
<bold>LLF</bold>
</term>
<def>
<p>Line-to-line fault</p>
</def>
</def-item>
<def-item>
<term id="G26-fenrg.2023.1114230">
<bold>LDA</bold>
</term>
<def>
<p>Linear discriminant analysis</p>
</def>
</def-item>
<def-item>
<term id="G27-fenrg.2023.1114230">
<bold>LWT</bold>
</term>
<def>
<p>Lifting wavelet transform</p>
</def>
</def-item>
<def-item>
<term id="G28-fenrg.2023.1114230">
<bold>LVQ</bold>
</term>
<def>
<p>Learning vector quantization</p>
</def>
</def-item>
<def-item>
<term id="G29-fenrg.2023.1114230">
<bold>MODWT</bold>
</term>
<def>
<p>Maximum overlap discrete wavelet transform</p>
</def>
</def-item>
<def-item>
<term id="G30-fenrg.2023.1114230">
<bold>MMF</bold>
</term>
<def>
<p>Mathematical morphology filters</p>
</def>
</def-item>
<def-item>
<term id="G31-fenrg.2023.1114230">
<bold>MG</bold>
</term>
<def>
<p>Morphology gradient</p>
</def>
</def-item>
<def-item>
<term id="G32-fenrg.2023.1114230">
<bold>MLPNN</bold>
</term>
<def>
<p>Multi-layer perceptron neural network</p>
</def>
</def-item>
<def-item>
<term id="G33-fenrg.2023.1114230">
<bold>MWT</bold>
</term>
<def>
<p>Morlet wavelet transform</p>
</def>
</def-item>
<def-item>
<term id="G34-fenrg.2023.1114230">
<bold>PNN</bold>
</term>
<def>
<p>Probabilistic neural network</p>
</def>
</def-item>
<def-item>
<term id="G35-fenrg.2023.1114230">
<bold>PCA</bold>
</term>
<def>
<p>Principal component analysis</p>
</def>
</def-item>
<def-item>
<term id="G36-fenrg.2023.1114230">
<bold>PTDS</bold>
</term>
<def>
<p>Power transmission and distribution system</p>
</def>
</def-item>
<def-item>
<term id="G37-fenrg.2023.1114230">
<bold>PCC</bold>
</term>
<def>
<p>Point of common coupling</p>
</def>
</def-item>
<def-item>
<term id="G38-fenrg.2023.1114230">
<bold>RTDS</bold>
</term>
<def>
<p>Real-time digital simulator</p>
</def>
</def-item>
<def-item>
<term id="G39-fenrg.2023.1114230">
<bold>RF</bold>
</term>
<def>
<p>Random forest</p>
</def>
</def-item>
<def-item>
<term id="G40-fenrg.2023.1114230">
<bold>RCGA</bold>
</term>
<def>
<p>Real coded genetic algorithm</p>
</def>
</def-item>
<def-item>
<term id="G41-fenrg.2023.1114230">
<bold>ReLU</bold>
</term>
<def>
<p>Rectified linear unit</p>
</def>
</def-item>
<def-item>
<term id="G42-fenrg.2023.1114230">
<bold>SLGF</bold>
</term>
<def>
<p>Single-line-to-ground fault</p>
</def>
</def-item>
<def-item>
<term id="G43-fenrg.2023.1114230">
<bold>ST</bold>
</term>
<def>
<p>S transform</p>
</def>
</def-item>
<def-item>
<term id="G44-fenrg.2023.1114230">
<bold>SVM</bold>
</term>
<def>
<p>Support vector machine</p>
</def>
</def-item>
<def-item>
<term id="G45-fenrg.2023.1114230">
<bold>SNR</bold>
</term>
<def>
<p>Signal-to-noise ratio</p>
</def>
</def-item>
<def-item>
<term id="G46-fenrg.2023.1114230">
<bold>SD</bold>
</term>
<def>
<p>Standard deviation</p>
</def>
</def-item>
<def-item>
<term id="G47-fenrg.2023.1114230">
<bold>STFT</bold>
</term>
<def>
<p>Short-time Fourier transform</p>
</def>
</def-item>
<def-item>
<term id="G48-fenrg.2023.1114230">
<bold>SG</bold>
</term>
<def>
<p>Synchronous generator</p>
</def>
</def-item>
<def-item>
<term id="G49-fenrg.2023.1114230">
<bold>TFA</bold>
</term>
<def>
<p>Time-frequency analysis</p>
</def>
</def-item>
<def-item>
<term id="G50-fenrg.2023.1114230">
<bold>TSK</bold>
</term>
<def>
<p>Takagi&#x2013;Sugeno&#x2013;Kang</p>
</def>
</def-item>
<def-item>
<term id="G51-fenrg.2023.1114230">
<bold>TZSCs</bold>
</term>
<def>
<p>Transient zero sequence currents</p>
</def>
</def-item>
<def-item>
<term id="G52-fenrg.2023.1114230">
<bold>LLLGF</bold>
</term>
<def>
<p>Triple-line-to-ground fault</p>
</def>
</def-item>
<def-item>
<term id="G53-fenrg.2023.1114230">
<bold>TTT</bold>
</term>
<def>
<p>Time&#x2013;time transform</p>
</def>
</def-item>
<def-item>
<term id="G54-fenrg.2023.1114230">
<bold>VCCP</bold>
</term>
<def>
<p>Voltage&#x2013;current characteristic profiles</p>
</def>
</def-item>
<def-item>
<term id="G55-fenrg.2023.1114230">
<bold>WCC</bold>
</term>
<def>
<p>Wavelet correlation coefficient</p>
</def>
</def-item>
<def-item>
<term id="G56-fenrg.2023.1114230">
<bold>WHTs</bold>
</term>
<def>
<p>Walsh&#x2013;Hadamard transforms</p>
</def>
</def-item>
</def-list>
</sec>
</back>
</article>