<?xml version="1.0" encoding="UTF-8"?>
<!DOCTYPE article PUBLIC "-//NLM//DTD Journal Publishing DTD v2.3 20070202//EN" "journalpublishing.dtd">
<article article-type="research-article" dtd-version="2.3" xml:lang="EN" xmlns:mml="http://www.w3.org/1998/Math/MathML" xmlns:xlink="http://www.w3.org/1999/xlink">
<front>
<journal-meta>
<journal-id journal-id-type="publisher-id">Front. Energy Res.</journal-id>
<journal-title>Frontiers in Energy Research</journal-title>
<abbrev-journal-title abbrev-type="pubmed">Front. Energy Res.</abbrev-journal-title>
<issn pub-type="epub">2296-598X</issn>
<publisher>
<publisher-name>Frontiers Media S.A.</publisher-name>
</publisher>
</journal-meta>
<article-meta>
<article-id pub-id-type="publisher-id">1100789</article-id>
<article-id pub-id-type="doi">10.3389/fenrg.2023.1100789</article-id>
<article-categories>
<subj-group subj-group-type="heading">
<subject>Energy Research</subject>
<subj-group>
<subject>Original Research</subject>
</subj-group>
</subj-group>
</article-categories>
<title-group>
<article-title>An advanced short-circuit protection scheme for a bipolar DC microgrid</article-title>
<alt-title alt-title-type="left-running-head">Kant et al.</alt-title>
<alt-title alt-title-type="right-running-head">
<ext-link ext-link-type="uri" xlink:href="https://doi.org/10.3389/fenrg.2023.1100789">10.3389/fenrg.2023.1100789</ext-link>
</alt-title>
</title-group>
<contrib-group>
<contrib contrib-type="author" corresp="yes">
<name>
<surname>Kant</surname>
<given-names>Kamal</given-names>
</name>
<xref ref-type="corresp" rid="c001">&#x2a;</xref>
<uri xlink:href="https://loop.frontiersin.org/people/2094474/overview"/>
</contrib>
<contrib contrib-type="author">
<name>
<surname>Ansari</surname>
<given-names>Salauddin</given-names>
</name>
</contrib>
<contrib contrib-type="author">
<name>
<surname>Gupta</surname>
<given-names>Om Hari</given-names>
</name>
<uri xlink:href="https://loop.frontiersin.org/people/2164263/overview"/>
</contrib>
</contrib-group>
<aff>
<institution>Electrical Engineering Department</institution>, <institution>National Institute of Technology Jamshedpur</institution>, <addr-line>Jamshedpur</addr-line>, <country>India</country>
</aff>
<author-notes>
<fn fn-type="edited-by">
<p>
<bold>Edited by:</bold> <ext-link ext-link-type="uri" xlink:href="https://loop.frontiersin.org/people/1948006/overview">Mahamad Nabab Alam</ext-link>, National Institute of Technology Warangal, India</p>
</fn>
<fn fn-type="edited-by">
<p>
<bold>Reviewed by:</bold> <ext-link ext-link-type="uri" xlink:href="https://loop.frontiersin.org/people/2103533/overview">Anu Bhalla</ext-link>, Indian Institute of Technology Roorkee, India</p>
<p>
<ext-link ext-link-type="uri" xlink:href="https://loop.frontiersin.org/people/2111065/overview">Hareshkumar Sabhadia</ext-link>, Singapore Institute of Technology, Singapore</p>
<p>
<ext-link ext-link-type="uri" xlink:href="https://loop.frontiersin.org/people/578945/overview">Monalisa Biswal</ext-link>, National Institute of Technology Raipur, India</p>
</fn>
<corresp id="c001">&#x2a;Correspondence: Kamal Kant, <email>2021rsee004@nitjsr.ac.in</email>
</corresp>
<fn fn-type="other">
<p>This article was submitted to Smart Grids, a section of the journal Frontiers in Energy Research</p>
</fn>
</author-notes>
<pub-date pub-type="epub">
<day>19</day>
<month>01</month>
<year>2023</year>
</pub-date>
<pub-date pub-type="collection">
<year>2023</year>
</pub-date>
<volume>11</volume>
<elocation-id>1100789</elocation-id>
<history>
<date date-type="received">
<day>17</day>
<month>11</month>
<year>2022</year>
</date>
<date date-type="accepted">
<day>09</day>
<month>01</month>
<year>2023</year>
</date>
</history>
<permissions>
<copyright-statement>Copyright &#xa9; 2023 Kant, Ansari and Gupta.</copyright-statement>
<copyright-year>2023</copyright-year>
<copyright-holder>Kant, Ansari and Gupta</copyright-holder>
<license xlink:href="http://creativecommons.org/licenses/by/4.0/">
<p>This is an open-access article distributed under the terms of the Creative Commons Attribution License (CC BY). The use, distribution or reproduction in other forums is permitted, provided the original author(s) and the copyright owner(s) are credited and that the original publication in this journal is cited, in accordance with accepted academic practice. No use, distribution or reproduction is permitted which does not comply with these terms.</p>
</license>
</permissions>
<abstract>
<p>In order to provide quick and accurate fault detection in a DC microgrid, a new protection strategy is developed in this study. It is based on the multi-resolution analysis of travelling waves. The multi-resolution analysis of travelling waves is carried out using discrete wavelet transform (DWT). The dyadic filter bank theory is used to obtain the DWT coefficient of the voltage travelling wave. The energy of the DWT coefficient is then determined, and the fault will be identified if this energy content exceeds the predetermined threshold value. Initially, the efficacy of the proposed algorithm is verified on a 500&#xa0;V ring-type bipolar DC microgrid test model, which is developed with MATLAB/Simulink environment. Then the results obtained were later validated with the real-time simulator Opal-RT. The various simulation results indicate that the proposed algorithm can successfully be implemented in both modes, i.e., grid-integrated and islanded. It can also provide protection against high resistance fault (HRF) up to 900&#xa0;&#x2126; in grid-integrated mode, and up to 1,300&#xa0;&#x2126; in islanded mode. The operating time of the proposed algorithm is also quite fast, i.e., 0.64&#xa0;m.</p>
</abstract>
<kwd-group>
<kwd>DC microgrid</kwd>
<kwd>travelling wave</kwd>
<kwd>wavelet transform</kwd>
<kwd>high resistance faults</kwd>
<kwd>islanded mode protection</kwd>
</kwd-group>
</article-meta>
</front>
<body>
<sec id="s1">
<title>1 Introduction</title>
<p>Due to the global coal crisis and the rising price of crude oil in the global market, many emerging nations must now lessen their reliance on fossil fuels to meet their energy needs (<xref ref-type="bibr" rid="B6">Burke et al., 2018</xref>). The inception of renewable energy-based electricity generation and the introduction of an electric transportation system can help a country to become energy independent (<xref ref-type="bibr" rid="B9">Gielen et al., 2019</xref>). The introduction of a DC microgrid (DCMG) can also prove to be a crucial breakthrough in the process of electricity generation and utilization. The idea of a DCMG is feasible in the near future due to the significant increase in electronic loads and smart appliances that primarily use DC power (<xref ref-type="bibr" rid="B2">Al-Ismail, 2021</xref>).</p>
<p>DC microgrids have several advantages over AC microgrids like low effective resistance, absence of inductive and capacitive reactance, lesser number of power converting stages as compared to AC microgrids, no frequency related issues in DG integration, and many more (<xref ref-type="bibr" rid="B12">Justo et al., 2013</xref>). However, the AC microgrid persisted in being preferred over the DC microgrid because of lack of a well-defined standards, technological advancement, and trustworthy protective measures (<xref ref-type="bibr" rid="B11">Joos et al., 2017</xref>). The protection of DCMG is one of the challenging issues due to various reasons such as the absence of current-zero crossing points, lack of frequency-dependent parameters, absence of sequence components, quickly rising fault current, etc., (<xref ref-type="bibr" rid="B3">Augustine et al., 2018</xref>). As the DC microgrid possesses less physical inertia as compared to the AC system (<xref ref-type="bibr" rid="B23">Sun et al., 2022</xref>), hence the fault current in these systems rises rapidly to an intolerant level in a very short duration of time (<xref ref-type="bibr" rid="B4">Beheshtaein et al., 2019</xref>). This necessitates the requirement of very fast protection schemes for DC microgrids.</p>
<p>In the past various conventional protection schemes such as over-current protection (<xref ref-type="bibr" rid="B21">Shabani and Mazlumi, 2020</xref>), rate of change of current-based protection (<xref ref-type="bibr" rid="B7">Chauhan et al., 2022</xref>), differential protection (<xref ref-type="bibr" rid="B8">Dhar et al., 2018</xref>), resistance-based protection (<xref ref-type="bibr" rid="B14">Kesava Rao and Jena, 2022</xref>), (<xref ref-type="bibr" rid="B26">Yadav and Tummuru, 2020</xref>), etc., Have been suggested for the relaying of DC microgrid. Some of the merits of conventional relaying schemes are easy implementation and low computational burden. However, the issues associated with these conventional protection schemes are slow response; high sensitivity for temporary faults; unable to protect against high resistance faults (HRF); And poor selectivity towards temporary faults (<xref ref-type="bibr" rid="B13">Kant and Gupta, 2022</xref>). To attain the objective of a faster response, a travelling wave (TW)-based relaying scheme has been proposed in various works of literature. The application of TW-based schemes for the protection of high voltage DC (HVDC) transmission systems has been reported in various kinds of literature. The fact that TW-based schemes do not rely on the magnitude of the fault current is one of their key advantages; as a result, these schemes function satisfactorily against HRFs (<xref ref-type="bibr" rid="B27">Zhang et al., 2012</xref>). Although there are various TW-based relaying schemes available for HVDC systems, the application of TW-based protection in low and medium-voltage DC systems (MVDC) is still an unexplored area. In (<xref ref-type="bibr" rid="B20">Saleh et al., 2019</xref>), a TW-based relaying strategy has been suggested for an MVDC microgrid. The proposed scheme in this literature is independent of the arrival times of the travelling wave and utilizes waveshape properties of the very first TW initiated by the fault. Due to the requirement of single-ended measurement only, no communication link is required to implement such schemes. Nowadays, many advanced techniques such as wavelet transform (WT), fuzzy logic, artificial neural network (ANN), etc. Are also being applied to improve the performance of the conventional DCMG protection schemes. As discussed in (<xref ref-type="bibr" rid="B22">Sharma et al., 2021</xref>), machine learning (ML) techniques are also used in combination with differential protection scheme for quick fault detection. This method uses a ML based support vector machine (SVM) classifier to increase the scheme&#x2019;s resilience to transient or momentary faults. The problem with this scheme is that it can detect faults up to 10&#x2126; resistance only. In (<xref ref-type="bibr" rid="B16">Mohanty et al., 2021</xref>), a cosine similarity-based relaying strategy has been presented for DCMG protection. The operating time of the proposed scheme is 3&#xa0;m. But again, it can detect faults up to 10&#x2126; resistance only. In (<xref ref-type="bibr" rid="B10">Jayamaha et al., 2019</xref>), a WT and ANN-based relaying strategy for a DCMG has been proposed. The proposed scheme can detect the ground fault with a maximum resistance up to 300&#x2126;, but the operating time varies between 3&#x2013;5.5&#xa0;m, depending on the type of fault.</p>
<p>Overall, there are a few things, in the available schemes, that may be improved and therefore, in this paper, an advanced short-circuit protection scheme for a DCMG is proposed. The key matters identified with previously discussed methods are a) the operating time of the relay; b) protection against HRFs; c) robustness during external fault or disturbances; and d) the operation during islanded operation. The proposed scheme is developed keeping all these issues into consideration and therefore, the main contributions of the developed scheme are as follows:<list list-type="simple">
<list-item>
<p>&#x2022; It is an ultra-fast relaying scheme that performs a multi-resolution analysis of TW using the DWT.</p>
</list-item>
<list-item>
<p>&#x2022; It works successfully under the grid-integrated as well as the islanded mode of DCMG.</p>
</list-item>
<list-item>
<p>&#x2022; It can successfully detect and classify faults.</p>
</list-item>
<list-item>
<p>&#x2022; It works effectively for pole-to-pole (PP) and pole-ground (PG) faults for HRFs up to 900&#xa0;&#x2126;.</p>
</list-item>
<list-item>
<p>&#x2022; Even in islanded mode, it can successfully detect HRFs up to 1,300&#xa0;&#x2126;.</p>
</list-item>
<list-item>
<p>&#x2022; It discriminates between faulty and non-fault conditions such as islanding and load switching events.</p>
</list-item>
<list-item>
<p>&#x2022; The results obtained are validated using a lab setup with the real-time simulator, i.e., Opal-RT.</p>
</list-item>
</list>
</p>
<p>The remainder of the paper is structured as follows: <xref ref-type="sec" rid="s2">Section 2</xref> describes the DC microgrid test system in detail; <xref ref-type="sec" rid="s3">Section 3</xref> offers a brief explanation on the TW and DWT; <xref ref-type="sec" rid="s4">Section 4</xref> introduces the suggested algorithm; and <xref ref-type="sec" rid="s5">Section 5</xref> includes the simulation results and analysis. <xref ref-type="sec" rid="s6">Section 6</xref> presents the real-time validation of the results, <xref ref-type="sec" rid="s7">Section 7</xref> presents a comparison of the proposed scheme with the existing schemes, and <xref ref-type="sec" rid="s8">Section 8</xref> presents the conclusion.</p>
</sec>
<sec id="s2">
<title>2 DC microgrid test system description</title>
<p>In this study, a 500V ring-main bipolar DCMG architecture, as shown in <xref ref-type="fig" rid="F1">Figure 1</xref>, has been considered for the implementation of the suggested scheme. This test system is a modification of the system considered in (<xref ref-type="bibr" rid="B7">Chauhan et al., 2022</xref>). The distributed generation (DG) sources, i.e., PV and battery are connected at bus two through appropriate DC-DC converters. The system is integrated to the grid at bus 1 with the help of a bi-directional voltage source converter (VSC). The bi-directional VSC, connected at the grid interface, enables the power transfer from/to DCMG. When connected to grid, the system voltage is maintained by the grid; and in islanded mode, it is maintained by the local sources. The battery is coupled to the bi-directional DC-DC converter, which is controlled to allow the battery to either absorb or supply power from/to the DC system. The PV-side DC-DC converter is managed to provide the DC system with the maximum real power available. To maintain the positive and negative pole voltage, a voltage balancer circuit is used at each bus. The grounding on the DC side is provided at each bus at the mid-point of voltage balancing capacitors (C1 &#x26; C2). A total load of 300&#xa0;kW (200&#xa0;kW on bus 3 &#x26; 100&#xa0;kW on bus 1) is connected to the DC system. A detailed description of the components connected to this test system is given in <xref ref-type="table" rid="T1">Table 1</xref>. The proposed scheme has been implemented for the protection of positive and negative pole lines between bus 1 and bus 2, i.e., lines P12 and N12, respectively. Hence the relays are connected at each terminal of both lines, i.e., R<sub>P1</sub>, R<sub>P2</sub>, R<sub>N1</sub>, and R<sub>N2</sub>, as shown in <xref ref-type="fig" rid="F1">Figure 1</xref>. Any fault outside this protected zone is considered an external fault.</p>
<fig id="F1" position="float">
<label>FIGURE 1</label>
<caption>
<p>Bi-polar DC microgrid test system.</p>
</caption>
<graphic xlink:href="fenrg-11-1100789-g001.tif"/>
</fig>
<table-wrap id="T1" position="float">
<label>TABLE 1</label>
<caption>
<p>Detailed description of the DC test system.</p>
</caption>
<table>
<thead valign="top">
<tr>
<th align="center">Sl.No.</th>
<th align="center">Component name</th>
<th align="center">Parameter name</th>
<th align="center">Rating</th>
</tr>
</thead>
<tbody valign="top">
<tr>
<td align="center">1</td>
<td align="left">DC Grid</td>
<td align="left">DC grid voltage</td>
<td align="left">500&#xa0;V</td>
</tr>
<tr>
<td rowspan="6" align="center">2</td>
<td rowspan="6" align="left">DC Cable</td>
<td rowspan="3" align="left">Length</td>
<td align="left">P12 &#x26; N12&#x2013;4&#xa0;km</td>
</tr>
<tr>
<td align="left">P13 &#x26; N13&#x2013;1&#xa0;km</td>
</tr>
<tr>
<td align="left">P23 &#x26; N23&#x2013;1&#xa0;km</td>
</tr>
<tr>
<td align="left">Resistance</td>
<td align="left">12.7&#xa0;m&#x2126;/km</td>
</tr>
<tr>
<td align="left">Inductance</td>
<td align="left">0.9337&#xa0;mH/km</td>
</tr>
<tr>
<td align="left">Capacitance</td>
<td align="left">12.74&#xa0;nF/km</td>
</tr>
<tr>
<td align="center">3</td>
<td align="left">PV system</td>
<td align="left">Power Rating</td>
<td align="left">200&#xa0;kW @1000&#xa0;W/m2</td>
</tr>
<tr>
<td align="center">4</td>
<td align="left">Battery</td>
<td align="left">Capacity</td>
<td align="left">668 Ah</td>
</tr>
<tr>
<td align="center">5</td>
<td align="left">Grid side VSC</td>
<td align="left">Power rating</td>
<td align="left">0.2&#xa0;MW</td>
</tr>
<tr>
<td align="center">6</td>
<td align="left">PV side DC-DC converter</td>
<td align="left">Power rating</td>
<td align="left">0.2&#xa0;MW</td>
</tr>
<tr>
<td align="center">7</td>
<td align="left">Battery side converter</td>
<td align="left">Power rating</td>
<td align="left">0.2&#xa0;MW</td>
</tr>
<tr>
<td align="center">8</td>
<td align="left">DC load</td>
<td align="left">DC load</td>
<td align="left">300&#xa0;kW</td>
</tr>
<tr>
<td align="center">9</td>
<td align="left">Voltage balancing capacitors</td>
<td align="left">C1 and C2</td>
<td align="left">75&#xa0;mF</td>
</tr>
</tbody>
</table>
</table-wrap>
</sec>
<sec id="s3">
<title>3 Preliminaries of TW and DWT</title>
<sec id="s3-1">
<title>3.1 Travelling wave</title>
<p>Travelling waves (TWs) are electromagnetic transients that are generated at the fault point upon the occurrence of the fault and propagate along the lines at a very high speed, nearly at the speed of light (<xref ref-type="bibr" rid="B1">Aftab et al., 20182020</xref>). These propagating TWs are captured at line terminals to design an ultra-fast relaying scheme. The TW-based relaying schemes are not new and widely employed for the protection of high voltage AC (HVAC) and HVDC transmission lines. But the application of these schemes in active distribution networks such as AC or DC microgrids needs to be investigated. The benefits such as ultra-fast operation and the independence of the fault current make the TW-based schemes very suitable for DC microgrid protection.</p>
</sec>
<sec id="s3-2">
<title>3.2 Discrete wavelet transform (DWT)</title>
<p>A signal can be processed using the sophisticated mathematical tool known as the wavelet transform (WT) (<xref ref-type="bibr" rid="B17">Pukhova et al., 2017</xref>). The WTs can be classified in two categories, viz., continuous wavelet transform (CWT) and discrete wavelet transform (DWT). The scales and locations used by the CWT are unlimited. In contrast, the DWT employs a finite collection of wavelets that have been specified at a specific set of scales and locations. In this study, the DWT has been applied.</p>
<p>Mathematically, the DWT of a signal is given as (<xref ref-type="bibr" rid="B5">Bentley and McDonnell, 1994</xref>).<disp-formula id="e1">
<mml:math id="m1">
<mml:mrow>
<mml:mi>D</mml:mi>
<mml:mi>W</mml:mi>
<mml:mi>T</mml:mi>
<mml:mrow>
<mml:mfenced open="(" close=")" separators="|">
<mml:mrow>
<mml:mi>m</mml:mi>
<mml:mo>,</mml:mo>
<mml:mi>k</mml:mi>
</mml:mrow>
</mml:mfenced>
</mml:mrow>
<mml:mo>&#x3d;</mml:mo>
<mml:mfrac>
<mml:mrow>
<mml:mn>1</mml:mn>
</mml:mrow>
<mml:mrow>
<mml:msqrt>
<mml:msubsup>
<mml:mi>a</mml:mi>
<mml:mn>0</mml:mn>
<mml:mi>m</mml:mi>
</mml:msubsup>
</mml:msqrt>
</mml:mrow>
</mml:mfrac>
<mml:mrow>
<mml:munderover>
<mml:mstyle displaystyle="true">
<mml:mo>&#x2211;</mml:mo>
</mml:mstyle>
<mml:mrow>
<mml:mi>k</mml:mi>
<mml:mo>&#x3d;</mml:mo>
<mml:mn>1</mml:mn>
</mml:mrow>
<mml:mi>N</mml:mi>
</mml:munderover>
<mml:mrow>
<mml:mi>f</mml:mi>
<mml:mrow>
<mml:mfenced open="[" close="]" separators="|">
<mml:mrow>
<mml:mi>n</mml:mi>
</mml:mrow>
</mml:mfenced>
</mml:mrow>
<mml:mo>&#x2a;</mml:mo>
<mml:mi>g</mml:mi>
</mml:mrow>
</mml:mrow>
<mml:mrow>
<mml:mfenced open="[" close="]" separators="|">
<mml:mrow>
<mml:mfrac>
<mml:mrow>
<mml:mi>k</mml:mi>
<mml:mo>&#x2212;</mml:mo>
<mml:mi>n</mml:mi>
<mml:msubsup>
<mml:mi>a</mml:mi>
<mml:mn>0</mml:mn>
<mml:mi>m</mml:mi>
</mml:msubsup>
<mml:msub>
<mml:mi>b</mml:mi>
<mml:mn>0</mml:mn>
</mml:msub>
</mml:mrow>
<mml:msubsup>
<mml:mi>a</mml:mi>
<mml:mn>0</mml:mn>
<mml:mi>m</mml:mi>
</mml:msubsup>
</mml:mfrac>
</mml:mrow>
</mml:mfenced>
</mml:mrow>
</mml:mrow>
</mml:math>
<label>(1)</label>
</disp-formula>Where <italic>f</italic>[n] is the input signal, <italic>g</italic>[n] is the mother wavelet, <italic>k</italic> is the present sample, <inline-formula id="inf1">
<mml:math id="m2">
<mml:mrow>
<mml:msubsup>
<mml:mi>a</mml:mi>
<mml:mn>0</mml:mn>
<mml:mi>m</mml:mi>
</mml:msubsup>
</mml:mrow>
</mml:math>
</inline-formula> is a scale parameter, and <inline-formula id="inf2">
<mml:math id="m3">
<mml:mrow>
<mml:msub>
<mml:mi>b</mml:mi>
<mml:mn>0</mml:mn>
</mml:msub>
</mml:mrow>
</mml:math>
</inline-formula> is the location parameter.</p>
<p>The DWT decomposes the input signal into the detail coefficient (D) and approximation coefficient (A) at each decomposition level. The detail coefficient (D) is the high-frequency component, and the approximation coefficient (A) is the low-frequency component of the input signal (<xref ref-type="bibr" rid="B15">Manohar et al., 2019</xref>).</p>
</sec>
</sec>
<sec id="s4">
<title>4 Proposed algorithm</title>
<p>The proposed algorithm is developed by combining the concept of TW and DWT. This algorithm does not utilize the timing of the incident wave at the line terminals. Instead, this algorithm is based on the waveshape properties of the travelling waves. The travelling waves were calculated by Eqs <xref ref-type="disp-formula" rid="e2">2</xref>, <xref ref-type="disp-formula" rid="e3">3</xref> (<xref ref-type="bibr" rid="B24">Tiwari et al., 2022</xref>).<disp-formula id="e2">
<mml:math id="m4">
<mml:mrow>
<mml:msub>
<mml:mi>V</mml:mi>
<mml:mrow>
<mml:mi>t</mml:mi>
<mml:mi>w</mml:mi>
<mml:mi>f</mml:mi>
</mml:mrow>
</mml:msub>
<mml:mrow>
<mml:mfenced open="(" close=")" separators="|">
<mml:mrow>
<mml:mi>k</mml:mi>
</mml:mrow>
</mml:mfenced>
</mml:mrow>
<mml:mo>&#x3d;</mml:mo>
<mml:mfrac>
<mml:mrow>
<mml:mn>1</mml:mn>
</mml:mrow>
<mml:mrow>
<mml:mn>2</mml:mn>
</mml:mrow>
</mml:mfrac>
<mml:mrow>
<mml:mfenced open="[" close="]" separators="|">
<mml:mrow>
<mml:mo>&#x394;</mml:mo>
<mml:msub>
<mml:mi>V</mml:mi>
<mml:mi>f</mml:mi>
</mml:msub>
<mml:mrow>
<mml:mfenced open="(" close=")" separators="|">
<mml:mrow>
<mml:mi>k</mml:mi>
</mml:mrow>
</mml:mfenced>
</mml:mrow>
<mml:mo>&#x2b;</mml:mo>
<mml:msub>
<mml:mi>Z</mml:mi>
<mml:mi>s</mml:mi>
</mml:msub>
<mml:mo>&#x2a;</mml:mo>
<mml:mo>&#x2206;</mml:mo>
<mml:msub>
<mml:mi>i</mml:mi>
<mml:mi>f</mml:mi>
</mml:msub>
<mml:mrow>
<mml:mfenced open="(" close=")" separators="|">
<mml:mrow>
<mml:mi>k</mml:mi>
</mml:mrow>
</mml:mfenced>
</mml:mrow>
</mml:mrow>
</mml:mfenced>
</mml:mrow>
</mml:mrow>
</mml:math>
<label>(2)</label>
</disp-formula>
<disp-formula id="e3">
<mml:math id="m5">
<mml:mrow>
<mml:msub>
<mml:mi>V</mml:mi>
<mml:mrow>
<mml:mi>t</mml:mi>
<mml:mi>w</mml:mi>
<mml:mi>b</mml:mi>
</mml:mrow>
</mml:msub>
<mml:mrow>
<mml:mfenced open="(" close=")" separators="|">
<mml:mrow>
<mml:mi>k</mml:mi>
</mml:mrow>
</mml:mfenced>
</mml:mrow>
<mml:mo>&#x3d;</mml:mo>
<mml:mfrac>
<mml:mrow>
<mml:mn>1</mml:mn>
</mml:mrow>
<mml:mrow>
<mml:mn>2</mml:mn>
</mml:mrow>
</mml:mfrac>
<mml:mrow>
<mml:mfenced open="[" close="]" separators="|">
<mml:mrow>
<mml:mo>&#x394;</mml:mo>
<mml:msub>
<mml:mi>V</mml:mi>
<mml:mi>b</mml:mi>
</mml:msub>
<mml:mrow>
<mml:mfenced open="(" close=")" separators="|">
<mml:mrow>
<mml:mi>k</mml:mi>
</mml:mrow>
</mml:mfenced>
</mml:mrow>
<mml:mo>&#x2212;</mml:mo>
<mml:msub>
<mml:mi>Z</mml:mi>
<mml:mi>s</mml:mi>
</mml:msub>
<mml:mo>&#x2a;</mml:mo>
<mml:mo>&#x2206;</mml:mo>
<mml:msub>
<mml:mi>i</mml:mi>
<mml:mi>b</mml:mi>
</mml:msub>
<mml:mrow>
<mml:mfenced open="(" close=")" separators="|">
<mml:mrow>
<mml:mi>k</mml:mi>
</mml:mrow>
</mml:mfenced>
</mml:mrow>
</mml:mrow>
</mml:mfenced>
</mml:mrow>
</mml:mrow>
</mml:math>
<label>(3)</label>
</disp-formula>Where subscript <italic>f</italic> and <italic>b</italic> denote the forward and backward wave quantities, respectively. <italic>V</italic>
<sub>
<italic>tw</italic>
</sub>
<italic>(k)</italic> is the voltage travelling wave at sample <italic>k</italic> and <italic>Z</italic>
<sub>
<italic>s</italic>
</sub> is the surge impedance of the dc cable. The change in voltage and current at the <italic>i</italic>
<sup>
<italic>th</italic>
</sup> bus can be calculated as in Eqs <xref ref-type="disp-formula" rid="e4">4</xref>, <xref ref-type="disp-formula" rid="e5">5</xref>.<disp-formula id="e4">
<mml:math id="m6">
<mml:mrow>
<mml:mo>&#x394;</mml:mo>
<mml:msub>
<mml:mi>V</mml:mi>
<mml:mi>i</mml:mi>
</mml:msub>
<mml:mrow>
<mml:mfenced open="(" close=")" separators="|">
<mml:mrow>
<mml:mi>k</mml:mi>
</mml:mrow>
</mml:mfenced>
</mml:mrow>
<mml:mo>&#x3d;</mml:mo>
<mml:msub>
<mml:mi>V</mml:mi>
<mml:mi>i</mml:mi>
</mml:msub>
<mml:mrow>
<mml:mfenced open="(" close=")" separators="|">
<mml:mrow>
<mml:mi>k</mml:mi>
</mml:mrow>
</mml:mfenced>
</mml:mrow>
<mml:mo>&#x2212;</mml:mo>
<mml:msub>
<mml:mi>V</mml:mi>
<mml:mi>i</mml:mi>
</mml:msub>
<mml:mrow>
<mml:mfenced open="(" close=")" separators="|">
<mml:mrow>
<mml:mi>k</mml:mi>
<mml:mo>&#x2212;</mml:mo>
<mml:mn>1</mml:mn>
</mml:mrow>
</mml:mfenced>
</mml:mrow>
</mml:mrow>
</mml:math>
<label>(4)</label>
</disp-formula>
<disp-formula id="e5">
<mml:math id="m7">
<mml:mrow>
<mml:mo>&#x394;</mml:mo>
<mml:msub>
<mml:mi>I</mml:mi>
<mml:mi>i</mml:mi>
</mml:msub>
<mml:mrow>
<mml:mfenced open="(" close=")" separators="|">
<mml:mrow>
<mml:mi>k</mml:mi>
</mml:mrow>
</mml:mfenced>
</mml:mrow>
<mml:mo>&#x3d;</mml:mo>
<mml:msub>
<mml:mi>I</mml:mi>
<mml:mi>i</mml:mi>
</mml:msub>
<mml:mrow>
<mml:mfenced open="(" close=")" separators="|">
<mml:mrow>
<mml:mi>k</mml:mi>
</mml:mrow>
</mml:mfenced>
</mml:mrow>
<mml:mo>&#x2212;</mml:mo>
<mml:msub>
<mml:mi>I</mml:mi>
<mml:mi>i</mml:mi>
</mml:msub>
<mml:mrow>
<mml:mfenced open="(" close=")" separators="|">
<mml:mrow>
<mml:mi>k</mml:mi>
<mml:mo>&#x2212;</mml:mo>
<mml:mn>1</mml:mn>
</mml:mrow>
</mml:mfenced>
</mml:mrow>
</mml:mrow>
</mml:math>
<label>(5)</label>
</disp-formula>
</p>
<p>The schemes based on the incident time of travelling waves require high frequency transient recorders to capture the travelling waves at the line terminals, and use of such costly equipment is not very economical for distribution lines. Hence in this study, the properties of the travelling are extracted by employing the signal processing tools, i.e., wavelet transform. The first incident forward voltage travelling wave is decomposed into the various high-frequency and low-frequency components by using the DWT&#x2019;s dyadic filter bank theory, as shown in <xref ref-type="fig" rid="F2">Figure 2</xref>. The selection of the mother wavelet is also an important criterion for the implementation of WT. Some of the literature available (<xref ref-type="bibr" rid="B18">Sabug et al., 20192020</xref>) suggest that Daubechies as mother wavelet gives better result in the case of power system studies. The details of the DWT used in this algorithm have been provided in <xref ref-type="table" rid="T2">Table 2</xref>.</p>
<fig id="F2" position="float">
<label>FIGURE 2</label>
<caption>
<p>Decomposition tree of DWT using dyadic filter bank theory.</p>
</caption>
<graphic xlink:href="fenrg-11-1100789-g002.tif"/>
</fig>
<table-wrap id="T2" position="float">
<label>TABLE 2</label>
<caption>
<p>Details of the DWT used in this algorithm.</p>
</caption>
<table>
<thead valign="top">
<tr>
<th align="left">Sl. No.</th>
<th align="left">DWT components</th>
<th align="left">Remarks</th>
</tr>
</thead>
<tbody valign="top">
<tr>
<td align="left">1</td>
<td align="left">Mother wavelet</td>
<td align="left">Daubechies</td>
</tr>
<tr>
<td align="left">2</td>
<td align="left">Wavelet order</td>
<td align="left">2</td>
</tr>
<tr>
<td align="left">3</td>
<td align="left">No. of levels</td>
<td align="left">2</td>
</tr>
<tr>
<td align="left">4</td>
<td align="left">Decomposition tree structure</td>
<td align="left">Symmetric</td>
</tr>
<tr>
<td align="left">5</td>
<td align="left">Sampling frequency</td>
<td align="left">200&#xa0;kHz</td>
</tr>
</tbody>
</table>
</table-wrap>
<p>The energy content of the extracted DWT coefficients of the voltage travelling wave is calculated by Eq <xref ref-type="disp-formula" rid="e6">6</xref>.<disp-formula id="e6">
<mml:math id="m8">
<mml:mrow>
<mml:msub>
<mml:mi>E</mml:mi>
<mml:mrow>
<mml:mi>t</mml:mi>
<mml:mi>w</mml:mi>
<mml:mi>f</mml:mi>
</mml:mrow>
</mml:msub>
<mml:mo>&#x3d;</mml:mo>
<mml:mrow>
<mml:munderover>
<mml:mstyle displaystyle="true">
<mml:mo>&#x2211;</mml:mo>
</mml:mstyle>
<mml:mrow>
<mml:mi>i</mml:mi>
<mml:mo>&#x3d;</mml:mo>
<mml:mn>1</mml:mn>
</mml:mrow>
<mml:mi>N</mml:mi>
</mml:munderover>
<mml:msup>
<mml:mrow>
<mml:mfenced open="|" close="|" separators="|">
<mml:mrow>
<mml:msub>
<mml:mi>d</mml:mi>
<mml:mrow>
<mml:mi>t</mml:mi>
<mml:mi>w</mml:mi>
<mml:mi>i</mml:mi>
</mml:mrow>
</mml:msub>
</mml:mrow>
</mml:mfenced>
</mml:mrow>
<mml:mn>2</mml:mn>
</mml:msup>
</mml:mrow>
</mml:mrow>
</mml:math>
<label>(6)</label>
</disp-formula>Where <italic>d</italic>
<sub>
<italic>tw</italic>
</sub> is the high-frequency detail coefficient of the voltage travelling wave (<italic>V</italic>
<sub>
<italic>tw</italic>
</sub>), and N is the number of samples. In this case, N is taken as 16 samples. The number of samples (N) were decided based on the rigorous simulation studies. The energy content of the DWT coefficient (<italic>d</italic>
<sub>
<italic>3</italic>
</sub>) following a PG fault and PP fault is presented in <xref ref-type="table" rid="T3">Table 3</xref>.</p>
<table-wrap id="T3" position="float">
<label>TABLE 3</label>
<caption>
<p>Energy of travelling wave at positive and negative poles during different types of faults.</p>
</caption>
<table>
<thead valign="top">
<tr>
<th align="left">Fault type</th>
<th align="left">Energy of positive pole voltage (EtwP)</th>
<th align="left">Energy of negative pole voltage (EtwN)</th>
<th align="center">&#x7c; EtwP&#x2013;EtwN&#x7c;</th>
</tr>
</thead>
<tbody valign="top">
<tr>
<td align="left">PPG</td>
<td align="left">2793.6</td>
<td align="left">1.0008</td>
<td align="left">2792.6</td>
</tr>
<tr>
<td align="left">NPG</td>
<td align="left">1.1726</td>
<td align="left">2777.1</td>
<td align="left">2775.93</td>
</tr>
<tr>
<td align="left">PP</td>
<td align="left">2765.3</td>
<td align="left">2763.6</td>
<td align="left">1.7</td>
</tr>
</tbody>
</table>
</table-wrap>
<p>If this energy content is more than the pre-set value, then the fault will be detected. The proposed algorithm is also able to classify the faults. With PP fault, the energy content of the DWT coefficient at both positive and negative poles (i.e., <italic>E</italic>
<sub>
<italic>twP</italic>
</sub> and <italic>E</italic>
<sub>
<italic>twN</italic>
</sub>) will almost be the same. Hence, the difference between both energies will be very small. If this difference energy is less than the pre-specified value, the fault will be a PP fault. While in the case of PG-fault, this energy difference will be more than the pre-set value. The pre-specified threshold value has been determined by simulating the test model for different fault and non-fault conditions and then observing the energy content of the DWT coefficients in each case. The flow chart of the proposed algorithm is shown in <xref ref-type="fig" rid="F3">Figure 3</xref>.</p>
<fig id="F3" position="float">
<label>FIGURE 3</label>
<caption>
<p>Flow chart of the proposed algorithm.</p>
</caption>
<graphic xlink:href="fenrg-11-1100789-g003.tif"/>
</fig>
</sec>
<sec sec-type="results|discussion" id="s5">
<title>5 Simulation results and discussion</title>
<p>The DCMG test system, as illustrated in <xref ref-type="fig" rid="F1">Figure 1</xref>, is simulated in the MATLAB/SIMULINK environment for the validation of the proposed algorithm. The performance of the suggested algorithm is evaluated in both fault- and non-fault-related scenarios.</p>
<sec id="s5-1">
<title>5.1 Fault conditions</title>
<p>The performance of the proposed scheme for various fault conditions has been presented in this section.</p>
<sec id="s5-1-1">
<title>5.1.1 Pole-to-ground (PG) fault simulation</title>
<p>To investigate the performance of the suggested algorithm for PG-fault, a positive pole-to-ground (PPG) fault with a fault resistance (<italic>R</italic>
<sub>
<italic>f</italic>
</sub>) of 0.1&#x2126; were simulated on the line P12, and the results have been discussed here. The fault current contribution from the grid (<italic>I</italic>
<sub>
<italic>fgrid</italic>
</sub>) and DG (<italic>I</italic>
<sub>
<italic>fdg</italic>
</sub>), and the total fault current (<italic>I</italic>
<sub>
<italic>f</italic>
</sub>) following the PPG fault at the mid-point of line P12 are shown in <xref ref-type="fig" rid="F4">Figure 4</xref>. The total fault is equal to the sum of the fault currents supplied from the grid and the DG. As shown in <xref ref-type="fig" rid="F4">Figure 4</xref>, the fault current initially rises to a value greater than 1200 A in very short time duration, i.e., within 15&#xa0;m, and then quickly settles down to a value around 600 A. For, this test system, normal current in the line P12 is around 55 A. So, the peak fault current is about 22 times the normal line current. That means if the fault current is allowed to reach the peak value, then it can pose some serious damage to the instruments present in the system. Hence, the relaying scheme must clear the fault well before the current reaches its peak value.</p>
<fig id="F4" position="float">
<label>FIGURE 4</label>
<caption>
<p>Fault current following a PPG fault at <italic>t</italic> &#x3d; 2&#xa0;s.</p>
</caption>
<graphic xlink:href="fenrg-11-1100789-g004.tif"/>
</fig>
<p>The energy content of the DWT coefficient of forward voltage travelling wave (<italic>E</italic>
<sub>
<italic>twfP</italic>
</sub>) is shown in <xref ref-type="fig" rid="F5">Figure 5A</xref>. As soon as this energy content crosses the pre-set value (<italic>E</italic>
<sub>
<italic>th</italic>
</sub>), the fault is detected, and a trip signal is generated by relays R<sub>P1</sub> and R<sub>P2</sub> to isolate the faulty line P12. The status of the trip signal from relays R<sub>P1</sub> and R<sub>P2</sub> is shown in <xref ref-type="fig" rid="F5">Figure 5B</xref>. As shown in <xref ref-type="fig" rid="F5">Figure 5B</xref>, the trip signal becomes high at t &#x3d; 2.00064&#xa0;s which means the proposed scheme can detect the PPG fault within 0.64&#xa0;m, which is quite fast.</p>
<fig id="F5" position="float">
<label>FIGURE 5</label>
<caption>
<p>
<bold>(A)</bold> Energy of forward voltage travelling wave, <bold>(B)</bold> Status of trip signal for relays R<sub>P1</sub> and R<sub>P2</sub> following a PPG fault on line P12 at <italic>t</italic> &#x3d; 2&#xa0;s.</p>
</caption>
<graphic xlink:href="fenrg-11-1100789-g005.tif"/>
</fig>
</sec>
<sec id="s5-1-2">
<title>5.1.2 Pole-to-pole (PP) fault simulation</title>
<p>The performance of the proposed algorithm has been evaluated by simulating a pole-to-pole (PP) fault with <italic>R</italic>
<sub>
<italic>f</italic>
</sub> &#x3d; 0.1&#xa0;&#x2126; on the mid-point of the lines P12 and N12. In this case, the forward voltage travelling wave (<italic>V</italic>
<sub>
<italic>twf</italic>
</sub>) is calculated at both positive and negative poles. The energy content of the DWT coefficient of the <italic>V</italic>
<sub>
<italic>twf</italic>
</sub> is shown in <xref ref-type="fig" rid="F6">Figure 6</xref>. As shown in <xref ref-type="fig" rid="F6">Figure 6</xref>, in the case of a PP fault, the energy of the DWT coefficient at both positive and negative poles is greater than the pre-set value. Hence, in this case, the trip signal will be generated by all four relays (i.e., two positive pole relays <italic>R</italic>
<sub>
<italic>P1</italic>
</sub> &#x26; <italic>R</italic>
<sub>
<italic>P2</italic>
</sub>, and two negative pole relays <italic>R</italic>
<sub>
<italic>N1</italic>
</sub> &#x26; <italic>R</italic>
<sub>
<italic>N2</italic>
</sub>).</p>
<fig id="F6" position="float">
<label>FIGURE 6</label>
<caption>
<p>Energy content of DWT coefficient <italic>V</italic>
<sub>
<italic>twf</italic>
</sub> following a PP-fault at <italic>t</italic> &#x3d; 2&#xa0;s, <bold>(A)</bold> Energy at the positive pole (<italic>E</italic>
<sub>
<italic>twfP</italic>
</sub>), <bold>(B)</bold> Energy at the negative pole (<italic>E</italic>
<sub>
<italic>twfN</italic>
</sub>).</p>
</caption>
<graphic xlink:href="fenrg-11-1100789-g006.tif"/>
</fig>
</sec>
<sec id="s5-1-3">
<title>5.1.3 Protection against HRF fault</title>
<p>In case of an HRF, the post-fault current in the affected line is very close to the pre-fault current in the line. Hence, it is very difficult to detect these types of faults using conventional overcurrent relays. A conventional protection scheme may treat HRF as an overload condition. Hence, an effective protection scheme must be able to distinguish between the fault and the overload case. To examine the operation of the suggested scheme under HRF, a PPG fault with different fault resistance is simulated on the mid-point of line P12. The current in line P12 (<italic>I</italic>
<sub>
<italic>p12</italic>
</sub>) following a PPG fault with <italic>R</italic>
<sub>
<italic>f</italic>
</sub> equal to 50&#xa0;&#x2126; is shown in <xref ref-type="fig" rid="F7">Figure 7</xref>. As the post-fault current in line P12 is very close to the pre-fault current, the current-based protection scheme may not be able to detect this fault. The energy content of the DWT coefficient of the forward voltage travelling wave at the positive pole (<italic>E</italic>
<sub>
<italic>twfP</italic>
</sub>) following a PPG fault with different fault resistances has been presented in <xref ref-type="fig" rid="F8">Figure 8</xref>. As presented in <xref ref-type="fig" rid="F8">Figure 8</xref>, the proposed algorithm can successfully detect a PG fault of fault resistance up to 900&#x2126;. From <xref ref-type="fig" rid="F8">Figure 8</xref>, it can also be interpreted that the operating time of the proposed algorithm is independent of the fault resistance. The operating time of this algorithm for each fault resistance is 0.64&#xa0;m.</p>
<fig id="F7" position="float">
<label>FIGURE 7</label>
<caption>
<p>Current in line P12 following a PPG fault with <italic>R</italic>
<sub>
<italic>f</italic>
</sub> &#x3d; 50&#xa0;&#x2126; at <italic>t</italic> &#x3d; 2&#xa0;s.</p>
</caption>
<graphic xlink:href="fenrg-11-1100789-g007.tif"/>
</fig>
<fig id="F8" position="float">
<label>FIGURE 8</label>
<caption>
<p>Energy content of DWT coefficient following a PPG fault with different fault resistances.</p>
</caption>
<graphic xlink:href="fenrg-11-1100789-g008.tif"/>
</fig>
</sec>
<sec id="s5-1-4">
<title>5.1.4 Protection in Islanded mode operation</title>
<p>During islanded mode operation, the power from the grid is not available and the total load connected to the system must be supplied by the DG only. The variation in fault current during islanded and grid-integrated operations can be observed in <xref ref-type="fig" rid="F9">Figure 9</xref>. In islanded operation, the fault current rises rapidly, reaches up to the peak value, and then quickly settles down to an extremely low value as compared to the grid-integrated mode. Hence, a fault in islanded mode must be detected before it settles down to a low value. The performance of the suggested algorithm has been examined by simulating a PPG and PP fault during islanded operation of the DCMG. The fault current following a PPG fault with <italic>R</italic>
<sub>
<italic>f</italic>
</sub> &#x3d; 1&#xa0;&#x2126; during islanded operation is shown in <xref ref-type="fig" rid="F9">Figure 9</xref>. The energy content of the DWT coefficient of <italic>V</italic>
<sub>
<italic>twf</italic>
</sub> at the positive pole is shown in <xref ref-type="fig" rid="F10">Figure 10</xref>. As soon as this energy content becomes higher than the threshold energy the trip signal is generated by relay <italic>R</italic>
<sub>
<italic>P1</italic>
</sub> and <italic>R</italic>
<sub>
<italic>P2</italic>
</sub>.</p>
<fig id="F9" position="float">
<label>FIGURE 9</label>
<caption>
<p>Fault current following a PPG fault at <italic>t</italic> &#x3d; 2&#xa0;s in grid-integrated and islanded operation.</p>
</caption>
<graphic xlink:href="fenrg-11-1100789-g009.tif"/>
</fig>
<fig id="F10" position="float">
<label>FIGURE 10</label>
<caption>
<p>Energy of DWT coefficient of <italic>V</italic>
<sub>
<italic>twf</italic>
</sub> following a PPG fault with <italic>R</italic>
<sub>
<italic>f</italic>
</sub> &#x3d; 1&#xa0;&#x2126; at <italic>t &#x3d;</italic> 2&#xa0;s during islanded operation of DCMG.</p>
</caption>
<graphic xlink:href="fenrg-11-1100789-g010.tif"/>
</fig>
<p>To evaluate the performance against a PP fault, a PP fault with <italic>R</italic>
<sub>
<italic>f</italic>
</sub> equal to 0.1&#xa0;&#x2126; is simulated between lines P12 and N12. To generate the trip signal for both positive and negative pole relays, the energy of the DWT coefficient of the <italic>V</italic>
<sub>
<italic>twf</italic>
</sub> at both positive and negative poles (i.e., <italic>E</italic>
<sub>
<italic>twfP</italic>
</sub> and <italic>E</italic>
<sub>
<italic>twfN</italic>
</sub>) is calculated using Eq <xref ref-type="disp-formula" rid="e6">6</xref>. In the case of a PP fault, both <italic>E</italic>
<sub>
<italic>twfP</italic>
</sub> and <italic>E</italic>
<sub>
<italic>twfN</italic>
</sub> will almost be the same, and in this case, as these values are greater than the pre-set value, as shown in <xref ref-type="fig" rid="F11">Figure 11</xref>, the trip signal will be generated by relays R<sub>P1</sub>, R<sub>P2</sub>, R<sub>N1</sub>, and R<sub>N2</sub>. To examine the performance of the proposed algorithm against HRF, a PPG fault at line P12 with different fault resistance has been simulated, and the energy of the DWT coefficient of <italic>V</italic>
<sub>
<italic>twf</italic>
</sub> is calculated for each case. The simulation results for these cases are presented in <xref ref-type="table" rid="T4">Table 4</xref>. The data obtained from <xref ref-type="table" rid="T4">Table 4</xref> shows that in the islanded mode, the proposed algorithm can protect HRF up to 1,300&#xa0;&#x2126;.</p>
<fig id="F11" position="float">
<label>FIGURE 11</label>
<caption>
<p>Energy of DWT coefficient of <italic>V</italic>
<sub>
<italic>twf</italic>
</sub> at both positive and negative pole following a PP fault with <italic>R</italic>
<sub>
<italic>f</italic>
</sub> &#x3d; 0.1&#xa0;&#x2126; at <italic>t</italic> &#x3d; 2&#xa0;s during islanded operation of DCMG.</p>
</caption>
<graphic xlink:href="fenrg-11-1100789-g011.tif"/>
</fig>
<table-wrap id="T4" position="float">
<label>TABLE 4</label>
<caption>
<p>Summary of the different cases considered in this study for the verification of the proposed algorithm.</p>
</caption>
<table>
<thead valign="top">
<tr>
<th rowspan="2" align="center">Sl. No.</th>
<th rowspan="2" align="center">Operating events</th>
<th colspan="2" align="center">Energy of DWT coefficient (joule)</th>
<th colspan="4" align="center">Relay tripping status (1-high, 0-low)</th>
<th rowspan="2" align="center">Operating time (milli-seconds)</th>
</tr>
<tr>
<th align="center">EtwfP</th>
<th align="center">EtwfN</th>
<th align="center">RP1</th>
<th align="center">RP2</th>
<th align="center">RN1</th>
<th align="center">RN2</th>
</tr>
</thead>
<tbody valign="top">
<tr>
<td align="left" style="background-color:#BFBFBF">1</td>
<td colspan="8" align="left" style="background-color:#BFBFBF">Fault in grid-integrated mode</td>
</tr>
<tr>
<td align="left">1A</td>
<td align="left">PPG fault with Rf &#x3d; 0.1&#xa0;&#x2126;</td>
<td align="left">2793.6</td>
<td align="left">1.0008</td>
<td align="left">1</td>
<td align="left">1</td>
<td align="left">0</td>
<td align="left">0</td>
<td align="left">0.64</td>
</tr>
<tr>
<td align="left">1B</td>
<td align="left">NPG fault with Rf &#x3d; 0.1&#xa0;&#x2126;</td>
<td align="left">1.1726</td>
<td align="left">2777.1</td>
<td align="left">0</td>
<td align="left">0</td>
<td align="left">1</td>
<td align="left">1</td>
<td align="left">0.64</td>
</tr>
<tr>
<td align="left">1C</td>
<td align="left">PP fault with Rf &#x3d; 0.1&#xa0;&#x2126;</td>
<td align="left">2765.3</td>
<td align="left">2763.6</td>
<td align="left">1</td>
<td align="left">1</td>
<td align="left">1</td>
<td align="left">1</td>
<td align="left">0.64</td>
</tr>
<tr>
<td align="left">1D</td>
<td align="left">PPG fault with Rf &#x3d; 50&#xa0;&#x2126;</td>
<td align="left">1103.3</td>
<td align="left">1.0008</td>
<td align="left">1</td>
<td align="left">1</td>
<td align="left">0</td>
<td align="left">0</td>
<td align="left">0.64</td>
</tr>
<tr>
<td align="left">1E</td>
<td align="left">PPG fault with Rf &#x3d; 100&#xa0;&#x2126;</td>
<td align="left">613.713</td>
<td align="left">1.0008</td>
<td align="left">1</td>
<td align="left">1</td>
<td align="left">0</td>
<td align="left">0</td>
<td align="left">0.64</td>
</tr>
<tr>
<td align="left">1F</td>
<td align="left">PPG fault with Rf &#x3d; 200&#xa0;&#x2126;</td>
<td align="left">316.035</td>
<td align="left">1.0008</td>
<td align="left">1</td>
<td align="left">1</td>
<td align="left">0</td>
<td align="left">0</td>
<td align="left">0.64</td>
</tr>
<tr>
<td align="left">1G</td>
<td align="left">PPG fault with Rf &#x3d; 500&#xa0;&#x2126;</td>
<td align="left">186.062</td>
<td align="left">1.0008</td>
<td align="left">1</td>
<td align="left">1</td>
<td align="left">0</td>
<td align="left">0</td>
<td align="left">0.64</td>
</tr>
<tr>
<td align="left">1H</td>
<td align="left">PPG fault with Rf &#x3d; 600&#xa0;&#x2126;</td>
<td align="left">168.01</td>
<td align="left">1.0008</td>
<td align="left">1</td>
<td align="left">1</td>
<td align="left">0</td>
<td align="left">0</td>
<td align="left">0.64</td>
</tr>
<tr>
<td align="left">1I</td>
<td align="left">PPG fault with Rf &#x3d; 700&#xa0;&#x2126;</td>
<td align="left">151.97</td>
<td align="left">1.0008</td>
<td align="left">1</td>
<td align="left">1</td>
<td align="left">0</td>
<td align="left">0</td>
<td align="left">0.64</td>
</tr>
<tr>
<td align="left">1J</td>
<td align="left">PPG fault with Rf &#x3d; 800&#xa0;&#x2126;</td>
<td align="left">137.37</td>
<td align="left">1.0008</td>
<td align="left">1</td>
<td align="left">1</td>
<td align="left">0</td>
<td align="left">0</td>
<td align="left">0.64</td>
</tr>
<tr>
<td align="left">1K</td>
<td align="left">PPG fault with Rf &#x3d; 900&#xa0;&#x2126;</td>
<td align="left">124.50</td>
<td align="left">1.0008</td>
<td align="left">1</td>
<td align="left">1</td>
<td align="left">0</td>
<td align="left">0</td>
<td align="left">0.64</td>
</tr>
<tr>
<td align="left">1L</td>
<td align="left">PPG fault with Rf &#x3d; 950&#xa0;&#x2126;</td>
<td align="left">118.622</td>
<td align="left">1.0008</td>
<td align="left">0</td>
<td align="left">0</td>
<td align="left">0</td>
<td align="left">0</td>
<td align="left">&#x2014;</td>
</tr>
<tr>
<td align="left" style="background-color:#BFBFBF">2</td>
<td colspan="8" align="left" style="background-color:#BFBFBF">Fault in islanded operation</td>
</tr>
<tr>
<td align="left">2A</td>
<td align="left">PPG fault with Rf &#x3d; 1&#xa0;&#x2126;</td>
<td align="left">2654.7</td>
<td align="left">0.3161</td>
<td align="left">1</td>
<td align="left">1</td>
<td align="left">0</td>
<td align="left">0</td>
<td align="left">0.64</td>
</tr>
<tr>
<td align="left">2B</td>
<td align="left">NPG fault with Rf &#x3d; 1&#xa0;&#x2126;</td>
<td align="left">0.3092</td>
<td align="left">2652.0</td>
<td align="left">0</td>
<td align="left">0</td>
<td align="left">1</td>
<td align="left">1</td>
<td align="left">0.64</td>
</tr>
<tr>
<td align="left">2C</td>
<td align="left">PPG fault with Rf &#x3d; 100&#xa0;&#x2126;</td>
<td align="left">559.807</td>
<td align="left">0.3161</td>
<td align="left">1</td>
<td align="left">1</td>
<td align="left">0</td>
<td align="left">0</td>
<td align="left">0.64</td>
</tr>
<tr>
<td align="left">2D</td>
<td align="left">PPG fault with Rf &#x3d; 200&#xa0;&#x2126;</td>
<td align="left">267.68</td>
<td align="left">0.3161</td>
<td align="left">1</td>
<td align="left">1</td>
<td align="left">0</td>
<td align="left">0</td>
<td align="left">0.64</td>
</tr>
<tr>
<td align="left">2E</td>
<td align="left">PPG fault with Rf &#x3d; 500&#xa0;&#x2126;</td>
<td align="left">207.15</td>
<td align="left">0.3161</td>
<td align="left">1</td>
<td align="left">1</td>
<td align="left">0</td>
<td align="left">0</td>
<td align="left">0.64</td>
</tr>
<tr>
<td align="left">2F</td>
<td align="left">PPG fault with Rf &#x3d; 600&#xa0;&#x2126;</td>
<td align="left">198.56</td>
<td align="left">0.3161</td>
<td align="left">1</td>
<td align="left">1</td>
<td align="left">0</td>
<td align="left">0</td>
<td align="left">0.64</td>
</tr>
<tr>
<td align="left">2G</td>
<td align="left">PPG fault with Rf &#x3d; 700&#xa0;&#x2126;</td>
<td align="left">187.39</td>
<td align="left">0.3161</td>
<td align="left">1</td>
<td align="left">1</td>
<td align="left">0</td>
<td align="left">0</td>
<td align="left">0.64</td>
</tr>
<tr>
<td align="left">2H</td>
<td align="left">PPG fault with Rf &#x3d; 800&#xa0;&#x2126;</td>
<td align="left">175.17</td>
<td align="left">0.3161</td>
<td align="left">1</td>
<td align="left">1</td>
<td align="left">0</td>
<td align="left">0</td>
<td align="left">0.64</td>
</tr>
<tr>
<td align="left">2I</td>
<td align="left">PPG fault with Rf &#x3d; 900&#xa0;&#x2126;</td>
<td align="left">162.89</td>
<td align="left">0.3161</td>
<td align="left">1</td>
<td align="left">1</td>
<td align="left">0</td>
<td align="left">0</td>
<td align="left">0.64</td>
</tr>
<tr>
<td align="left">2J</td>
<td align="left">PPG fault with Rf &#x3d; 1,000&#xa0;&#x2126;</td>
<td align="left">151.15</td>
<td align="left">0.3161</td>
<td align="left">1</td>
<td align="left">1</td>
<td align="left">0</td>
<td align="left">0</td>
<td align="left">0.64</td>
</tr>
<tr>
<td align="left">2K</td>
<td align="left">PPG fault with Rf &#x3d; 1.2k&#x2126;</td>
<td align="left">130.14</td>
<td align="left">0.3161</td>
<td align="left">1</td>
<td align="left">1</td>
<td align="left">0</td>
<td align="left">0</td>
<td align="left">0.64</td>
</tr>
<tr>
<td align="left">2L</td>
<td align="left">PPG fault with Rf &#x3d; 1.3&#xa0;k&#xa0;&#x2126;</td>
<td align="left">120.999</td>
<td align="left">0.3161</td>
<td align="left">1</td>
<td align="left">1</td>
<td align="left">0</td>
<td align="left">0</td>
<td align="left">0.64</td>
</tr>
<tr>
<td align="left">2M</td>
<td align="left">PPG fault with Rf &#x3d; 1.35k&#x2126;</td>
<td align="left">116.74</td>
<td align="left">0.3161</td>
<td align="left">0</td>
<td align="left">0</td>
<td align="left">0</td>
<td align="left">0</td>
<td align="left">&#x2014;</td>
</tr>
<tr>
<td align="left">2N</td>
<td align="left">PP fault with Rf &#x3d; 0.1&#xa0;&#x2126;</td>
<td align="left">2648.5</td>
<td align="left">2648.5</td>
<td align="left">1</td>
<td align="left">1</td>
<td align="left">1</td>
<td align="left">1</td>
<td align="left">0.64</td>
</tr>
<tr>
<td align="left" style="background-color:#BFBFBF">3</td>
<td colspan="8" align="left" style="background-color:#BFBFBF">External faults</td>
</tr>
<tr>
<td align="left">3A</td>
<td align="left">LLL-fault on AC side</td>
<td align="left">13.74</td>
<td align="left">11.34</td>
<td align="left">0</td>
<td align="left">0</td>
<td align="left">0</td>
<td align="left">0</td>
<td align="left">&#x2014;</td>
</tr>
<tr>
<td align="left">3B</td>
<td align="left">LL-fault on AC side</td>
<td align="left">5.154</td>
<td align="left">6.119</td>
<td align="left">0</td>
<td align="left">0</td>
<td align="left">0</td>
<td align="left">0</td>
<td align="left">&#x2014;</td>
</tr>
<tr>
<td align="left">3C</td>
<td align="left">LLG-fault on AC side</td>
<td align="left">5.415</td>
<td align="left">7.973</td>
<td align="left">0</td>
<td align="left">0</td>
<td align="left">0</td>
<td align="left">0</td>
<td align="left">&#x2014;</td>
</tr>
<tr>
<td align="left">3D</td>
<td align="left">LG-fault on AC side</td>
<td align="left">6.034</td>
<td align="left">0.089</td>
<td align="left">0</td>
<td align="left">0</td>
<td align="left">0</td>
<td align="left">0</td>
<td align="left">&#x2014;</td>
</tr>
<tr>
<td align="left">3E</td>
<td align="left">Close-in external PPG fault</td>
<td align="left">38.96</td>
<td align="left">18.544</td>
<td align="left">0</td>
<td align="left">0</td>
<td align="left">0</td>
<td align="left">0</td>
<td align="left">&#x2014;</td>
</tr>
<tr>
<td align="left" style="background-color:#BFBFBF">4</td>
<td colspan="8" align="left" style="background-color:#BFBFBF">Non-fault operation</td>
</tr>
<tr>
<td align="left">4A</td>
<td align="left">Grid outage</td>
<td align="left">0.0181</td>
<td align="left">0.0168</td>
<td align="left">0</td>
<td align="left">0</td>
<td align="left">0</td>
<td align="left">0</td>
<td align="left">&#x2014;</td>
</tr>
<tr>
<td align="left">4B</td>
<td align="left">Load switching-Scenario-I</td>
<td align="left">0.04579</td>
<td align="left">0.01993</td>
<td align="left">0</td>
<td align="left">0</td>
<td align="left">0</td>
<td align="left">0</td>
<td align="left">&#x2014;</td>
</tr>
<tr>
<td align="left">4C</td>
<td align="left">Load switching-Scenario-II</td>
<td align="left">0.1202</td>
<td align="left">0.07788</td>
<td align="left">0</td>
<td align="left">0</td>
<td align="left">0</td>
<td align="left">0</td>
<td align="left">&#x2014;</td>
</tr>
<tr>
<td align="left">4D</td>
<td align="left">DG uncertainty</td>
<td align="left">0.077</td>
<td align="left">0.075</td>
<td align="left">0</td>
<td align="left">0</td>
<td align="left">0</td>
<td align="left">0</td>
<td align="left">&#x2014;</td>
</tr>
<tr>
<td align="left">4E</td>
<td align="left">Tripping of other distribution lines</td>
<td align="left">0.7089</td>
<td align="left">0.3394</td>
<td align="left">0</td>
<td align="left">0</td>
<td align="left">0</td>
<td align="left">0</td>
<td align="left">&#x2014;</td>
</tr>
<tr>
<td align="left">4F</td>
<td align="left">DG outage</td>
<td align="left">10.45</td>
<td align="left">10.29</td>
<td align="left">0</td>
<td align="left">0</td>
<td align="left">0</td>
<td align="left">0</td>
<td align="left">&#x2014;</td>
</tr>
</tbody>
</table>
</table-wrap>
</sec>
<sec id="s5-1-5">
<title>5.1.5 Protection during unbalanced loading condition</title>
<p>Till now the utility of the proposed scheme for the balanced network conditions have been presented. In this section, the effectiveness of this scheme during the unbalanced network condition have been presented. To create a unbalance in the system a load of 100&#xa0;kW is connected at bus-2 between the positive pole and neutral. This load is connected at voltage level of 250&#xa0;V. The simulation result associated with a PPG fault with <italic>R</italic>
<sub>
<italic>f</italic>
</sub> &#x3d; 10&#xa0;&#x2126; is presented in <xref ref-type="fig" rid="F12">Figures 12</xref>, <xref ref-type="fig" rid="F13">13</xref>. In balanced condition there will be no current through the neutral during the normal operation. The current in neutral will only if the network is unbalanced, as shown in <xref ref-type="fig" rid="F12">Figure 12B</xref>. The energy of the DWT coefficients presented in <xref ref-type="fig" rid="F13">Figure 13</xref> confirms the operation of the proposed scheme during the unbalanced loading conditions.</p>
<fig id="F12" position="float">
<label>FIGURE 12</label>
<caption>
<p>Current following a PPG fault with <italic>R</italic>
<sub>
<italic>f</italic>
</sub> <italic>&#x3d;</italic> 10&#xa0;&#x2126; <bold>(A)</bold> Fault current <bold>(B)</bold> Neutral current.</p>
</caption>
<graphic xlink:href="fenrg-11-1100789-g012.tif"/>
</fig>
<fig id="F13" position="float">
<label>FIGURE 13</label>
<caption>
<p>Energy of DWT coefficient of <italic>V</italic>
<sub>
<italic>twf</italic>
</sub> following a PPG fault with <italic>R</italic>
<sub>
<italic>f</italic>
</sub> &#x3d; 10&#x2126; at <italic>t &#x3d;</italic> 2 s with unbalanced loading condition.</p>
</caption>
<graphic xlink:href="fenrg-11-1100789-g013.tif"/>
</fig>
</sec>
<sec id="s5-1-6">
<title>5.1.6 Impact of noise (SNR 40&#xa0;dB)</title>
<p>To verify the impact of noise, a noise of SNR 40&#xa0;dB is added to the current signal measured at relay point R<sub>P2</sub>. A PPG fault with R<sub>f</sub> &#x3d; 1&#xa0;&#x2126; is create on the cable P21. The simulation result presented in <xref ref-type="fig" rid="F14">Figure 14</xref> following this fault confirms that the proposed scheme works successfully under the noisy environment also.</p>
<fig id="F14" position="float">
<label>FIGURE 14</label>
<caption>
<p>
<bold>(A)</bold> Current in cable P21 with SNR 40&#xa0;dB <bold>(B)</bold> Energy of <italic>V</italic>
<sub>
<italic>twf</italic>
</sub> following the PPG fault.</p>
</caption>
<graphic xlink:href="fenrg-11-1100789-g014.tif"/>
</fig>
</sec>
</sec>
<sec id="s5-2">
<title>5.2 External fault condition</title>
<sec id="s5-2-1">
<title>5.2.1 AC side fault</title>
<p>A fault on the AC side of the DCMG may also affect the voltage and current on the DC side. But a protection scheme employed for DCMG protection should not respond to these external faults. To demonstrate the effect of AC side faults on the proposed algorithm, an LLL fault on the AC side has been created at <italic>t</italic> &#x3d; 2&#xa0;s. To see the impact of this fault on the status of trip signals for both positive and negative pole relays, the energies of the DWT coefficients of the <italic>V</italic>
<sub>
<italic>twf</italic>
</sub> (i.e., <italic>E</italic>
<sub>
<italic>twfP</italic>
</sub> &#x26; <italic>E</italic>
<sub>
<italic>twfN</italic>
</sub>) are calculated at both positive and negative poles and presented in <xref ref-type="fig" rid="F15">Figure 15</xref>. As shown in the figure, the energies <italic>E</italic>
<sub>
<italic>twfP</italic>
</sub> and <italic>E</italic>
<sub>
<italic>twfN</italic>
</sub> are significantly less than the threshold value <italic>E</italic>
<sub>
<italic>th</italic>
</sub> which is equal to 120. Hence, the trip signal stays low and the protection scheme will not treat this event as a fault.</p>
<fig id="F15" position="float">
<label>FIGURE 15</label>
<caption>
<p>Energy content of DWT coefficients of <italic>V</italic>
<sub>
<italic>twf</italic>
</sub> at both positive and negative poles following an LLL-fault on the AC side.</p>
</caption>
<graphic xlink:href="fenrg-11-1100789-g015.tif"/>
</fig>
</sec>
<sec id="s5-2-2">
<title>5.2.2 External close-in fault</title>
<p>To verify the effect of close-in external fault on the nearby relays, a PPG fault is simulated closer to the relay R<sub>P2</sub> outside its protection zone, as shown in <xref ref-type="fig" rid="F16">Figure 16A</xref>.</p>
<fig id="F16" position="float">
<label>FIGURE16</label>
<caption>
<p>
<bold>(A)</bold> Close-in external fault; <bold>(B)</bold> Energy of voltage travelling wave at positive pole following a close-in external PPG fault.</p>
</caption>
<graphic xlink:href="fenrg-11-1100789-g016.tif"/>
</fig>
<p>To see the effect of this fault on the tripping status of the relay RP2, the energy of the DWT coefficients of the voltage travelling wave is calculated, and the same has been presented in <xref ref-type="fig" rid="F16">Figure 16B</xref>. As the energy of the DWT coefficient at this point is less than the threshold value, the trip signal for the relay <italic>R</italic>
<sub>
<italic>P2</italic>
</sub> stays low. It means that the relay <italic>R</italic>
<sub>
<italic>P2</italic>
</sub> remains unaffected during this external fault.</p>
</sec>
</sec>
<sec id="s5-3">
<title>5.3 Non-fault conditions</title>
<p>A decent protection algorithm needs to be discriminatory enough to distinguish between a fault and a no-fault state. Therefore, several non-fault scenarios such as: grid outage; load switching; DG uncertainty; DG outages; and disconnection of any other distribution line, were simulated and the results have been presented in <xref ref-type="table" rid="T4">Table 4</xref>. The results presented in <xref ref-type="table" rid="T4">Table 4</xref> confirm the selectivity of the proposed approach for non-fault conditions, as this scheme remains unaffected from these non-fault operations.</p>
</sec>
<sec id="s5-4">
<title>5.4 Summary</title>
<p>In the previous section, the effectiveness of the proposed algorithm has been verified by implementing this for various fault and non-fault scenarios, and a summary of the same has been presented in <xref ref-type="table" rid="T4">Table 4</xref>. The proposed algorithm can effectively detect PPG, NPG, and PP faults during both islanded and grid-integrated operations. In grid-integrated mode, it can provide protection against HRF of up to 900&#xa0;&#x2126;. While during islanded operation, it can detect HRF up to 1,300&#xa0;&#x2126;. The operating time of the presented scheme is 0.64&#xa0;m, which is quite fast. In the case of MRA-based schemes, the operating time does not depend on the type of fault and the fault resistances, it mainly depends on the sampling frequency and the no. of samples considered for evaluation. <xref ref-type="table" rid="T5">Table 5</xref> shows the effect of sampling frequency and no. of samples on the fault detection time of the proposed scheme. The information presented in the table shows that the proposed scheme works satisfactorily (with slight compromise in fault detection time, i.e., 0.8&#xa0;m) up to the sampling frequency as low as 10&#xa0;kHz.</p>
<table-wrap id="T5" position="float">
<label>TABLE</label>
<caption>
<p>5 Effect of sampling frequency and no. of samples (N) on the fault detection time of the proposed scheme.</p>
</caption>
<table>
<thead valign="top">
<tr>
<th rowspan="2" align="left">Sampling frequency (kHz)</th>
<th colspan="5" align="center">Fault detection time (ms)</th>
</tr>
<tr>
<th align="left">N &#x3d; 64</th>
<th align="left">N &#x3d; 32</th>
<th align="left">N &#x3d; 16</th>
<th align="left">N &#x3d; 8</th>
<th align="left">N &#x3d; 4</th>
</tr>
</thead>
<tbody valign="top">
<tr>
<td align="left">200</td>
<td align="left">2.56</td>
<td align="left">1.28</td>
<td align="left">0.64</td>
<td align="left">&#x2014;</td>
<td align="left">&#x2014;</td>
</tr>
<tr>
<td align="left">20</td>
<td align="left">3.2</td>
<td align="left">1.6</td>
<td align="left">0.8</td>
<td align="left">0.4</td>
<td align="left">0.4</td>
</tr>
<tr>
<td align="left">10</td>
<td align="left">&#x2014;</td>
<td align="left">3.2</td>
<td align="left">1.6</td>
<td align="left">0.8</td>
<td align="left">0.8</td>
</tr>
<tr>
<td align="left">4</td>
<td align="left">&#x2014;</td>
<td align="left">8</td>
<td align="left">4</td>
<td align="left">2</td>
<td align="left">2</td>
</tr>
</tbody>
</table>
</table-wrap>
</sec>
</sec>
<sec id="s6">
<title>6 Real-time validation</title>
<p>The operational validation of the proposed algorithm is conducted with the OPAL-RT time simulator. The laboratory set-up for the real-time validation is shown in <xref ref-type="fig" rid="F17">Figure 17</xref>. The test system shown in <xref ref-type="fig" rid="F1">Figure 1</xref> is used for real-time simulation. Several cases were simulated for real-time validation of the proposed scheme, and the result of one such case has been presented here.</p>
<fig id="F17" position="float">
<label>FIGURE 17</label>
<caption>
<p>Laboratory set-up for real-time validation of the proposed algorithm.</p>
</caption>
<graphic xlink:href="fenrg-11-1100789-g017.tif"/>
</fig>
<sec id="s6-1">
<title>6.1 Case: PPG fault with <italic>R</italic>
<sub>
<italic>f</italic>
</sub> &#x3d; 0.1&#xa0;&#x2126; in grid-integrated mode</title>
<p>The real-time result of a PPG fault in grid-integrated mode, with <italic>R</italic>
<sub>
<italic>f</italic>
</sub> &#x3d; 50&#xa0;&#x2126;, is shown in <xref ref-type="fig" rid="F18">Figure 18</xref>. As seen in the figure, the wavelet energy (<italic>E</italic>
<sub>
<italic>twf</italic>
</sub>) increases up on the fault inception, and as soon as this energy becomes greater than the threshold value, the trip signal becomes high. The change in fault current (<italic>I</italic>
<sub>
<italic>f</italic>
</sub>) and the variation in positive pole voltage at bus-2 (<italic>V</italic>
<sub>
<italic>B2P</italic>
</sub>) following the PPG fault inception can also be observed in <xref ref-type="fig" rid="F18">Figure 18</xref>.</p>
<fig id="F18" position="float">
<label>FIGURE 18</label>
<caption>
<p>Real-time result for PPG fault at the middle of the line P12 with <italic>R</italic>
<sub>
<italic>f</italic>
</sub> &#x3d; 50&#xa0;&#x2126; during the grid-integrated mode.</p>
</caption>
<graphic xlink:href="fenrg-11-1100789-g018.tif"/>
</fig>
</sec>
</sec>
<sec id="s7">
<title>7 Comparative study</title>
<p>In <xref ref-type="table" rid="T5">Table 5</xref>, the performance of the suggested algorithm is contrasted with that of other currently available techniques. <xref ref-type="table" rid="T6">Table 6</xref> shows that the suggested algorithm can identify a ground fault up to a fault resistance of 900&#xa0;&#x2126; in the grid-integrated mode, which is greater than the other approaches stated in the literature. The suggested algorithm operates in 0.64&#xa0;m, which is faster than the majority of the algorithms described in the literature. The suggested system does not malfunction in the presence of an outside disturbance like an AC side fault, a grid outage, or a DG outage. Since it is unaffected by external or non-fault situations, this protection strategy offers superior stability than others. Investigating whether a protection strategy is adaptable enough to function well in both grid-integrated and islanded modes is another crucial situation. This situation has not been taken into account by the numerous protection strategies studied in the literature. However, the efficiency of the suggested algorithm has been carefully examined for both grid-integrated and islanded operations. The study&#x2019;s findings confirm that the suggested strategy can properly function in both operating modes. Additionally, in islanded mode, it is capable of detecting PG faults up to 1,300&#xa0;&#x2126; fault resistance. As a result, the suggested scheme proves to be superior to the other existing schemes in many aspects.</p>
<table-wrap id="T6" position="float">
<label>TABLE 6</label>
<caption>
<p>Comparison of the proposed algorithm with existing methods.</p>
</caption>
<table>
<thead valign="top">
<tr>
<th rowspan="2" align="left">Parameters/Operation of the relay</th>
<th rowspan="2" align="left">Proposed scheme</th>
<th colspan="7" align="center">Existing methods</th>
</tr>
<tr>
<th align="left">
<xref ref-type="bibr" rid="B7">Chauhan et al. (2022)</xref>
</th>
<th align="left">
<xref ref-type="bibr" rid="B8">Dhar et al. (2018)</xref>
</th>
<th align="left">
<xref ref-type="bibr" rid="B14">Kesava Rao and Jena, (2022)</xref>
</th>
<th align="left">
<xref ref-type="bibr" rid="B25">Wang et al. (2021)</xref>
</th>
<th align="left">
<xref ref-type="bibr" rid="B19">Saleh et al. (2017)</xref>
</th>
<th align="left">
<xref ref-type="bibr" rid="B16">Mohanty et al. (2021)</xref>
</th>
<th align="left">
<xref ref-type="bibr" rid="B10">Jayamaha et al. (2019)</xref>
</th>
</tr>
</thead>
<tbody valign="top">
<tr>
<td align="left">Relay operating time (ms)</td>
<td align="left">0.64</td>
<td align="left">1</td>
<td align="left">&#x3c;100</td>
<td align="left">3</td>
<td align="left">1</td>
<td align="left">3</td>
<td align="left">3</td>
<td align="left">3&#x2013;5.5</td>
</tr>
<tr>
<td align="left">HRF in grid connected mode</td>
<td align="left">900&#xa0;&#x2126;</td>
<td align="left">1&#xa0;&#x2126;</td>
<td align="left">2&#xa0;&#x2126;</td>
<td align="left">30&#xa0;&#x2126;</td>
<td align="left">10&#xa0;&#x2126;</td>
<td align="left">200&#xa0;&#x2126;</td>
<td align="left">10&#xa0;&#x2126;</td>
<td align="left">300&#xa0;&#x2126;</td>
</tr>
<tr>
<td align="left">Protection in islanded mode</td>
<td align="left">Yes</td>
<td align="left">Yes</td>
<td align="left">&#xd7;</td>
<td align="left">&#xd7;</td>
<td align="left">&#xd7;</td>
<td align="left">&#xd7;</td>
<td align="left">&#xd7;</td>
<td align="left">Yes</td>
</tr>
<tr>
<td align="left">HRF in islanded mode</td>
<td align="left">1,300&#xa0;&#x2126;</td>
<td align="left">&#xd7;</td>
<td align="left">&#xd7;</td>
<td align="left">&#xd7;</td>
<td align="left">&#xd7;</td>
<td align="left">&#xd7;</td>
<td align="left">&#xd7;</td>
<td align="left">&#xd7;</td>
</tr>
<tr>
<td align="left">AC side faults</td>
<td align="left">No</td>
<td align="left">No</td>
<td align="left">&#xd7;</td>
<td align="left">&#xd7;</td>
<td align="left">&#xd7;</td>
<td align="left">Yes</td>
<td align="left">&#xd7;</td>
<td align="left">&#xd7;</td>
</tr>
<tr>
<td align="left">Grid outage</td>
<td align="left">No</td>
<td align="left">No</td>
<td align="left">&#xd7;</td>
<td align="left">&#xd7;</td>
<td align="left">&#xd7;</td>
<td align="left">&#xd7;</td>
<td align="left">&#xd7;</td>
<td align="left">&#xd7;</td>
</tr>
<tr>
<td align="left">Close-in external fault</td>
<td align="left">No</td>
<td align="left">No</td>
<td align="left">&#xd7;</td>
<td align="left">No</td>
<td align="left">&#xd7;</td>
<td align="left">Yes</td>
<td align="left">&#xd7;</td>
<td align="left">&#xd7;</td>
</tr>
<tr>
<td align="left">DG outage</td>
<td align="left">No</td>
<td align="left">No</td>
<td align="left">&#xd7;</td>
<td align="left">&#xd7;</td>
<td align="left">&#xd7;</td>
<td align="left">&#xd7;</td>
<td align="left">&#xd7;</td>
<td align="left">&#xd7;</td>
</tr>
<tr>
<td align="left">DG uncertainty</td>
<td align="left">No</td>
<td align="left">No</td>
<td align="left">&#xd7;</td>
<td align="left">No</td>
<td align="left">&#xd7;</td>
<td align="left">&#xd7;</td>
<td align="left">&#xd7;</td>
<td align="left">&#xd7;</td>
</tr>
</tbody>
</table>
<table-wrap-foot>
<fn>
<p>&#xd7;, Not Considered.</p>
</fn>
</table-wrap-foot>
</table-wrap>
</sec>
<sec sec-type="conclusion" id="s8">
<title>8 Conclusion</title>
<p>For the preservation of DCMG, a novel protection system has been described in this study. In order to verify the effectiveness of the suggested approach, a test model for a 500&#xa0;V ring-main bipolar DCMG was created in the MATLAB/Simulink environment. Faults such as PPG, NPG, and PP were then simulated. The suggested algorithm has been shown to be a very efficient solution for the protection of DC microgrids and can function well in both grid-integrated and islanded modes. Additionally, it is capable of detecting HRFs of up to 900&#x2126; in grid-integrated mode and 1,300&#xa0;&#x2126; in islanded mode. The operating time of the proposed algorithm is independent of the type of faults and fault resistances, and it can detect all types of faults in 0.64&#xa0;m, which is quite fast. The suggested algorithm&#x2019;s resilience has been tested during faults and external disturbance transients, and it has been discovered that this scheme is unaffected by these external disturbances. The suggested approach is therefore very robust, accurate, and highly selective and offers a quick, stable, and trustworthy solution for the protection of DC microgrids.</p>
</sec>
</body>
<back>
<sec sec-type="data-availability" id="s9">
<title>Data availability statement</title>
<p>The raw data supporting the conclusion of this article will be made available by the authors, without undue reservation.</p>
</sec>
<sec id="s10">
<title>Author contributions</title>
<p>KK, SA, and OG has contributed to the conception and design of this work. KK has done the statistical analysis and prepared the first draft of the manuscript. All authors contributed to manuscript revision, read, and approved the submitted version.</p>
</sec>
<sec sec-type="COI-statement" id="s11">
<title>Conflict of interest</title>
<p>The authors declare that the research was conducted in the absence of any commercial or financial relationships that could be construed as a potential conflict of interest.</p>
</sec>
<sec sec-type="disclaimer" id="s12">
<title>Publisher&#x2019;s note</title>
<p>All claims expressed in this article are solely those of the authors and do not necessarily represent those of their affiliated organizations, or those of the publisher, the editors and the reviewers. Any product that may be evaluated in this article, or claim that may be made by its manufacturer, is not guaranteed or endorsed by the publisher.</p>
</sec>
<ref-list>
<title>References</title>
<ref id="B1">
<citation citation-type="journal">
<person-group person-group-type="author">
<name>
<surname>Aftab</surname>
<given-names>M. A.</given-names>
</name>
<name>
<surname>Hussain</surname>
<given-names>S. M. S.</given-names>
</name>
<name>
<surname>Ali</surname>
<given-names>I.</given-names>
</name>
<name>
<surname>Ustun</surname>
<given-names>T. S.</given-names>
</name>
</person-group> (<year>2018</year>). <article-title>Dynamic protection of power systems with high penetration of renewables: A review of the traveling wave based fault location techniques</article-title>. <source>Int. J. Electr. Power Energy Syst.</source> <volume>114</volume>, <fpage>105410</fpage>. <pub-id pub-id-type="doi">10.1016/j.ijepes.2019.105410</pub-id>
</citation>
</ref>
<ref id="B2">
<citation citation-type="journal">
<person-group person-group-type="author">
<name>
<surname>Al-Ismail</surname>
<given-names>F. S.</given-names>
</name>
</person-group> (<year>2021</year>). <article-title>DC microgrid planning, operation, and control: A comprehensive review</article-title>. <source>IEEE Access</source> <volume>9</volume>, <fpage>36154</fpage>&#x2013;<lpage>36172</lpage>. <pub-id pub-id-type="doi">10.1109/ACCESS.2021.3062840</pub-id>
</citation>
</ref>
<ref id="B3">
<citation citation-type="book">
<person-group person-group-type="author">
<name>
<surname>Augustine</surname>
<given-names>S.</given-names>
</name>
<name>
<surname>Quiroz</surname>
<given-names>J. E.</given-names>
</name>
<name>
<surname>Reno</surname>
<given-names>M. J.</given-names>
</name>
<name>
<surname>Brahma</surname>
<given-names>S.</given-names>
</name>
</person-group> (<year>2018</year>). &#x201c;<article-title>DC microgrid protection: Review and challenges</article-title>,&#x201d;. <comment>SAND2018-8853</comment> (<publisher-loc>Albuquerque, NM</publisher-loc>: <publisher-name>Sandia National Laboratories</publisher-name>). <pub-id pub-id-type="doi">10.2172/1465634</pub-id>
</citation>
</ref>
<ref id="B4">
<citation citation-type="journal">
<person-group person-group-type="author">
<name>
<surname>Beheshtaein</surname>
<given-names>S.</given-names>
</name>
<name>
<surname>Cuzner</surname>
<given-names>R. M.</given-names>
</name>
<name>
<surname>Forouzesh</surname>
<given-names>M.</given-names>
</name>
<name>
<surname>Savaghebi</surname>
<given-names>M.</given-names>
</name>
<name>
<surname>Guerrero</surname>
<given-names>J. M.</given-names>
</name>
</person-group> (<year>2019</year>). <article-title>DC microgrid protection: A comprehensive review</article-title>. <source>IEEE J. Emerg. Sel. Top. Power Electron.</source>, <fpage>1</fpage>. <comment>in press</comment>. <pub-id pub-id-type="doi">10.1109/jestpe.2019.2904588</pub-id>
</citation>
</ref>
<ref id="B5">
<citation citation-type="journal">
<person-group person-group-type="author">
<name>
<surname>Bentley</surname>
<given-names>P. M.</given-names>
</name>
<name>
<surname>McDonnell</surname>
<given-names>J. T. E.</given-names>
</name>
</person-group> (<year>1994</year>). <article-title>Wavelet transforms: An introduction</article-title>. <source>Electron. Commun. Eng. J.</source> <volume>6</volume> (<issue>4</issue>), <fpage>175</fpage>&#x2013;<lpage>186</lpage>. <pub-id pub-id-type="doi">10.1049/ecej:19940401</pub-id>
</citation>
</ref>
<ref id="B6">
<citation citation-type="journal">
<person-group person-group-type="author">
<name>
<surname>Burke</surname>
<given-names>P. J.</given-names>
</name>
<name>
<surname>Stern</surname>
<given-names>D. I.</given-names>
</name>
<name>
<surname>Bruns</surname>
<given-names>S. B.</given-names>
</name>
</person-group> (<year>2018</year>). <article-title>The impact of electricity on economic development: A macroeconomic perspective</article-title>. <source>Int. Rev. Environ. Resour. Econ.</source> <volume>12</volume> (<issue>1</issue>), <fpage>85</fpage>&#x2013;<lpage>127</lpage>. <pub-id pub-id-type="doi">10.1561/101.00000101</pub-id>
</citation>
</ref>
<ref id="B7">
<citation citation-type="journal">
<person-group person-group-type="author">
<name>
<surname>Chauhan</surname>
<given-names>P.</given-names>
</name>
<name>
<surname>Gupta</surname>
<given-names>C. P.</given-names>
</name>
<name>
<surname>Tripathy</surname>
<given-names>M.</given-names>
</name>
</person-group> (<year>2022</year>). <article-title>A novel adaptive protection technique based on rate-of-rise of Fault Current in DC microgrid</article-title>. <source>Electr. Power Syst. Res.</source> <volume>207</volume>, <fpage>107832</fpage>&#x2013;<lpage>107913</lpage>. <pub-id pub-id-type="doi">10.1016/j.epsr.2022.107832</pub-id>
</citation>
</ref>
<ref id="B8">
<citation citation-type="journal">
<person-group person-group-type="author">
<name>
<surname>Dhar</surname>
<given-names>S.</given-names>
</name>
<name>
<surname>Patnaik</surname>
<given-names>R. K.</given-names>
</name>
<name>
<surname>Dash</surname>
<given-names>P. K.</given-names>
</name>
</person-group> (<year>2018</year>). <article-title>fault detection and location of photovoltaic based DC microgrid using differential protection strategy</article-title>. <source>IEEE Trans. Smart Grid</source> <volume>9</volume> (<issue>5</issue>), <fpage>4303</fpage>&#x2013;<lpage>4312</lpage>. <pub-id pub-id-type="doi">10.1109/TSG.2017.2654267</pub-id>
</citation>
</ref>
<ref id="B9">
<citation citation-type="journal">
<person-group person-group-type="author">
<name>
<surname>Gielen</surname>
<given-names>D.</given-names>
</name>
<name>
<surname>Boshell</surname>
<given-names>F.</given-names>
</name>
<name>
<surname>Saygin</surname>
<given-names>D.</given-names>
</name>
<name>
<surname>Bazilian</surname>
<given-names>M. D.</given-names>
</name>
<name>
<surname>Wagner</surname>
<given-names>N.</given-names>
</name>
<name>
<surname>Gorini</surname>
<given-names>R.</given-names>
</name>
</person-group> (<year>2019</year>). <article-title>The role of renewable energy in the global energy transformation</article-title>. <source>Energy Strateg. Rev.</source> <volume>24</volume>, <fpage>38</fpage>&#x2013;<lpage>50</lpage>. <pub-id pub-id-type="doi">10.1016/j.esr.2019.01.006</pub-id>
</citation>
</ref>
<ref id="B10">
<citation citation-type="journal">
<person-group person-group-type="author">
<name>
<surname>Jayamaha</surname>
<given-names>D. K. J. S.</given-names>
</name>
<name>
<surname>Lidula</surname>
<given-names>N. W. A.</given-names>
</name>
<name>
<surname>Rajapakse</surname>
<given-names>A. D.</given-names>
</name>
</person-group> (<year>2019</year>). <article-title>Wavelet-multi resolution analysis based ANN architecture for fault detection and localization in DC microgrids</article-title>. <source>IEEE Access</source> <volume>7</volume>, <fpage>145371</fpage>&#x2013;<lpage>145384</lpage>. <pub-id pub-id-type="doi">10.1109/ACCESS.2019.2945397</pub-id>
</citation>
</ref>
<ref id="B11">
<citation citation-type="journal">
<person-group person-group-type="author">
<name>
<surname>Joos</surname>
<given-names>G.</given-names>
</name>
<name>
<surname>Reilly</surname>
<given-names>J.</given-names>
</name>
<name>
<surname>Bower</surname>
<given-names>W.</given-names>
</name>
<name>
<surname>Neal</surname>
<given-names>R.</given-names>
</name>
</person-group> (<year>2017</year>). <article-title>The need for standardization: The benefits to the core functions of the microgrid control system</article-title>. <source>IEEE Power Energy Mag.</source> <volume>15</volume> (<issue>4</issue>), <fpage>32</fpage>&#x2013;<lpage>40</lpage>. <pub-id pub-id-type="doi">10.1109/MPE.2017.2690518</pub-id>
</citation>
</ref>
<ref id="B12">
<citation citation-type="journal">
<person-group person-group-type="author">
<name>
<surname>Justo</surname>
<given-names>J. J.</given-names>
</name>
<name>
<surname>Mwasilu</surname>
<given-names>F.</given-names>
</name>
<name>
<surname>Lee</surname>
<given-names>J.</given-names>
</name>
<name>
<surname>Jung</surname>
<given-names>J. W.</given-names>
</name>
</person-group> (<year>2013</year>). <article-title>AC-microgrids versus DC-microgrids with distributed energy resources: A review</article-title>. <source>Renew. Sustain. Energy Rev.</source> <volume>24</volume>, <fpage>387</fpage>&#x2013;<lpage>405</lpage>. <pub-id pub-id-type="doi">10.1016/J.RSER.2013.03.067</pub-id>
</citation>
</ref>
<ref id="B13">
<citation citation-type="journal">
<person-group person-group-type="author">
<name>
<surname>Kant</surname>
<given-names>K.</given-names>
</name>
<name>
<surname>Gupta</surname>
<given-names>O. H.</given-names>
</name>
</person-group> (<year>2022</year>). <article-title>DC microgrid: A comprehensive review on protection challenges and schemes</article-title>. <source>IETE Tech. Rev.</source> <volume>210</volume>, <fpage>1</fpage>&#x2013;<lpage>17</lpage>. <pub-id pub-id-type="doi">10.1080/02564602.2022.2136271</pub-id>
</citation>
</ref>
<ref id="B14">
<citation citation-type="journal">
<person-group person-group-type="author">
<name>
<surname>Kesava Rao</surname>
<given-names>G.</given-names>
</name>
<name>
<surname>Jena</surname>
<given-names>P.</given-names>
</name>
</person-group> (<year>2022</year>). <article-title>Unit protection of tapped line DC microgrid</article-title>. <source>IEEE J. Emerg. Sel. Top. Power Electron.</source> <volume>10</volume> (<issue>4</issue>), <fpage>4680</fpage>&#x2013;<lpage>4689</lpage>. <pub-id pub-id-type="doi">10.1109/JESTPE.2022.3143525</pub-id>
</citation>
</ref>
<ref id="B15">
<citation citation-type="confproc">
<person-group person-group-type="author">
<name>
<surname>Manohar</surname>
<given-names>M.</given-names>
</name>
<name>
<surname>Koley</surname>
<given-names>E.</given-names>
</name>
<name>
<surname>Ghosh</surname>
<given-names>S.</given-names>
</name>
</person-group> (<year>2019</year>). &#x201c;<article-title>A wavelet and ANFIS based reliable protection technique for Microgrid</article-title>,&#x201d; in <conf-name>Proceedings of the 2019 8th International Conference on Power Systems: Transition towards Sustainable, Smart and Flexible Grids ICPS</conf-name>, <fpage>1</fpage>&#x2013;<lpage>6</lpage>. <pub-id pub-id-type="doi">10.1109/ICPS48983.2019.9067617</pub-id>
<conf-loc>Jaipur, India</conf-loc> <conf-date>December 2019</conf-date>
</citation>
</ref>
<ref id="B16">
<citation citation-type="journal">
<person-group person-group-type="author">
<name>
<surname>Mohanty</surname>
<given-names>R.</given-names>
</name>
<name>
<surname>Sahoo</surname>
<given-names>S.</given-names>
</name>
<name>
<surname>Pradhan</surname>
<given-names>A. K.</given-names>
</name>
<name>
<surname>Blaabjerg</surname>
<given-names>F.</given-names>
</name>
</person-group> (<year>2021</year>). <article-title>A cosine similarity-based centralized protection scheme for dc microgrids</article-title>. <source>IEEE J. Emerg. Sel. Top. Power Electron.</source> <volume>9</volume> (<issue>5</issue>), <fpage>5646</fpage>&#x2013;<lpage>5656</lpage>. <pub-id pub-id-type="doi">10.1109/JESTPE.2021.3060587</pub-id>
</citation>
</ref>
<ref id="B17">
<citation citation-type="confproc">
<person-group person-group-type="author">
<name>
<surname>Pukhova</surname>
<given-names>V.</given-names>
</name>
<name>
<surname>Gorelova</surname>
<given-names>E.</given-names>
</name>
<name>
<surname>Ferrini</surname>
<given-names>G.</given-names>
</name>
<name>
<surname>Burnasheva</surname>
<given-names>S.</given-names>
</name>
</person-group> (<year>2017</year>). &#x201c;<article-title>Time-frequency representation of signals by wavelet transform</article-title>,&#x201d; in <conf-name>Proc. 2017 IEEE Russ. Sect. Young Res. Electr. Electron. Eng. Conf. ElConRus</conf-name>, <conf-loc>Moscow, Russia</conf-loc>, <conf-date>April. 2017</conf-date>, <fpage>715</fpage>&#x2013;<lpage>718</lpage>. <pub-id pub-id-type="doi">10.1109/EICONRUS.2017.7910658</pub-id>
</citation>
</ref>
<ref id="B18">
<citation citation-type="journal">
<person-group person-group-type="author">
<name>
<surname>Sabug</surname>
<given-names>L.</given-names>
</name>
<name>
<surname>Musa</surname>
<given-names>A.</given-names>
</name>
<name>
<surname>Costa</surname>
<given-names>F.</given-names>
</name>
<name>
<surname>Monti</surname>
<given-names>A.</given-names>
</name>
</person-group> (<year>2019</year>). <article-title>Real-time boundary wavelet transform-based DC fault protection system for MTDC grids</article-title>. <source>Int. J. Electr. Power Energy Syst.</source> <volume>115</volume>, <fpage>105475</fpage>. <pub-id pub-id-type="doi">10.1016/j.ijepes.2019.105475</pub-id>
</citation>
</ref>
<ref id="B19">
<citation citation-type="journal">
<person-group person-group-type="author">
<name>
<surname>Saleh</surname>
<given-names>K. A.</given-names>
</name>
<name>
<surname>Hooshyar</surname>
<given-names>A.</given-names>
</name>
<name>
<surname>El-Saadany</surname>
<given-names>E. F.</given-names>
</name>
</person-group> (<year>2017</year>). <article-title>Hybrid passive-overcurrent relay for detection of faults in low-voltage DC grids</article-title>. <source>IEEE Trans. Smart Grid</source> <volume>8</volume> (<issue>3</issue>), <fpage>1129</fpage>&#x2013;<lpage>1138</lpage>. <pub-id pub-id-type="doi">10.1109/TSG.2015.2477482</pub-id>
</citation>
</ref>
<ref id="B20">
<citation citation-type="journal">
<person-group person-group-type="author">
<name>
<surname>Saleh</surname>
<given-names>K. A.</given-names>
</name>
<name>
<surname>Hooshyar</surname>
<given-names>A.</given-names>
</name>
<name>
<surname>El-Saadany</surname>
<given-names>E. F.</given-names>
</name>
</person-group> (<year>2019</year>). <article-title>Ultra-high-speed traveling-wave-based protection scheme for medium-voltage DC microgrids</article-title>. <source>IEEE Trans. Smart Grid</source> <volume>10</volume> (<issue>2</issue>), <fpage>1440</fpage>&#x2013;<lpage>1451</lpage>. <pub-id pub-id-type="doi">10.1109/TSG.2017.2767552</pub-id>
</citation>
</ref>
<ref id="B21">
<citation citation-type="journal">
<person-group person-group-type="author">
<name>
<surname>Shabani</surname>
<given-names>A.</given-names>
</name>
<name>
<surname>Mazlumi</surname>
<given-names>K.</given-names>
</name>
</person-group> (<year>2020</year>). <article-title>Evaluation of a communication-assisted overcurrent protection scheme for photovoltaic-based DC microgrid</article-title>. <source>IEEE Trans. Smart Grid</source> <volume>11</volume> (<issue>1</issue>), <fpage>429</fpage>&#x2013;<lpage>439</lpage>. <pub-id pub-id-type="doi">10.1109/TSG.2019.2923769</pub-id>
</citation>
</ref>
<ref id="B22">
<citation citation-type="confproc">
<person-group person-group-type="author">
<name>
<surname>Sharma</surname>
<given-names>N. K.</given-names>
</name>
<name>
<surname>Saxena</surname>
<given-names>A.</given-names>
</name>
<name>
<surname>Samantaray</surname>
<given-names>S. R.</given-names>
</name>
</person-group> &#x201c;<article-title>An intelligent differential protection scheme for DC microgrid</article-title>,&#x201d; in <conf-name>Proceedings of the 2021 9th IEEE International Conference on Power Systems (ICPS)</conf-name>, <conf-loc>Moscow, Russia</conf-loc>, <conf-date>December 2021</conf-date>, <fpage>1</fpage>&#x2013;<lpage>6</lpage>. <pub-id pub-id-type="doi">10.1109/icps52420.2021.9670330</pub-id>
</citation>
</ref>
<ref id="B23">
<citation citation-type="journal">
<person-group person-group-type="author">
<name>
<surname>Sun</surname>
<given-names>S.</given-names>
</name>
<name>
<surname>Tang</surname>
<given-names>C.</given-names>
</name>
<name>
<surname>Hailati</surname>
<given-names>G.</given-names>
</name>
<name>
<surname>Xie</surname>
<given-names>D.</given-names>
</name>
</person-group> (<year>2022</year>). <article-title>Voltage monitoring based on ANN-aided nonlinear stability analysis for DC microgrids</article-title>. <source>Front. Energy Res.</source> <volume>1</volume>, <fpage>1</fpage>&#x2013;<lpage>14</lpage>. <pub-id pub-id-type="doi">10.3389/FENRG.2022.1045809</pub-id>
</citation>
</ref>
<ref id="B24">
<citation citation-type="journal">
<person-group person-group-type="author">
<name>
<surname>Tiwari</surname>
<given-names>R. S.</given-names>
</name>
<name>
<surname>Gupta</surname>
<given-names>O. H.</given-names>
</name>
<name>
<surname>Sood</surname>
<given-names>V. K.</given-names>
</name>
</person-group> (<year>2022</year>). <article-title>fault detection using backward propagating traveling waves for bipolar LCC-HVDC lines</article-title>. <source>Electr. Power Components Syst.</source> <volume>50</volume> (<issue>1</issue>), <fpage>1</fpage>&#x2013;<lpage>14</lpage>. <comment>accepted</comment>. <pub-id pub-id-type="doi">10.1080/15325008.2022.2136788</pub-id>
</citation>
</ref>
<ref id="B25">
<citation citation-type="journal">
<person-group person-group-type="author">
<name>
<surname>Wang</surname>
<given-names>T.</given-names>
</name>
<name>
<surname>Liang</surname>
<given-names>L.</given-names>
</name>
<name>
<surname>Gurumurthy</surname>
<given-names>S. K.</given-names>
</name>
<name>
<surname>Ponci</surname>
<given-names>F.</given-names>
</name>
<name>
<surname>Monti</surname>
<given-names>A.</given-names>
</name>
<name>
<surname>Yang</surname>
<given-names>Z.</given-names>
</name>
<etal/>
</person-group> (<year>2021</year>). <article-title>Model-based fault detection and isolation in DC microgrids using optimal observers</article-title>. <source>IEEE J. Emerg. Sel. Top. Power Electron.</source> <volume>9</volume> (<issue>5</issue>), <fpage>5613</fpage>&#x2013;<lpage>5630</lpage>. <pub-id pub-id-type="doi">10.1109/JESTPE.2020.3045418</pub-id>
</citation>
</ref>
<ref id="B26">
<citation citation-type="journal">
<person-group person-group-type="author">
<name>
<surname>Yadav</surname>
<given-names>N.</given-names>
</name>
<name>
<surname>Tummuru</surname>
<given-names>N. R.</given-names>
</name>
</person-group> (<year>2020</year>). <article-title>A real-time resistance based fault detection technique for zonal type low-voltage DC microgrid applications</article-title>. <source>IEEE Trans. Ind. Appl.</source> <volume>56</volume> (<issue>6</issue>), <fpage>6815</fpage>&#x2013;<lpage>6824</lpage>. <pub-id pub-id-type="doi">10.1109/TIA.2020.3017564</pub-id>
</citation>
</ref>
<ref id="B27">
<citation citation-type="journal">
<person-group person-group-type="author">
<name>
<surname>Zhang</surname>
<given-names>Y.</given-names>
</name>
<name>
<surname>Tai</surname>
<given-names>N.</given-names>
</name>
<name>
<surname>Xu</surname>
<given-names>B.</given-names>
</name>
</person-group> (<year>2012</year>). <article-title>Fault analysis and traveling-wave protection scheme for bipolar HVDC lines</article-title>. <source>IEEE Trans. Power Deliv.</source> <volume>27</volume> (<issue>3</issue>), <fpage>1583</fpage>&#x2013;<lpage>1591</lpage>. <pub-id pub-id-type="doi">10.1109/TPWRD.2012.2190528</pub-id>