<?xml version="1.0" encoding="UTF-8"?>
<!DOCTYPE article PUBLIC "-//NLM//DTD Journal Publishing DTD v2.3 20070202//EN" "journalpublishing.dtd">
<article article-type="research-article" dtd-version="2.3" xml:lang="EN" xmlns:mml="http://www.w3.org/1998/Math/MathML" xmlns:xlink="http://www.w3.org/1999/xlink">
<front>
<journal-meta>
<journal-id journal-id-type="publisher-id">Front. Energy Res.</journal-id>
<journal-title>Frontiers in Energy Research</journal-title>
<abbrev-journal-title abbrev-type="pubmed">Front. Energy Res.</abbrev-journal-title>
<issn pub-type="epub">2296-598X</issn>
<publisher>
<publisher-name>Frontiers Media S.A.</publisher-name>
</publisher>
</journal-meta>
<article-meta>
<article-id pub-id-type="publisher-id">1106836</article-id>
<article-id pub-id-type="doi">10.3389/fenrg.2022.1106836</article-id>
<article-categories>
<subj-group subj-group-type="heading">
<subject>Energy Research</subject>
<subj-group>
<subject>Original Research</subject>
</subj-group>
</subj-group>
</article-categories>
<title-group>
<article-title>Enhancing transient stability of power systems using a resistive superconducting fault current limiter</article-title>
<alt-title alt-title-type="left-running-head">Alashqar et al.</alt-title>
<alt-title alt-title-type="right-running-head">
<ext-link ext-link-type="uri" xlink:href="https://doi.org/10.3389/fenrg.2022.1106836">10.3389/fenrg.2022.1106836</ext-link>
</alt-title>
</title-group>
<contrib-group>
<contrib contrib-type="author">
<name>
<surname>Alashqar</surname>
<given-names>Mohamed</given-names>
</name>
<xref ref-type="aff" rid="aff1">
<sup>1</sup>
</xref>
<xref ref-type="aff" rid="aff2">
<sup>2</sup>
</xref>
<xref ref-type="aff" rid="aff3">
<sup>3</sup>
</xref>
<uri xlink:href="https://loop.frontiersin.org/people/1928228/overview"/>
</contrib>
<contrib contrib-type="author" corresp="yes">
<name>
<surname>Yang</surname>
<given-names>Conghuan</given-names>
</name>
<xref ref-type="aff" rid="aff1">
<sup>1</sup>
</xref>
<xref ref-type="corresp" rid="c001">&#x2a;</xref>
<uri xlink:href="https://loop.frontiersin.org/people/1590647/overview"/>
</contrib>
<contrib contrib-type="author">
<name>
<surname>Xue</surname>
<given-names>Ying</given-names>
</name>
<xref ref-type="aff" rid="aff4">
<sup>4</sup>
</xref>
<uri xlink:href="https://loop.frontiersin.org/people/1901708/overview"/>
</contrib>
<contrib contrib-type="author">
<name>
<surname>Liu</surname>
<given-names>Zhaoxi</given-names>
</name>
<xref ref-type="aff" rid="aff4">
<sup>4</sup>
</xref>
</contrib>
<contrib contrib-type="author">
<name>
<surname>Zheng</surname>
<given-names>Weiye</given-names>
</name>
<xref ref-type="aff" rid="aff4">
<sup>4</sup>
</xref>
<uri xlink:href="https://loop.frontiersin.org/people/1831610/overview"/>
</contrib>
<contrib contrib-type="author">
<name>
<surname>Zhang</surname>
<given-names>Xiao-Ping</given-names>
</name>
<xref ref-type="aff" rid="aff2">
<sup>2</sup>
</xref>
<uri xlink:href="https://loop.frontiersin.org/people/1437942/overview"/>
</contrib>
</contrib-group>
<aff id="aff1">
<sup>1</sup>
<institution>Department of Electrical Engineering</institution>, <institution>School of Naval Architecture and Ocean Engineering</institution>, <institution>Guangzhou Maritime University</institution>, <addr-line>Guangzhou</addr-line>, <country>China</country>
</aff>
<aff id="aff2">
<sup>2</sup>
<institution>Department of Electronic, Electrical and Systems Engineering</institution>, <institution>School of Engineering</institution>, <institution>University of Birmingham</institution>, <addr-line>Birmingham</addr-line>, <addr-line>England</addr-line>, <country>United Kingdom</country>
</aff>
<aff id="aff3">
<sup>3</sup>
<institution>Qatar General Electricity &#x26; Water Corporation (KAHRAMAA)</institution>, <addr-line>Doha</addr-line>, <country>Qatar</country>
</aff>
<aff id="aff4">
<sup>4</sup>
<institution>School of Electric Power Engineering</institution>, <institution>South China University of Technology</institution>, <addr-line>Guangzhou</addr-line>, <country>China</country>
</aff>
<author-notes>
<fn fn-type="edited-by">
<p>
<bold>Edited by:</bold> <ext-link ext-link-type="uri" xlink:href="https://loop.frontiersin.org/people/1235831/overview">Xue Lyu</ext-link>, University of Wisconsin-Madison, United States</p>
</fn>
<fn fn-type="edited-by">
<p>
<bold>Reviewed by:</bold> <ext-link ext-link-type="uri" xlink:href="https://loop.frontiersin.org/people/2113921/overview">Yangbin Zeng</ext-link>, Tsinghua University, China</p>
<p>
<ext-link ext-link-type="uri" xlink:href="https://loop.frontiersin.org/people/2116905/overview">Sen Zhang</ext-link>, State Grid Jiangsu Electric Power Co., LTD., China</p>
</fn>
<corresp id="c001">&#x2a;Correspondence: Conghuan Yang, <email>conghuanyang@foxmail.com</email>
</corresp>
<fn fn-type="other">
<p>This article was submitted to Smart Grids, a section of the journal Frontiers in Energy Research</p>
</fn>
</author-notes>
<pub-date pub-type="epub">
<day>23</day>
<month>01</month>
<year>2023</year>
</pub-date>
<pub-date pub-type="collection">
<year>2022</year>
</pub-date>
<volume>10</volume>
<elocation-id>1106836</elocation-id>
<history>
<date date-type="received">
<day>24</day>
<month>11</month>
<year>2022</year>
</date>
<date date-type="accepted">
<day>08</day>
<month>12</month>
<year>2022</year>
</date>
</history>
<permissions>
<copyright-statement>Copyright &#xa9; 2023 Alashqar, Yang, Xue, Liu, Zheng and Zhang.</copyright-statement>
<copyright-year>2023</copyright-year>
<copyright-holder>Alashqar, Yang, Xue, Liu, Zheng and Zhang</copyright-holder>
<license xlink:href="http://creativecommons.org/licenses/by/4.0/">
<p>This is an open-access article distributed under the terms of the Creative Commons Attribution License (CC BY). The use, distribution or reproduction in other forums is permitted, provided the original author(s) and the copyright owner(s) are credited and that the original publication in this journal is cited, in accordance with accepted academic practice. No use, distribution or reproduction is permitted which does not comply with these terms.</p>
</license>
</permissions>
<abstract>
<p>The electricity demand keeps increasing with development and time, which leads to the need to install more generating units in the grid. Therefore, the fault current levels will rise above the limits of the electrical equipment, particularly when the electric grid becomes meshed and interconnected with neighboring networks. Consequently, the electrical equipment needs to be replaced or use a method that will decrease the fault current to be within the permissible boundaries. The existing solutions such as neutral impedance, current limiting reactor (CLR), and bus splitting have negative impacts on the electric grid. The superconducting fault current limiter (SFCL) appears to be a promising solution. In this paper, the resistive SFCL is proposed to enhance the stability of the interconnected power system. The two-area system is used as a case study for the interconnected power system. Also, the optimal value and locations of the resistive SFCL are analyzed. The results show that the system will remain stable without tuning the power system stabilizer (PSS).</p>
</abstract>
<kwd-group>
<kwd>interconnected power system</kwd>
<kwd>two-area system</kwd>
<kwd>resistive superconductor fault current limiter</kwd>
<kwd>fault location</kwd>
<kwd>power system dynamic</kwd>
</kwd-group>
</article-meta>
</front>
<body>
<sec id="s1">
<title>1 Introduction</title>
<p>One of the unique properties of the power system operation is that the electrical speed of all generating units must be the same (<xref ref-type="bibr" rid="B37">Padiyar, 2004</xref>). This is known as the synchronous operation of the power system. However, any disturbance to the power system operation can affect the rotating speeds of rotors, i.e., the network frequency (<xref ref-type="bibr" rid="B23">Kundur, 1994</xref>; <xref ref-type="bibr" rid="B3">Anderson and Fouad, 2003</xref>; <xref ref-type="bibr" rid="B22">Kundur et al., 2004</xref>; <xref ref-type="bibr" rid="B37">Padiyar, 2004</xref>; <xref ref-type="bibr" rid="B14">Grigsby, 2012</xref>). The transient stability (<italic>large-disturbance rotor angle stability)</italic> is defined as &#x201c;the ability of the power system to maintain synchronism when subjected to a severe disturbance, such as a short circuit on transmission facilities, loss of generation, or loss of a large load&#x201d; where the small-signal stability is defined as &#x201c;the ability of the power system to maintain synchronism when subjected to small disturbances, such as switching of small loads, generators or transmission line tripping, for which the equations that describe the dynamics of the power system may be linearized for analytical purposes.&#x201d; (<xref ref-type="bibr" rid="B23">Kundur, 1994</xref>), (<xref ref-type="bibr" rid="B22">Kundur et al., 2004</xref>; <xref ref-type="bibr" rid="B9">Das, 2007</xref>; <xref ref-type="bibr" rid="B29">Machowski et al., 2008</xref>). It is essential to note that the transient stability is dependent on the operating condition and the perturbation, which makes the analysis of the transient stability more complicated. Also, the linearization analysis does not apply to transient stability analysis (<xref ref-type="bibr" rid="B37">Padiyar, 2004</xref>). Under a transient event, the system response involves large excursions of generator rotor angles, power flows, bus voltages, and other system variables. If the resulting angular separation between the machines in the power system remains within certain bounds, the system maintains synchronism. Loss of synchronism because of transient instability, if it occurs, will usually be evident within 2&#x2013;3&#xa0;s of the initial disturbance (<xref ref-type="bibr" rid="B23">Kundur, 1994</xref>).</p>
<p>The fault levels in the power system drastically increased due to various reasons. For example, the integration of multiple energy sectors (<xref ref-type="bibr" rid="B52">Zheng et al., 2020</xref>), the continuous increase in electricity demands, the massive scale of the power plants either conventional or renewable generation, and the expansion of power grid (<xref ref-type="bibr" rid="B20">Koyama and Yanabu, 2009</xref>; <xref ref-type="bibr" rid="B42">Sung et al., 2009</xref>; <xref ref-type="bibr" rid="B27">Li et al., 2014</xref>). Therefore, the stresses caused by excessive fault currents led to high mechanical, electrical, and thermal instabilities of electric networks (<xref ref-type="bibr" rid="B24">Lee et al., 2008</xref>). Consequently, the electrical apparatus might be damaged and cause a partial blackout or even a major blackout if the existing switch gears are not upgraded (<xref ref-type="bibr" rid="B3">Anderson and Fouad, 2003</xref>), (<xref ref-type="bibr" rid="B14">Grigsby, 2012</xref>), (<xref ref-type="bibr" rid="B32">Miyashita et al., 2005</xref>; <xref ref-type="bibr" rid="B18">Kodle et al., 2016</xref>; <xref ref-type="bibr" rid="B13">Glover et al., 2017</xref>). These changes are the main concerns for the transmission system operators because an increase in the fault levels negatively impacts the power system in terms of security and reliability (<xref ref-type="bibr" rid="B39">Ravindranath and Chander, 1977</xref>). Therefore, fault-limiting techniques are required. Many effective methods were used, for instance, bus splitting, current limiting reactors, and others. However, each of these has its own limiting factors. For example, using bus splitting will reduce the reliability of the interconnected system. Also, series reactors have drawbacks such as constant high reactive losses, bulky, and contributing to grid voltage drops. Therefore, a new technique should be utilized to overcome the disadvantages (<xref ref-type="bibr" rid="B5">Blair et al., 2012</xref>; <xref ref-type="bibr" rid="B41">Son et al., 2012</xref>; <xref ref-type="bibr" rid="B15">Jain et al., 2016</xref>). Different methods were used to mitigate the transient instability, such as flexible AC transmission system (FACTS) controller, which includes static VAR Compensator (SVC), thyristor-controlled series capacitor (TCSC), static synchronous series compensator (STATCOM) and unified power flow controller (UPFC) (<xref ref-type="bibr" rid="B16">Kamarposhti et al., 2021</xref>), (<xref ref-type="bibr" rid="B45">Wang et al., 2020</xref>).</p>
<p>Superconducting fault current limiters are superconducting power equipment whose impedance is small in steady-state condition and large in a fault condition. Therefore, SFCLs do not deteriorate power system stability in steady-state conditions and effectively limit the short-circuit currents in a fault condition (<xref ref-type="bibr" rid="B40">Sjostrom et al., 1999</xref>). Different types of SFCL are available in the market; resistive SFCLs, shielded Core FCL, SFCL bridge, and saturated iron core FCL. The Resistive SFCLs have been the primary choice for SFCL field experiments. Its popularity due to its simple concept, compact size and weight, and resistant nature (<xref ref-type="bibr" rid="B6">Blair, 2013</xref>). The shielded iron core SCFCL, or often called inductive SCFCL advantageous is that there is no current lead to cryogenic temperatures and that the superconductor is exhibited to large currents but low voltages. Like resistive SCFCLs, a quench takes place in the superconductor and therefore a recovery time of several seconds is needed. However, A major drawback of this type is the large volume and weight which is similar to a transformer of the same power rating (<xref ref-type="bibr" rid="B36">Noe and Steurer, 2007</xref>). SCFCL bridge rectifiers are made up of diodes or thyristors arranged in a complete bridge configuration. This SFCL type is undesirable because it no longer controls short-circuit current if, for example, one of the semiconductors fails and causes a short circuit. Furthermore, the total losses are rather substantial.</p>
<p>SFCLs are used to minimize the short circuit current to a definite value and have the ability to decrease the levels of fault current within the electricity grid by factors of 3&#x2013;10 times (<xref ref-type="bibr" rid="B4">Baldan et al., 2007</xref>), (<xref ref-type="bibr" rid="B10">Egorova et al., 2013</xref>). Under normal circumstances, SFCL is quenched to a temperature of approximately &#x2212;200&#xb0;C, which can be accomplished in a cost-efficient way by using liquid nitrogen (<xref ref-type="bibr" rid="B5">Blair et al., 2012</xref>), (<xref ref-type="bibr" rid="B40">Sjostrom et al., 1999</xref>), (<xref ref-type="bibr" rid="B25">Lee, 2011</xref>), (<xref ref-type="bibr" rid="B43">Vojen&#x10d;iak et al., 2016</xref>). This will minimize the material&#x2019;s resistivity, which means that it will not have any influence on the network under normal conditions (<xref ref-type="bibr" rid="B31">Matsumoto et al., 2010</xref>), (<xref ref-type="bibr" rid="B50">Yonemura et al., 2015</xref>). However, if the current goes above the nominal, the materials instantaneously lose their properties of superconductivity and work as a typical resistor. During that situation, the current will be reduced to a predefined value (<xref ref-type="bibr" rid="B24">Lee et al., 2008</xref>), (<xref ref-type="bibr" rid="B44">Wang et al., 2014</xref>). These properties make superconductors work as a self-triggered current limiter. Moreover, significant features introduced by the superconductors, such as negligible voltage drop and energy losses during steady-state operating conditions, enable higher grid loads without upgrading the equipment in the power system (<xref ref-type="bibr" rid="B19">Kovalsky et al., 2005</xref>; <xref ref-type="bibr" rid="B51">Zhang et al., 2015</xref>; <xref ref-type="bibr" rid="B21">Kumar et al., 2016</xref>).</p>
<p>The normalized non-linear relationship between current flow in a superconductor and its resistance is demonstrated in <xref ref-type="fig" rid="F1">Figure 1</xref>. It can be seen from <xref ref-type="fig" rid="F1">Figure 1</xref> that when a fault develops, the current rises, causing the superconductor to quench and exponentially increase its resistance. Most SFCL designs consider the above behavior to limit the fault current in the first cycle [<xref ref-type="bibr" rid="B11">Electric Power Research Institute (EPRI), 2009</xref>], (<xref ref-type="bibr" rid="B17">Khatibi and Bigdeli, 2014</xref>). Under normal grid operation, resistive SFCLs use superconducting material as the main current-carrying conductor. The principle of operation is shown in the single-line diagram in the upper half of <xref ref-type="fig" rid="F1">Figure 1</xref>. As mentioned before, the lower plot is a normalized performance of the voltage across <italic>R</italic>
<sub>
<italic>sc</italic>
</sub> as a function of the ratio of the current through the SFCL device (<italic>I</italic>
<sub>
<italic>Line</italic>
</sub>)to the critical current (<italic>I</italic>
<sub>
<italic>c</italic>
</sub>) of the superconducting element<italic>.</italic> The level of the current at which the quench happens is identified by the operating temperature, the size, and the category of the superconductor. The quick rise in resistance produces a voltage across the superconductor and leads the current to convey to a shunt, a combination of resistor and inductor. The shunt&#x2019;s role is to limit the voltage increase across the superconductor in the quench situation. In essence, the superconductor works like a switch with a millisecond response that stimulates the transition of the load current to the shunt impedance. Theoretically, the initial fault current is restricted to less than one cycle [<xref ref-type="bibr" rid="B11">Electric Power Research Institute (EPRI), 2009</xref>].</p>
<fig id="F1" position="float">
<label>FIGURE 1</label>
<caption>
<p>Resistive Type SFCL with Shunt Element and a normalized plot of voltage and current in a superconductor at a constant temperature and magnetic field. [<xref ref-type="bibr" rid="B11">Electric Power Research Institute (EPRI), 2009</xref>], (<xref ref-type="bibr" rid="B38">Pawar and Chavan, 2017</xref>).</p>
</caption>
<graphic xlink:href="fenrg-10-1106836-g001.tif"/>
</fig>
<p>Eq. <xref ref-type="disp-formula" rid="e1">1</xref> describes the characteristics of the resistive type of SFCL behavior (<xref ref-type="bibr" rid="B7">Chen et al., 2016a</xref>), (<xref ref-type="bibr" rid="B35">Moon et al., 2011</xref>).<disp-formula id="e1">
<mml:math id="m1">
<mml:mrow>
<mml:mi>R</mml:mi>
<mml:mrow>
<mml:mfenced open="(" close=")" separators="|">
<mml:mrow>
<mml:mi>t</mml:mi>
</mml:mrow>
</mml:mfenced>
</mml:mrow>
<mml:mo>&#x3d;</mml:mo>
<mml:mrow>
<mml:mfenced open="{" close="" separators="|">
<mml:mrow>
<mml:mtable columnalign="center">
<mml:mtr>
<mml:mtd>
<mml:mn>0</mml:mn>
</mml:mtd>
<mml:mtd>
<mml:mrow>
<mml:mfenced open="(" close=")" separators="|">
<mml:mrow>
<mml:mi>t</mml:mi>
<mml:mo>&#x3c;</mml:mo>
<mml:msub>
<mml:mi>t</mml:mi>
<mml:mn>0</mml:mn>
</mml:msub>
</mml:mrow>
</mml:mfenced>
</mml:mrow>
</mml:mtd>
</mml:mtr>
<mml:mtr>
<mml:mtd>
<mml:mrow>
<mml:msub>
<mml:mi>R</mml:mi>
<mml:mi>n</mml:mi>
</mml:msub>
<mml:msup>
<mml:mrow>
<mml:mfenced open="[" close="]" separators="|">
<mml:mrow>
<mml:mn>1</mml:mn>
<mml:mo>&#x2212;</mml:mo>
<mml:msup>
<mml:mi>e</mml:mi>
<mml:mrow>
<mml:mfenced open="(" close=")" separators="|">
<mml:mrow>
<mml:mo>&#x2212;</mml:mo>
<mml:mfrac>
<mml:mrow>
<mml:mi>t</mml:mi>
<mml:mo>&#x2212;</mml:mo>
<mml:msub>
<mml:mi>t</mml:mi>
<mml:mn>0</mml:mn>
</mml:msub>
</mml:mrow>
<mml:mi>T</mml:mi>
</mml:mfrac>
</mml:mrow>
</mml:mfenced>
</mml:mrow>
</mml:msup>
</mml:mrow>
</mml:mfenced>
</mml:mrow>
<mml:mrow>
<mml:mn>1</mml:mn>
<mml:mo>/</mml:mo>
<mml:mn>2</mml:mn>
</mml:mrow>
</mml:msup>
</mml:mrow>
</mml:mtd>
<mml:mtd>
<mml:mrow>
<mml:mfenced open="(" close=")" separators="|">
<mml:mrow>
<mml:msub>
<mml:mi>t</mml:mi>
<mml:mn>0</mml:mn>
</mml:msub>
<mml:mo>&#x2264;</mml:mo>
<mml:mi>t</mml:mi>
<mml:mo>&#x3c;</mml:mo>
<mml:msub>
<mml:mi>t</mml:mi>
<mml:mn>1</mml:mn>
</mml:msub>
</mml:mrow>
</mml:mfenced>
</mml:mrow>
</mml:mtd>
</mml:mtr>
<mml:mtr>
<mml:mtd>
<mml:mrow>
<mml:msub>
<mml:mi>C</mml:mi>
<mml:mn>1</mml:mn>
</mml:msub>
<mml:mrow>
<mml:mfenced open="(" close=")" separators="|">
<mml:mrow>
<mml:mi>t</mml:mi>
<mml:mo>&#x2212;</mml:mo>
<mml:msub>
<mml:mi>t</mml:mi>
<mml:mn>1</mml:mn>
</mml:msub>
</mml:mrow>
</mml:mfenced>
</mml:mrow>
<mml:mo>&#x2b;</mml:mo>
<mml:msub>
<mml:mi>D</mml:mi>
<mml:mn>1</mml:mn>
</mml:msub>
</mml:mrow>
</mml:mtd>
<mml:mtd>
<mml:mrow>
<mml:mfenced open="(" close=")" separators="|">
<mml:mrow>
<mml:msub>
<mml:mi>t</mml:mi>
<mml:mn>1</mml:mn>
</mml:msub>
<mml:mo>&#x2264;</mml:mo>
<mml:mi>t</mml:mi>
<mml:mo>&#x3c;</mml:mo>
<mml:msub>
<mml:mi>t</mml:mi>
<mml:mn>2</mml:mn>
</mml:msub>
</mml:mrow>
</mml:mfenced>
</mml:mrow>
</mml:mtd>
</mml:mtr>
<mml:mtr>
<mml:mtd>
<mml:mrow>
<mml:msub>
<mml:mi>C</mml:mi>
<mml:mn>2</mml:mn>
</mml:msub>
<mml:mrow>
<mml:mfenced open="(" close=")" separators="|">
<mml:mrow>
<mml:mi>t</mml:mi>
<mml:mo>&#x2212;</mml:mo>
<mml:msub>
<mml:mi>t</mml:mi>
<mml:mn>2</mml:mn>
</mml:msub>
</mml:mrow>
</mml:mfenced>
</mml:mrow>
<mml:mo>&#x2b;</mml:mo>
<mml:msub>
<mml:mi>D</mml:mi>
<mml:mn>2</mml:mn>
</mml:msub>
</mml:mrow>
</mml:mtd>
<mml:mtd>
<mml:mrow>
<mml:mfenced open="(" close=")" separators="|">
<mml:mrow>
<mml:msub>
<mml:mi>t</mml:mi>
<mml:mn>2</mml:mn>
</mml:msub>
<mml:mo>&#x2264;</mml:mo>
<mml:mi>t</mml:mi>
<mml:mo>&#x3c;</mml:mo>
<mml:msub>
<mml:mi>t</mml:mi>
<mml:mn>3</mml:mn>
</mml:msub>
</mml:mrow>
</mml:mfenced>
</mml:mrow>
</mml:mtd>
</mml:mtr>
</mml:mtable>
</mml:mrow>
</mml:mfenced>
</mml:mrow>
</mml:mrow>
</mml:math>
<label>(1)</label>
</disp-formula>
</p>
<p>
<italic>R</italic>
<sub>
<italic>n</italic>
</sub> denotes the SFCL&#x2019;s normal-state resistance; <italic>T</italic> is the time constant. The SFCL&#x2019;s time-domain characteristics of <italic>t0</italic>, <italic>t1,</italic> and <italic>t2</italic> indicate the quench-starting time, the first recovery-starting time, and the secondary recovery-starting time, respectively, as shown in <xref ref-type="fig" rid="F2">Figure 2</xref>. The function coefficients are C1, D1, C2, and D2, as stated in Eq. <xref ref-type="disp-formula" rid="e1">1</xref> (<xref ref-type="bibr" rid="B42">Sung et al., 2009</xref>), (<xref ref-type="bibr" rid="B7">Chen et al., 2016a</xref>), (<xref ref-type="bibr" rid="B12">Elshiekh et al., 2013</xref>), (<xref ref-type="bibr" rid="B28">Lim et al., 2009</xref>).</p>
<fig id="F2" position="float">
<label>FIGURE 2</label>
<caption>
<p>Quench/recovery model of the superconducting coil used in the SFCL (<xref ref-type="bibr" rid="B49">Yang et al., 2017</xref>), (<xref ref-type="bibr" rid="B8">Chen et al., 2016b</xref>).</p>
</caption>
<graphic xlink:href="fenrg-10-1106836-g002.tif"/>
</fig>
<p>In this paper, the resistive SCFL is used to verify that the fault current can be minimized significantly. Also, the transient stability of the power system can be enhanced without tuning the PSS. There are difficulties in tuning the PSS because the technique used, simulation study, field implementation, and the number of standard tests to be undertaken for its evaluation differ from utility to utility and vendor to vendor. As a result, the power system planner and the operator must examine and evaluate the efficiency of PSS tuning following the stated criteria for the specific power system. Nevertheless, many power plants have been reported to have tuned their PSS at unit commissioning, during automatic voltage regulator (AVR) modernization, or based on system operator observation/feedback (<xref ref-type="bibr" rid="B48">Wang et al., 2019</xref>).</p>
<p>It should be noted that refs (<xref ref-type="bibr" rid="B32">Miyashita et al., 2005</xref>), (<xref ref-type="bibr" rid="B38">Pawar and Chavan, 2017</xref>), (<xref ref-type="bibr" rid="B34">Mohamed, 2012</xref>), and (<xref ref-type="bibr" rid="B46">Wang et al., 2018a</xref>) used a single-machine infinite bus (SMIB) to study the improvement of the transient stability by using SCFL. However, each area contributes to the short circuit within the interconnected network in the interconnected power system. Therefore, this paper uses a two-area system with four synchronous machines to analyze the impact of resistive SCFL on angle stability. Different fault locations and fault types are considered in the analysis. Also, the optimal location and value of the resistive SFCL were analyzed.</p>
</sec>
<sec id="s2">
<title>2 Superconductor fault current limiter</title>
<p>To design a resistive SCFL, five parameters need to be defined (<xref ref-type="bibr" rid="B42">Sung et al., 2009</xref>), (<xref ref-type="bibr" rid="B51">Zhang et al., 2015</xref>), (<xref ref-type="bibr" rid="B1">Alaraifi et al., 2013</xref>), (<xref ref-type="bibr" rid="B46">Wang et al., 2018a</xref>):<list list-type="simple">
<list-item>
<p>1 The triggering current (the value at which the SFCL will be stimulated).</p>
</list-item>
<list-item>
<p>2 The quenching resistance (Maximum resistance).</p>
</list-item>
<list-item>
<p>3 The quenching time is the time that the SFCL will be activated.</p>
</list-item>
<list-item>
<p>4 The minimum resistance of 0.01&#x2126;, which is the SFCL&#x2019;s normal operation resistance.</p>
</list-item>
<list-item>
<p>5 The recovery time of 1&#xa0;s.</p>
</list-item>
</list>
</p>
<p>All these parameters have been taken into consideration in designing SFCL. The design of the single phase of the step resistance SFCL model is shown in <xref ref-type="fig" rid="F3">Figure 3</xref>. The principle of operation can be described as follows: firstly, the current measurement is used to measure the current of each phase to compute the absolute and RMS values of the phase line current by RMS block. If the RMS current is less than the triggering current, then the model will consider the SFCL in the normal operating state (superconductivity situation), and the SFCL will take a resistive value of 0.0&#xa0;L &#x2126; (the minimum resistance). Otherwise, if the RMS value of the line current is higher than the triggering current, then the model will lose the superconductivity state and increase rapidly to the maximum predefined value. Lastly, the fault current drops below the triggering current because the fault was cleared, and the SFCL restores the superconducting condition after recovery. The transport delay block is installed to implement the maximum resistance for 1&#xa0;s from the moment the fault occurs. The resistive SFCL is connected in series with the transmission line in the event of a short circuit. According to the above-mentioned, the summary of the parameters used in the SFCL modeling can be represented in <xref ref-type="table" rid="T1">Table 1</xref>.</p>
<fig id="F3" position="float">
<label>FIGURE 3</label>
<caption>
<p>Single-phase model of SFCL.</p>
</caption>
<graphic xlink:href="fenrg-10-1106836-g003.tif"/>
</fig>
<table-wrap id="T1" position="float">
<label>TABLE 1</label>
<caption>
<p>Parameters used in the SFCL.</p>
</caption>
<table>
<thead valign="top">
<tr>
<th align="center">Parameters</th>
<th align="center">Value</th>
</tr>
</thead>
<tbody valign="top">
<tr>
<td align="left">System voltage (3-phase)</td>
<td align="center">230&#xa0;kV</td>
</tr>
<tr>
<td align="left">Maximum resistance</td>
<td align="center">10&#x2126;</td>
</tr>
<tr>
<td align="left">Minimum resistance</td>
<td align="center">0.01&#x2126;</td>
</tr>
<tr>
<td align="left">Trigger current</td>
<td align="center">850&#xa0;A</td>
</tr>
<tr>
<td align="left">Time delay (recovery time)</td>
<td align="center">1&#xa0;s</td>
</tr>
</tbody>
</table>
</table-wrap>
</sec>
<sec id="s3">
<title>3 Power system model</title>
<p>The interconnected two-area system is shown in <xref ref-type="fig" rid="F4">Figure 4</xref>. The system consists of two similar areas connected <italic>via</italic> a weak tie line (230&#xa0;kV lines of 220&#xa0;km length (<xref ref-type="bibr" rid="B23">Kundur, 1994</xref>)). Each area has two synchronous generators, and there are 967&#xa0;MW, and 1767&#xa0;MW loads at area 1 and area 2, respectively, and the system operates with area 1 exporting 400&#xa0;MW to area 2; detailed parameters in the <xref ref-type="app" rid="app1">Appendix A1</xref>. <xref ref-type="fig" rid="F4">Figure 4</xref> shows the proposed locations of the resistive type SFCL in the interconnected power system, case 1 in <xref ref-type="fig" rid="F4">Figure 4A</xref>, and case 2 in <xref ref-type="fig" rid="F4">Figure 4B</xref>. The power system has been modeled in MATLAB and SIMULINK software to perform different scenarios. In the simulation studies, different types of faults are applied in different locations on line one to demonstrate the performance of SFCLs.</p>
<fig id="F4" position="float">
<label>FIGURE 4</label>
<caption>
<p>Two area system <bold>(A)</bold> case 1. <bold>(B)</bold> Case (2).</p>
</caption>
<graphic xlink:href="fenrg-10-1106836-g004.tif"/>
</fig>
<p>The short circuit current at bus <inline-formula id="inf1">
<mml:math id="m2">
<mml:mrow>
<mml:mi>i</mml:mi>
</mml:mrow>
</mml:math>
</inline-formula> can be calculated as follows<disp-formula id="e2">
<mml:math id="m3">
<mml:mrow>
<mml:msub>
<mml:mi>I</mml:mi>
<mml:mrow>
<mml:mi>s</mml:mi>
<mml:mi>c</mml:mi>
</mml:mrow>
</mml:msub>
<mml:mo>&#x3d;</mml:mo>
<mml:mfrac>
<mml:mrow>
<mml:msup>
<mml:mi>E</mml:mi>
<mml:mi>i</mml:mi>
</mml:msup>
</mml:mrow>
<mml:mrow>
<mml:msub>
<mml:mi>Z</mml:mi>
<mml:mrow>
<mml:mi>i</mml:mi>
<mml:mi>i</mml:mi>
</mml:mrow>
</mml:msub>
</mml:mrow>
</mml:mfrac>
</mml:mrow>
</mml:math>
<label>(2)</label>
</disp-formula>where is <inline-formula id="inf2">
<mml:math id="m4">
<mml:mrow>
<mml:msub>
<mml:mi>Z</mml:mi>
<mml:mrow>
<mml:mi>i</mml:mi>
<mml:mi>i</mml:mi>
</mml:mrow>
</mml:msub>
</mml:mrow>
</mml:math>
</inline-formula> bus impedance from <inline-formula id="inf3">
<mml:math id="m5">
<mml:mrow>
<mml:mi>i</mml:mi>
</mml:mrow>
</mml:math>
</inline-formula>, which includes the SFCL impedance as well, and <inline-formula id="inf4">
<mml:math id="m6">
<mml:mrow>
<mml:msup>
<mml:mi>E</mml:mi>
<mml:mi>i</mml:mi>
</mml:msup>
</mml:mrow>
</mml:math>
</inline-formula> is the pre-fault voltage of bus <inline-formula id="inf5">
<mml:math id="m7">
<mml:mrow>
<mml:mi>i</mml:mi>
</mml:mrow>
</mml:math>
</inline-formula>.</p>
<p>Increasing the critical clearing time or angle typically improves angular stability. Critical clearance time for a machine can be improved by avoiding active power changes during faults, according to the swing equation for a synchronous machine.<disp-formula id="e3">
<mml:math id="m8">
<mml:mrow>
<mml:mfrac>
<mml:mrow>
<mml:mi>d</mml:mi>
<mml:msub>
<mml:mi>&#x3c9;</mml:mi>
<mml:mi>k</mml:mi>
</mml:msub>
</mml:mrow>
<mml:mrow>
<mml:mi>d</mml:mi>
<mml:mi>t</mml:mi>
</mml:mrow>
</mml:mfrac>
<mml:mo>&#x3d;</mml:mo>
<mml:mfrac>
<mml:mrow>
<mml:mn>1</mml:mn>
</mml:mrow>
<mml:mrow>
<mml:msub>
<mml:mi>M</mml:mi>
<mml:mi>k</mml:mi>
</mml:msub>
</mml:mrow>
</mml:mfrac>
<mml:mrow>
<mml:mfenced open="(" close=")" separators="|">
<mml:mrow>
<mml:msubsup>
<mml:mi>P</mml:mi>
<mml:mi>m</mml:mi>
<mml:mi>k</mml:mi>
</mml:msubsup>
<mml:mo>&#x2212;</mml:mo>
<mml:msubsup>
<mml:mi>P</mml:mi>
<mml:mi>e</mml:mi>
<mml:mi>k</mml:mi>
</mml:msubsup>
</mml:mrow>
</mml:mfenced>
</mml:mrow>
</mml:mrow>
</mml:math>
<label>(3)</label>
</disp-formula>
<disp-formula id="e4">
<mml:math id="m9">
<mml:mrow>
<mml:msub>
<mml:mi>&#x3c9;</mml:mi>
<mml:mi>k</mml:mi>
</mml:msub>
<mml:mo>&#x3d;</mml:mo>
<mml:mfrac>
<mml:mrow>
<mml:mi>d</mml:mi>
<mml:msub>
<mml:mi>&#x3b4;</mml:mi>
<mml:mi>k</mml:mi>
</mml:msub>
</mml:mrow>
<mml:mrow>
<mml:mi>d</mml:mi>
<mml:mi>t</mml:mi>
</mml:mrow>
</mml:mfrac>
</mml:mrow>
</mml:math>
<label>(4)</label>
</disp-formula>
<disp-formula id="e5">
<mml:math id="m10">
<mml:mrow>
<mml:mi>H</mml:mi>
<mml:mo>&#x3d;</mml:mo>
<mml:mfrac>
<mml:msub>
<mml:mi>&#x3c9;</mml:mi>
<mml:mn>0</mml:mn>
</mml:msub>
<mml:mrow>
<mml:mn>2</mml:mn>
<mml:msub>
<mml:mi>M</mml:mi>
<mml:mi>k</mml:mi>
</mml:msub>
</mml:mrow>
</mml:mfrac>
</mml:mrow>
</mml:math>
<label>(5)</label>
</disp-formula>Where <inline-formula id="inf6">
<mml:math id="m11">
<mml:mrow>
<mml:msub>
<mml:mi>M</mml:mi>
<mml:mi>k</mml:mi>
</mml:msub>
</mml:mrow>
</mml:math>
</inline-formula> is the inertia consatant of machine <inline-formula id="inf7">
<mml:math id="m12">
<mml:mrow>
<mml:mi>k</mml:mi>
</mml:mrow>
</mml:math>
</inline-formula>, <inline-formula id="inf8">
<mml:math id="m13">
<mml:mrow>
<mml:msub>
<mml:mi>&#x3c9;</mml:mi>
<mml:mi>k</mml:mi>
</mml:msub>
</mml:mrow>
</mml:math>
</inline-formula> is the rotor speed of machine <inline-formula id="inf9">
<mml:math id="m14">
<mml:mrow>
<mml:mi>k</mml:mi>
</mml:mrow>
</mml:math>
</inline-formula>, <inline-formula id="inf10">
<mml:math id="m15">
<mml:mrow>
<mml:msub>
<mml:mi>&#x3b4;</mml:mi>
<mml:mi>k</mml:mi>
</mml:msub>
</mml:mrow>
</mml:math>
</inline-formula> is the rotor angle of machine <inline-formula id="inf11">
<mml:math id="m16">
<mml:mrow>
<mml:mi>k</mml:mi>
</mml:mrow>
</mml:math>
</inline-formula>, <inline-formula id="inf12">
<mml:math id="m17">
<mml:mrow>
<mml:msubsup>
<mml:mi>P</mml:mi>
<mml:mi>m</mml:mi>
<mml:mi>k</mml:mi>
</mml:msubsup>
</mml:mrow>
</mml:math>
</inline-formula> is the mechanical power of machine <inline-formula id="inf13">
<mml:math id="m18">
<mml:mrow>
<mml:mi>k</mml:mi>
</mml:mrow>
</mml:math>
</inline-formula>, and <inline-formula id="inf14">
<mml:math id="m19">
<mml:mrow>
<mml:msubsup>
<mml:mi>P</mml:mi>
<mml:mi>e</mml:mi>
<mml:mi>k</mml:mi>
</mml:msubsup>
</mml:mrow>
</mml:math>
</inline-formula> is the electrical power delevied machine <inline-formula id="inf15">
<mml:math id="m20">
<mml:mrow>
<mml:mi>k</mml:mi>
</mml:mrow>
</mml:math>
</inline-formula>. Hence, By subsituting Eqs <xref ref-type="disp-formula" rid="e4">4</xref>, <xref ref-type="disp-formula" rid="e5">5</xref> into Eq. <xref ref-type="disp-formula" rid="e3">3</xref>, the swing equation will be formulated in Eq. <xref ref-type="disp-formula" rid="e6">6</xref>
<disp-formula id="e6">
<mml:math id="m21">
<mml:mrow>
<mml:mfrac>
<mml:mrow>
<mml:mn>2</mml:mn>
<mml:msub>
<mml:mi>H</mml:mi>
<mml:mi>k</mml:mi>
</mml:msub>
</mml:mrow>
<mml:msub>
<mml:mi>&#x3c9;</mml:mi>
<mml:mn>0</mml:mn>
</mml:msub>
</mml:mfrac>
<mml:mfrac>
<mml:mrow>
<mml:msup>
<mml:mi>d</mml:mi>
<mml:mn>2</mml:mn>
</mml:msup>
<mml:msub>
<mml:mi>&#x3b4;</mml:mi>
<mml:mi>k</mml:mi>
</mml:msub>
</mml:mrow>
<mml:mrow>
<mml:mi>d</mml:mi>
<mml:msup>
<mml:mi>t</mml:mi>
<mml:mn>2</mml:mn>
</mml:msup>
</mml:mrow>
</mml:mfrac>
<mml:mo>&#x3d;</mml:mo>
<mml:mrow>
<mml:mfenced open="(" close=")" separators="|">
<mml:mrow>
<mml:msubsup>
<mml:mi>P</mml:mi>
<mml:mi>m</mml:mi>
<mml:mi>k</mml:mi>
</mml:msubsup>
<mml:mo>&#x2212;</mml:mo>
<mml:msubsup>
<mml:mi>P</mml:mi>
<mml:mi>e</mml:mi>
<mml:mi>k</mml:mi>
</mml:msubsup>
</mml:mrow>
</mml:mfenced>
</mml:mrow>
</mml:mrow>
</mml:math>
<label>(6)</label>
</disp-formula>
</p>
</sec>
<sec id="s4">
<title>4 Simulation results and observations</title>
<p>In this section, the system will be tested under different scenarios to verify that the SFCL can not only limit the fault current but also improve the power system&#x2019;s transient stability without tuning PSSs. Two kinds of PSS have been used: simplified PSS and conventional PSS. The simplified PSS is MB-PSS designed to introduce intermediate phase advance at all oscillation frequencies of interest, compensating for the inherent lag between field excitation and electrical torque (<xref ref-type="bibr" rid="B52">Zheng et al., 2020</xref>), (<xref ref-type="bibr" rid="B26">Leiva Roca et al., 2022</xref>). Therefore, only six parameters are required to be tuned. In contrast, the conventional PSS uses the measured electrical power and its relationship to shaft speed as an input signal (<xref ref-type="bibr" rid="B26">Leiva Roca et al., 2022</xref>), (<xref ref-type="bibr" rid="B47">Wang et al., 2018b</xref>).</p>
<sec id="s4-1">
<title>4.1 Simplified PSS with SFCL</title>
<p>As mentioned in the previous section, the main objective of using SFCL is to minimize the fault current. As shown in <xref ref-type="fig" rid="F5">Figures 5A, B</xref>, using the SFCL help reduce the fault current through the faulted line by 58%, and the fault current shared from area 1 is reduced by more than 50%.</p>
<fig id="F5" position="float">
<label>FIGURE 5</label>
<caption>
<p>
<bold>(A)</bold> The RMS current through the faulted line. <bold>(B)</bold> Phase-a RMS current with and without SFCL, from area one.</p>
</caption>
<graphic xlink:href="fenrg-10-1106836-g005.tif"/>
</fig>
<p>It is well known that PSS is one of the robust solutions to maintain system stability, if it is perfectly tuned, which can be seen in <xref ref-type="fig" rid="F6">Figures 6</xref>&#x2013;<xref ref-type="fig" rid="F8">8</xref>. However, if the SFCLs are installed in specific locations, the behavior of the power system will be enhanced. For example, <xref ref-type="fig" rid="F6">Figure 6</xref> shows the active power transferred from B1 to B2 when a severe fault (three phase fault) occurs in the middle of line one. During the fault, the active power drops 210&#xa0;MW when PSS is only used and when the SFCL installed at the end of each area (case 1) as shown in <xref ref-type="fig" rid="F4">Figure 4A</xref>. However, if the SFCL added also at the end of the faulted line (case 2) as shown in <xref ref-type="fig" rid="F4">Figure 4B</xref>, the active power drops will be less with 160&#xa0;MW.</p>
<fig id="F6" position="float">
<label>FIGURE 6</label>
<caption>
<p>
<bold>(A)</bold> Active power transferred from B1 and B2 when a three-phase fault is applied at the middle of line one. <bold>(B)</bold> Single line to ground fault applied in the middle of line one. <bold>(C)</bold> Different values of resistance of SFCLs in case 1.</p>
</caption>
<graphic xlink:href="fenrg-10-1106836-g006.tif"/>
</fig>
<fig id="F7" position="float">
<label>FIGURE 7</label>
<caption>
<p>
<bold>(A)</bold> The voltage at B1 (pu). <bold>(B)</bold> The voltage at B2 (pu). <bold>(C)</bold> G1 terminal voltage (pu).</p>
</caption>
<graphic xlink:href="fenrg-10-1106836-g007.tif"/>
</fig>
<fig id="F8" position="float">
<label>FIGURE 8</label>
<caption>
<p>
<bold>(A)</bold> G1 rotor speed (pu). <bold>(B)</bold> Electrical power output from G1 (pu). <bold>(C)</bold> The system performance when the fault resistance is 80&#x2126;. <bold>(D)</bold> The system performance when the fault resistance is 10&#x2126;.</p>
</caption>
<graphic xlink:href="fenrg-10-1106836-g008.tif"/>
</fig>
<p>For single phase fault in the middle of line one, the active power drops with 130&#xa0;MW in the case of PSS only used as shown in <xref ref-type="fig" rid="F6">Figure 6A</xref>. While in cases 1 and 2, the active power drops further with 150&#xa0;MW. In all cases, the system reaches the same steady state as shown in <xref ref-type="fig" rid="F6">Figure 6B</xref>.</p>
<p>The resistance value of the SFCL is important. For instance, <xref ref-type="fig" rid="F6">Figure 6C</xref> illustrates the performance of the active power flow from B1 to B2 when the resistance of the SFCLs changes. It can be seen that when the resistance value increases, there is a further drop in the active power in the event of a three-phase short circuit due to the power loss increasing during the quenching time of the SFCL. Also, increasing the resistance of the SFCL will increase the voltage drop in the grid.</p>
<p>The voltage stability is essential, which needs to be maintained at certain limits before, during, and after the fault. <xref ref-type="fig" rid="F7">Figures 7A, B</xref> show the voltage at B1 and B2, while <xref ref-type="fig" rid="F7">Figure 7C</xref> illustrates the terminal voltage of the G1. From these figures, it can be noticed that voltages drop to new steady-state conditions but are still within &#xb1;5% of the nominal. During the fault, the voltage dip is more because the system impedance increases during the disturbance with SFCLs. Nevertheless, once the fault is cleared, the SFCL returns to normal operation, and all buses&#x2019; voltages return to a stable state.</p>
<p>During the fault, the impact on the rotor speed of G1 is less when SFCLs are installed in both areas. Non-etheless, after the disturbance is cleared the rotor speed decreases by 0.002&#xa0;pu lower than the system with only PSSs installed at all units. Then this increases gradually to a new operating point, which is exemplified in <xref ref-type="fig" rid="F8">Figure 8A</xref>. When the disturbance occurs, the frequency rose to 60.18&#xa0;Hz because the active power is dropped sharply. Once the fault is cleared, the frequency drops to 59.82&#xa0;Hz, which is the minimum frequency. After that, the system returns to a steady state with a frequency of around 60.18&#xa0;Hz. Moreover, <xref ref-type="fig" rid="F8">Figure 8B</xref> demonstrates the electrical output power from generator one, which is located in area one, and the impact of using SFCL in desired locations.</p>
<p>The fault resistance can affect the system&#x2019;s transient performance. The following figures show the system performance when the value of the fault resistance is changed.</p>
<p>
<xref ref-type="fig" rid="F8">Figure 8C</xref> displays the active power transferred from B1 to B2 when the three-phase fault is applied at 1s for eight cycles. The fault resistance is 80&#x2126;. Without installing SFCLs, the active power transfer from area1 to area2 increases to 600&#xa0;MW compared to <xref ref-type="fig" rid="F6">Figure 6A</xref> when the fault resistance is small (0.001&#x2126;). However, if the SFCLs are installed at the proposed locations, as shown in <xref ref-type="fig" rid="F4">Figure 4</xref>, the transient active power will be reduced by 100&#xa0;MW, which means the stress on the generating units will be decreased. Additionally, if the fault resistance is 10&#x2126;, the active power flow will reach the pre-fault value steadily with the proposed locations as shown in <xref ref-type="fig" rid="F8">Figure 8D</xref>.</p>
<p>The fault location is also crucial in the power system stability study. When the three-phase fault occurs at 20&#xa0;km away from B2, the system losses synchronism as shown in <xref ref-type="fig" rid="F9">Figure 9B</xref> and without SFCL. Hence, by using SFCLs, the power system&#x2019;s synchronism can be maintained without any tuning of the PSS. Similarly, when the fault happens 20&#xa0;km away from B1, the system performance without SFCLs was influenced severely during and after the fault, with a maximum of 500&#xa0;MW and a minimum of 150&#xa0;MW. Notably, when the SFCLs are used in both areas, the difference will be reduced to 450&#xa0;MW at the maximum and 250&#xa0;MW at the minimum, as shown in <xref ref-type="fig" rid="F9">Figure 9A</xref>. Consequently, the stress on the generators will be restricted.</p>
<fig id="F9" position="float">
<label>FIGURE 9</label>
<caption>
<p>
<bold>(A)</bold> The fault is located 20&#xa0;km away from B1. <bold>(B)</bold> The fault is located 20&#xa0;km away from B2.</p>
</caption>
<graphic xlink:href="fenrg-10-1106836-g009.tif"/>
</fig>
</sec>
<sec id="s4-2">
<title>4.2 Conventional PSS with SFCL</title>
<p>The most crucial point is maintaining the continuity of power flow from B1 to B2. This depends on the severity of the short circuit and the system condition at the time of the fault. In this case, a three-phase fault has been applied in different locations on line 1. Before the fault incident, both transmission lines carried the same active power. However, once line 1 is tripped, the other line must carry the full transferred power from area-1 to area-2. <xref ref-type="fig" rid="F10">Figure 10A</xref> shows the power flow from B1 to B2 when a three-phase short circuit occurs in the middle of line one. The system with only conventional acceleration power delta power system stabilizer (Delta Pa) goes to instability, which means that the synchronism of the grid has been lost. Synchronization failure happens because Delta Pa PSS uses an open loop system. The conventional acceleration power-based- (Delta Pa) PSS is used for damping the small-signal oscillation and is unsuitable for large disturbances. However, with resistive SFCL the system is stable.</p>
<fig id="F10" position="float">
<label>FIGURE 10</label>
<caption>
<p>
<bold>(A)</bold> Transferred power from B1 to B2, when the fault applied at the middle of the transmission line one. <bold>(B)</bold> The voltage at B1 (pu). <bold>(C)</bold> The voltage at B2 (pu).</p>
</caption>
<graphic xlink:href="fenrg-10-1106836-g010.tif"/>
</fig>
<p>
<xref ref-type="fig" rid="F10">Figures 10C</xref> show the voltages at B1 and B2. It can be seen from the figure that the voltages go into instability after the disturbance. However, if the SFCL is used, the voltages are stable and within the operational limits of &#xb1;5% of the nominal value.</p>
<p>
<xref ref-type="fig" rid="F11">Figure 11A</xref> demonstrates the rotor speed of generator 1 in area 1. The frequency drops to 59.76&#xa0;Hz, with a peak value of 60.48&#xa0;Hz. Finally, the system reaches a steady state at 59.94&#xa0;Hz. That change in frequency is related to the change in electrical power output from generator 1, which is shown in <xref ref-type="fig" rid="F11">Figure 11C</xref>. While <xref ref-type="fig" rid="F11">Figure 11B</xref> shows the terminal voltage of machine 1 in area 1 as an example, and it is observed that the simulation stopped running for a few seconds after the short circuit happens. This is because the terminal voltage keeps increasing and the active power decreases. Nevertheless, the voltage is closer to the nominal value when the SFCLs were installed (either case 1 or 2).</p>
<fig id="F11" position="float">
<label>FIGURE 11</label>
<caption>
<p>
<bold>(A)</bold> G1 rotor speed (pu). <bold>(B)</bold> The terminal voltage of G1. <bold>(C)</bold> Electrical power output from G1.</p>
</caption>
<graphic xlink:href="fenrg-10-1106836-g011.tif"/>
</fig>
<p>
<xref ref-type="fig" rid="F12">Figure 12A</xref> shows that when the disturbance occurs near the receiving end bus, the system will collapse because the Delta Pa PSS uses an open loop system which is unable to maintain the system synchronism under a new highly stressed operating point. However, if the SFCLs are installed in association with the conventional PSS the system will remain synchronized and stable. <xref ref-type="fig" rid="F12">Figure 12B</xref> emphasizes that the SFCLs would improve the power system stability under any condition.</p>
<fig id="F12" position="float">
<label>FIGURE 12</label>
<caption>
<p>
<bold>(A)</bold> Transferred power from B1 to B2, when the fault applied at the 20&#xa0;km away from B2. <bold>(B)</bold> Transferred power from B1 to B2, when the fault applied at the 20&#xa0;km away from B1.</p>
</caption>
<graphic xlink:href="fenrg-10-1106836-g012.tif"/>
</fig>
</sec>
</sec>
<sec id="s5">
<title>5 SFCL practical application issues</title>
<p>There are still obstacles to the large-scale application of resistive-type SFCL. Although it is compact in structure, simple to implement (directly connected to the transmission line), has no control required, is rapid in response, and has minimal impact on the power grid, it requires a significant number of superconducting tapes (high in cost). In addition, it has higher AC loss generated during the current limiting period. There are still other issues, such as the costly material and production costs, the high cost of low-temperature operation and maintenance, and the operation&#x2019;s dependability not yet shown. Furthermore, the cryogenic system&#x2019;s capacity will rise with the number of superconductors. Therefore, the cryogenic system must be inspected and replaced regularly. As a result, cryogenic system stability and extended life expectancy should be necessary for the stable and safe operation of SFCLs.</p>
<p>From a protection point of view, when SFCLs were added to existing electric networks, the amount of the maximum fault current might change, affecting the protection coordination system between protective relays. To examine protection coordination with fault current limiters, the triggering level of the fault current limiters, the installation site, and the amount of impedance caused by the fault current limiter should also be considered.</p>
<p>Despite the superior current limiting capabilities achieved by SFCLs, commercialization and installation of superconducting fault limiters have been delayed due to technical and economic concerns as mentioned above. <xref ref-type="table" rid="T2">Table 2</xref> shows three resistive SFCL implemented in England, Germany and Italy.</p>
<table-wrap id="T2" position="float">
<label>TABLE 2</label>
<caption>
<p>Resistive SFCL Demonstration Projects [<xref ref-type="bibr" rid="B11">Electric Power Research Institute (EPRI), 2009</xref>], (<xref ref-type="bibr" rid="B30">Martini et al., 2014</xref>).</p>
</caption>
<table>
<thead valign="top">
<tr>
<th align="center">Projects</th>
<th align="center">England</th>
<th align="center">Germany</th>
<th align="center">A2A</th>
</tr>
</thead>
<tbody valign="top">
<tr>
<td align="center">Location</td>
<td align="center">Lancashire, United Kingdom</td>
<td align="center">Boxberg, Germany</td>
<td align="center">North Italy</td>
</tr>
<tr>
<td align="center">Site</td>
<td align="center">Bamber Bridge</td>
<td align="center">Local Power Plant</td>
<td align="center">San Dionigi Substation (MI)</td>
</tr>
<tr>
<td align="center">Status</td>
<td align="center">Operating</td>
<td align="center">Operating</td>
<td align="center">Fabrication of the first prototype</td>
</tr>
<tr>
<td align="center">Utility/Host</td>
<td align="center">Consortium</td>
<td align="center">Vattenfall Europe Generation AG</td>
<td align="center">A2A Reti Elettriche Spa Group</td>
</tr>
<tr>
<td align="center">In-Grid Start</td>
<td align="center">Fall 2009</td>
<td align="center">Fall 2009</td>
<td align="center">Early 2010</td>
</tr>
<tr>
<td align="center">Rated Current</td>
<td align="center">100 A</td>
<td align="center">800&#xa0;A</td>
<td align="center">250&#xa0;A</td>
</tr>
<tr>
<td align="center">Expected Max Fault Current</td>
<td align="center">55&#xa0;kA</td>
<td align="center">63&#xa0;kA</td>
<td align="center">30&#xa0;kA</td>
</tr>
<tr>
<td align="center">Current-Limiting Capability</td>
<td align="center">55&#xa0;kA &#x2192; 7&#xa0;kA</td>
<td align="center">63&#xa0;kA &#x2192; 30&#xa0;kA</td>
<td align="center">2 &#x3c; I<sub>SC</sub>/I<sub>Lim</sub> &#x3c; 2.2</td>
</tr>
<tr>
<td align="center">Max Limiting Duration</td>
<td align="center">0.12&#xa0;s</td>
<td align="center">0.12&#xa0;s</td>
<td align="center">300&#x2013;400&#xa0;m</td>
</tr>
<tr>
<td align="center">HTS Material</td>
<td align="center">BSSCO-2212 bulk tubes</td>
<td align="center">BSSCO-2212 bulk tubes</td>
<td align="center">BSCCO 1G</td>
</tr>
<tr>
<td align="center">HTS Conductor Supplier/Fabricator</td>
<td align="center">Nexans</td>
<td align="center">Nexans</td>
<td align="center">SEI</td>
</tr>
<tr>
<td align="center">Cryogen</td>
<td align="center">LN2</td>
<td align="center">LN2</td>
<td align="center">LN2</td>
</tr>
<tr>
<td align="center">Nominal Operating Temperature</td>
<td align="center">75&#xa0;K</td>
<td align="center">65&#xa0;K</td>
<td align="center">65&#xa0;K</td>
</tr>
</tbody>
</table>
</table-wrap>
</sec>
<sec id="s6">
<title>6 Fault current techniques within Qatar national grid</title>
<p>The transmission network in Qatar consists of 8 power plants that use natural gas and one PV power plant, and above 400 substations with different voltage levels (400&#xa0;kV, 220&#xa0;kV, 132&#xa0;kV, 66&#xa0;kV, 33&#xa0;kV, 22&#xa0;kV, and 11&#xa0;kV) (<xref ref-type="bibr" rid="B2">Alashqar et al., 2022</xref>). As a result, the transmission and distribution expansion meshed the national grid, and the fault level increased. <xref ref-type="fig" rid="F13">Figure 13</xref> shows the comparison between 2020 and 2021 subject to the total number of tripping the transmission network, and these tripping due to several reasons such as joint cable failure, protection maloperation, fault in the OHL, third-party damage, <italic>etc.,</italic>
</p>
<fig id="F13" position="float">
<label>FIGURE 13</label>
<caption>
<p>Total tripping in the transmission network in 2020 and 2021.</p>
</caption>
<graphic xlink:href="fenrg-10-1106836-g013.tif"/>
</fig>
<p>
<xref ref-type="fig" rid="F14">Figures 14</xref>, <xref ref-type="fig" rid="F15">15</xref> show a real measurement for the system behavior after a phase-phase fault occurred in the 400&#xa0;kV OHL circuit. The fault happened during the minimum time on 16th January 2021 when the number of running machines was less than the peak in summer. As a result, the system peak on the day of incidence is 50% less compared to the system peak in summer. <xref ref-type="fig" rid="F14">Figure 14</xref> illustrates that the fault current reached around 23&#xa0;kA in both phase a and phase b. Also, <xref ref-type="fig" rid="F15">Figure 15A</xref> shows the voltage behavior, and it can be seen clearly that a voltage dip occurred, and the voltage reached 308&#xa0;kV and normalized within 71&#xa0;m. Furthermore, as shown in <xref ref-type="fig" rid="F15">Figure 15B</xref>, the system frequency fluctuated to reach around 50.4&#xa0;Hz maximum and approximately 49.6&#xa0;Hz minimum.</p>
<fig id="F14" position="float">
<label>FIGURE 14</label>
<caption>
<p>Three phase current after phase-to-phase fault occurred.</p>
</caption>
<graphic xlink:href="fenrg-10-1106836-g014.tif"/>
</fig>
<fig id="F15" position="float">
<label>FIGURE 15</label>
<caption>
<p>
<bold>(A)</bold> Voltage behavior at 400&#xa0;kV level at one substation, <bold>(B)</bold> System frequency (readings every 50&#xa0;ms from PMU).</p>
</caption>
<graphic xlink:href="fenrg-10-1106836-g015.tif"/>
</fig>
<p>Traditional techniques are used to limit the fault current, such as splitting busbars, restricting generations in some locations, opening circuits (cable, OHL, and transformers), installing series reactors, and for future generations, high-impedance transformers are required. The SFCL is not preferable from a planning perspective due to the high cost compared to the other solution. For example, the cost of a series reactor in the 400&#xa0;kV level costs 3.2&#xa0;M$ (excluding the modification cost in the line), whereas a SFCL unit costs three times the series reactor. However, the SFCL is still developing, and the cost will decline with time.</p>
</sec>
<sec sec-type="conclusion" id="s7">
<title>6 Conclusion</title>
<p>Stability is a great concern of the power system operations, which needs to be maintained under any operating condition. However, the growth in the electricity supply and the sophistication in the electrical networks leads to an increase in fault current levels, threatening the power system stability. Therefore, a SFCL becomes a promising solution to overcome these challenges. This paper shows a comprehensive analysis of the influence of the SFCL in an interconnected power system. The key findings are:<list list-type="simple">
<list-item>
<p>1) The resistive value of the SFCL needs to be adjusted to avoid voltage drop during normal and abnormal operation conditions.</p>
</list-item>
<list-item>
<p>2) The best location for installing SFCL in the interconnected power system is at the end of each area before the tie line.</p>
</list-item>
<list-item>
<p>3) The fault current is reduced, avoiding the upgrade of the electric equipment.</p>
</list-item>
<list-item>
<p>4) The results show that deploying resistive SFCL enhances the system stability without tuning the power system stabilizer (PSS).</p>
</list-item>
</list>
</p>
</sec>
</body>
<back>
<sec sec-type="data-availability" id="s8">
<title>Data availability statement</title>
<p>The original contributions presented in the study are included in the article/Supplementary Material, further inquiries can be directed to the corresponding author.</p>
</sec>
<sec id="s9">
<title>Author contributions</title>
<p>MA, CY, and YX developed the original ideas and prepared the manuscript; ZL, WZ, and X-PZ helped revise the paper.</p>
</sec>
<sec sec-type="COI-statement" id="s10">
<title>Conflict of interest</title>
<p>MA was empolyed by the Qatar General Electricity &#x26; Water Corporation (KAHRAMAA).</p>
<p>The remaining authors declare that the research was conducted in the absence of any commercial or financial relationships that could be construed as a potential conflict of interest.</p>
</sec>
<sec sec-type="disclaimer" id="s11">
<title>Publisher&#x2019;s note</title>
<p>All claims expressed in this article are solely those of the authors and do not necessarily represent those of their affiliated organizations, or those of the publisher, the editors and the reviewers. Any product that may be evaluated in this article, or claim that may be made by its manufacturer, is not guaranteed or endorsed by the publisher.</p>
</sec>
<ref-list>
<title>References</title>
<ref id="B1">
<citation citation-type="journal">
<person-group person-group-type="author">
<name>
<surname>Alaraifi</surname>
<given-names>S.</given-names>
</name>
<name>
<surname>Moursi</surname>
<given-names>M. S. E.</given-names>
</name>
<name>
<surname>Zeineldin</surname>
<given-names>H. H.</given-names>
</name>
</person-group> (<year>2013</year>). <article-title>Optimal allocation of HTS-FCL for power system security and stability Enhancement</article-title>. <source>IEEE Trans. Power Syst.</source> <volume>28</volume> (<issue>4</issue>), <fpage>4701</fpage>&#x2013;<lpage>4711</lpage>. <pub-id pub-id-type="doi">10.1109/TPWRS.2013.2273539</pub-id>
</citation>
</ref>
<ref id="B2">
<citation citation-type="journal">
<person-group person-group-type="author">
<name>
<surname>Alashqar</surname>
<given-names>M.</given-names>
</name>
<name>
<surname>Xue</surname>
<given-names>Y.</given-names>
</name>
<name>
<surname>Yang</surname>
<given-names>C.</given-names>
</name>
<name>
<surname>Zhang</surname>
<given-names>X.-P.</given-names>
</name>
</person-group> (<year>2022</year>). <article-title>Comprehensive economic analysis of PV farm -A case study of Alkarsaah PV farm in Qatar</article-title>. <source>Front. Energy Res.</source> <volume>10</volume>. <fpage>987773</fpage>. <pub-id pub-id-type="doi">10.3389/fenrg.2022.987773</pub-id>
</citation>
</ref>
<ref id="B3">
<citation citation-type="book">
<person-group person-group-type="author">
<name>
<surname>Anderson</surname>
<given-names>P. M.</given-names>
</name>
<name>
<surname>Fouad</surname>
<given-names>A. A.</given-names>
</name>
</person-group> (<year>2003</year>). <source>Power system control and stability</source>. <edition>Second edition</edition>. <publisher-loc>Piscataway, NJ</publisher-loc>: <publisher-name>IEEE Press: Wiley-Interscience</publisher-name>.</citation>
</ref>
<ref id="B4">
<citation citation-type="journal">
<person-group person-group-type="author">
<name>
<surname>Baldan</surname>
<given-names>C. A.</given-names>
</name>
<name>
<surname>Shigue</surname>
<given-names>C. Y.</given-names>
</name>
<name>
<surname>Lamas</surname>
<given-names>J. S.</given-names>
</name>
<name>
<surname>Filho</surname>
<given-names>E. R.</given-names>
</name>
</person-group> (<year>2007</year>). <article-title>Test results of a superconducting fault current limiter using YBCO Coated conductor</article-title>. <source>IEEE Trans. Appl. Supercond.</source> <volume>17</volume> (<issue>2</issue>), <fpage>1903</fpage>&#x2013;<lpage>1906</lpage>. <pub-id pub-id-type="doi">10.1109/TASC.2007.897771</pub-id>
</citation>
</ref>
<ref id="B5">
<citation citation-type="journal">
<person-group person-group-type="author">
<name>
<surname>Blair</surname>
<given-names>S. M.</given-names>
</name>
<name>
<surname>Booth</surname>
<given-names>C. D.</given-names>
</name>
<name>
<surname>Burt</surname>
<given-names>G. M.</given-names>
</name>
</person-group> (<year>2012</year>). <article-title>Current&#x2013;time characteristics of resistive superconducting fault current limiters</article-title>. <source>IEEE Trans. Appl. Supercond.</source> <volume>22</volume> (<issue>2</issue>), <fpage>5600205</fpage>. <pub-id pub-id-type="doi">10.1109/TASC.2012.2187291</pub-id>
</citation>
</ref>
<ref id="B6">
<citation citation-type="book">
<person-group person-group-type="author">
<name>
<surname>Blair</surname>
<given-names>S. M.</given-names>
</name>
</person-group> (<year>2013</year>). <source>The analysis and application of resistive superconducting fault current limiters in present and future power systems</source>. <publisher-loc>Glasgow, Scotland</publisher-loc>: <publisher-name>University of Strathclyde</publisher-name>, <fpage>192</fpage>.</citation>
</ref>
<ref id="B7">
<citation citation-type="journal">
<person-group person-group-type="author">
<name>
<surname>Chen</surname>
<given-names>L.</given-names>
</name>
<name>
<surname>Chen</surname>
<given-names>H.</given-names>
</name>
<name>
<surname>Yang</surname>
<given-names>J.</given-names>
</name>
<name>
<surname>Shu</surname>
<given-names>Z.</given-names>
</name>
<name>
<surname>He</surname>
<given-names>H.</given-names>
</name>
<name>
<surname>Shu</surname>
<given-names>X.</given-names>
</name>
</person-group> (<year>2016</year>). <article-title>Conceptual design of a high-speed electromagnetic switch for a modified flux-coupling-type SFCL and its application in renewable energy system</article-title>. <source>SpringerPlus</source> <volume>5</volume>, <fpage>771</fpage>. <pub-id pub-id-type="doi">10.1186/s40064-016-2347-6</pub-id>
</citation>
</ref>
<ref id="B8">
<citation citation-type="journal">
<person-group person-group-type="author">
<name>
<surname>Chen</surname>
<given-names>L.</given-names>
</name>
<name>
<surname>Tu</surname>
<given-names>X.</given-names>
</name>
<name>
<surname>Chen</surname>
<given-names>H.</given-names>
</name>
<name>
<surname>Yang</surname>
<given-names>J.</given-names>
</name>
<name>
<surname>Wu</surname>
<given-names>Y.</given-names>
</name>
<name>
<surname>Shu</surname>
<given-names>X.</given-names>
</name>
<etal/>
</person-group> (<year>2016</year>). <article-title>Technical evaluation of superconducting fault current limiters used in a Micro-grid by considering the Fault characteristics of distributed generation, energy Storage and power loads</article-title>. <source>Energies</source> <volume>9</volume> (<issue>10</issue>), <fpage>769</fpage>. <pub-id pub-id-type="doi">10.3390/en9100769</pub-id>
</citation>
</ref>
<ref id="B9">
<citation citation-type="book">
<person-group person-group-type="author">
<name>
<surname>Das</surname>
<given-names>D.</given-names>
</name>
</person-group> (<year>2007</year>). <source>Electrical power systems</source>. <publisher-loc>New Delhi,India</publisher-loc>: <publisher-name>New Age International</publisher-name>.</citation>
</ref>
<ref id="B10">
<citation citation-type="web">
<person-group person-group-type="author">
<name>
<surname>Egorova</surname>
<given-names>E.</given-names>
</name>
<name>
<surname>Bahirat</surname>
<given-names>H.</given-names>
</name>
<name>
<surname>Mork</surname>
<given-names>D. B. A.</given-names>
</name>
<name>
<surname>Perger</surname>
<given-names>D. W. F.</given-names>
</name>
<name>
<surname>Holcomb</surname>
<given-names>D. M.</given-names>
</name>
</person-group> (<year>2013</year>). <article-title>EMTP-ATP modeling of a resistive superconducting fault current limiter</article-title>. <comment>Available at: <ext-link ext-link-type="uri" xlink:href="https://www.ipstconf.org/papers/Proc_IPST2013/13IPST071.pdf">https://www.ipstconf.org/papers/Proc_IPST2013/13IPST071.pdf</ext-link>.</comment>
</citation>
</ref>
<ref id="B11">
<citation citation-type="book">
<person-group person-group-type="author">
<name>
<surname>Electric Power Research Institute (Epri)</surname>
</name>
</person-group> (<year>2009</year>). <source>Superconducting Fault current limiters, technology watch 2009</source>. <publisher-loc>Palo Alto, CA</publisher-loc>: <publisher-name>EPRI</publisher-name>, <fpage>1017793</fpage>
<comment>. <ext-link ext-link-type="uri" xlink:href="http://assets.fiercemarkets.net/public/smartgridnews/000000000001017793.pdf">http://assets.fiercemarkets.net/public/smartgridnews/000000000001017793.pdf</ext-link> (accessed 20, 08, 2019)</comment>.</citation>
</ref>
<ref id="B12">
<citation citation-type="journal">
<person-group person-group-type="author">
<name>
<surname>Elshiekh</surname>
<given-names>M. E.</given-names>
</name>
<name>
<surname>Mansour</surname>
<given-names>D. A.</given-names>
</name>
<name>
<surname>Azmy</surname>
<given-names>A. M.</given-names>
</name>
</person-group> (<year>2013</year>). <article-title>Improving Fault Ride-through capability of DFIG-based Wind Turbine using superconducting fault current limiter</article-title>. <source>IEEE Trans. Appl. Supercond.</source> <volume>23</volume> (<issue>3</issue>), <fpage>5601204</fpage>. <pub-id pub-id-type="doi">10.1109/TASC.2012.2235132</pub-id>
</citation>
</ref>
<ref id="B13">
<citation citation-type="book">
<person-group person-group-type="author">
<name>
<surname>Glover</surname>
<given-names>J. D.</given-names>
</name>
<name>
<surname>Overbye</surname>
<given-names>T. J.</given-names>
</name>
<name>
<surname>Sarma</surname>
<given-names>M. S.</given-names>
</name>
</person-group> (<year>2017</year>). <source>Power system analysis &#x26; design</source>. <edition>Sixth edition</edition>. <publisher-loc>Boston, MA</publisher-loc>: <publisher-name>Cengage Learning</publisher-name>.</citation>
</ref>
<ref id="B14">
<citation citation-type="book">
<person-group person-group-type="author">
<name>
<surname>Grigsby</surname>
<given-names>L. L.</given-names>
</name>
</person-group> (<year>2012</year>). <source>Power system stability and control [electronic resource]</source>. <edition>3rd ed.</edition> (<publisher-loc>Boca Raton, Fla</publisher-loc>: <publisher-name>CRC Press</publisher-name>).</citation>
</ref>
<ref id="B15">
<citation citation-type="confproc">
<person-group person-group-type="author">
<name>
<surname>Jain</surname>
<given-names>A.</given-names>
</name>
<name>
<surname>Dubey</surname>
<given-names>V. K.</given-names>
</name>
<name>
<surname>Jawale</surname>
<given-names>G.</given-names>
</name>
<name>
<surname>Mangalvedekar</surname>
<given-names>H. A.</given-names>
</name>
<name>
<surname>Kanakgiri</surname>
<given-names>K.</given-names>
</name>
</person-group> (<year>2016</year>). &#x201c;<article-title>Limiting fault current in a power system network by SFCL: A step input approach</article-title>,&#x201d; in <conf-name>2016 IEEE 6th International Conference on Power Systems (ICPS)</conf-name>, <conf-loc>New Delhi, India</conf-loc>, <conf-date>March 2016</conf-date> (<publisher-name>IEEE</publisher-name>), <fpage>1</fpage>&#x2013;<lpage>5</lpage>. <pub-id pub-id-type="doi">10.1109/ICPES.2016.7584095</pub-id>
</citation>
</ref>
<ref id="B16">
<citation citation-type="journal">
<person-group person-group-type="author">
<name>
<surname>Kamarposhti</surname>
<given-names>M. A.</given-names>
</name>
<name>
<surname>Shokouhandeh</surname>
<given-names>H.</given-names>
</name>
<name>
<surname>Colak</surname>
<given-names>I.</given-names>
</name>
<name>
<surname>Band</surname>
<given-names>S. S.</given-names>
</name>
<name>
<surname>Eguchi</surname>
<given-names>K.</given-names>
</name>
</person-group> (<year>2021</year>). <article-title>Optimal location of FACTS devices in Order to Simultaneously improving transmission losses and stability Margin using artificial Bee Colony algorithm</article-title>. <source>IEEE Access</source> <volume>9</volume>, <fpage>125920</fpage>&#x2013;<lpage>125929</lpage>. <pub-id pub-id-type="doi">10.1109/ACCESS.2021.3108687</pub-id>
</citation>
</ref>
<ref id="B17">
<citation citation-type="journal">
<person-group person-group-type="author">
<name>
<surname>Khatibi</surname>
<given-names>M.</given-names>
</name>
<name>
<surname>Bigdeli</surname>
<given-names>M.</given-names>
</name>
</person-group> (<year>2014</year>). <article-title>Transient stability improvement of power systems by optimal sizing and allocation of resistive superconducting fault current limiters using Particle</article-title>. <source>Swarm Optim.</source> <volume>1</volume> (<issue>3</issue>), <fpage>17</fpage>.</citation>
</ref>
<ref id="B18">
<citation citation-type="confproc">
<person-group person-group-type="author">
<name>
<surname>Kodle</surname>
<given-names>S.</given-names>
</name>
<name>
<surname>Padmini</surname>
<given-names>V.</given-names>
</name>
<name>
<surname>Bahirat</surname>
<given-names>H. J.</given-names>
</name>
<name>
<surname>Khaparde</surname>
<given-names>S. A.</given-names>
</name>
<name>
<surname>Lubicki</surname>
<given-names>P.</given-names>
</name>
<name>
<surname>Dabeer</surname>
<given-names>V.</given-names>
</name>
</person-group> (<year>2016</year>). &#x201c;<article-title>Application of Super Conducting fault current limiter in Indian grid</article-title>,&#x201d; in <conf-name>2016 IEEE 6th International Conference on Power Systems (ICPS)</conf-name>, <conf-loc>New Delhi, India</conf-loc>, <conf-date>March 2016</conf-date> (<publisher-name>IEEE</publisher-name>), <fpage>1</fpage>&#x2013;<lpage>6</lpage>. <pub-id pub-id-type="doi">10.1109/ICPES.2016.7584226</pub-id>
</citation>
</ref>
<ref id="B19">
<citation citation-type="journal">
<person-group person-group-type="author">
<name>
<surname>Kovalsky</surname>
<given-names>L.</given-names>
</name>
<name>
<surname>Xing</surname>
<given-names>Y.</given-names>
</name>
<name>
<surname>Tekletsadik</surname>
<given-names>K.</given-names>
</name>
<name>
<surname>Keri</surname>
<given-names>A.</given-names>
</name>
<name>
<surname>Bock</surname>
<given-names>J.</given-names>
</name>
<name>
<surname>Breuer</surname>
<given-names>F.</given-names>
</name>
</person-group> (<year>2005</year>). <article-title>Applications of superconducting fault current limiters in electric power transmission systems</article-title>. <source>IEEE Trans. Appl. Supercond.</source> <volume>15</volume> (<issue>2</issue>), <fpage>2130</fpage>&#x2013;<lpage>2133</lpage>. <pub-id pub-id-type="doi">10.1109/TASC.2005.849471</pub-id>
</citation>
</ref>
<ref id="B20">
<citation citation-type="journal">
<person-group person-group-type="author">
<name>
<surname>Koyama</surname>
<given-names>T.</given-names>
</name>
<name>
<surname>Yanabu</surname>
<given-names>S.</given-names>
</name>
</person-group> (<year>2009</year>). <article-title>Study and development of superconducting fault current limiter with high speed Reclosing</article-title>. <source>IEEE Trans. Appl. Supercond.</source> <volume>19</volume> (<issue>3</issue>), <fpage>1868</fpage>&#x2013;<lpage>1871</lpage>. <pub-id pub-id-type="doi">10.1109/TASC.2009.2018783</pub-id>
</citation>
</ref>
<ref id="B21">
<citation citation-type="journal">
<person-group person-group-type="author">
<name>
<surname>Kumar</surname>
<given-names>A.</given-names>
</name>
<name>
<surname>Verma</surname>
<given-names>N.</given-names>
</name>
<name>
<surname>Kumari</surname>
<given-names>S. K.</given-names>
</name>
</person-group> (<year>2016</year>). <article-title>Application of superconducting fault current limiter in single phase system using Simulink</article-title>. <source>Imperial J. Interdiscip. Res.</source> <volume>2</volume> (<issue>8</issue>). <comment>Available at: <ext-link ext-link-type="uri" xlink:href="http://www.imperialjournals.com/index.php/IJIR/article/view/1563">http://www.imperialjournals.com/index.php/IJIR/article/view/1563</ext-link> (Accessed 25, 06, 2019)</comment>.</citation>
</ref>
<ref id="B22">
<citation citation-type="journal">
<person-group person-group-type="author">
<name>
<surname>Kundur</surname>
<given-names>P.</given-names>
</name>
<name>
<surname>Paserba</surname>
<given-names>J.</given-names>
</name>
<name>
<surname>Ajjarapu</surname>
<given-names>V.</given-names>
</name>
<name>
<surname>Andersson</surname>
<given-names>G.</given-names>
</name>
<name>
<surname>Bose</surname>
<given-names>A.</given-names>
</name>
<name>
<surname>Canizares</surname>
<given-names>C.</given-names>
</name>
<etal/>
</person-group> (<year>2004</year>). <article-title>Definition and classification of power system stability IEEE/CIGRE joint task force on stability terms and definitions</article-title>. <source>IEEE Trans. Power Syst.</source> <volume>19</volume> (<issue>3</issue>), <fpage>1387</fpage>&#x2013;<lpage>1401</lpage>. <pub-id pub-id-type="doi">10.1109/TPWRS.2004.825981</pub-id>
</citation>
</ref>
<ref id="B23">
<citation citation-type="book">
<person-group person-group-type="author">
<name>
<surname>Kundur</surname>
<given-names>P.</given-names>
</name>
</person-group> (<year>1994</year>). <source>Power system stability and control</source>. <publisher-loc>New York ; London</publisher-loc>: <publisher-name>McGraw-Hill</publisher-name>.</citation>
</ref>
<ref id="B24">
<citation citation-type="journal">
<person-group person-group-type="author">
<name>
<surname>Lee</surname>
<given-names>B. W.</given-names>
</name>
<name>
<surname>Sim</surname>
<given-names>J.</given-names>
</name>
<name>
<surname>Park</surname>
<given-names>K. B.</given-names>
</name>
<name>
<surname>Oh</surname>
<given-names>I. S.</given-names>
</name>
</person-group> (<year>2008</year>). <article-title>Practical application issues of superconducting fault current limiters for electric power systems</article-title>. <source>IEEE Trans. Appl. Supercond.</source> <volume>18</volume> (<issue>2</issue>), <fpage>620</fpage>&#x2013;<lpage>623</lpage>. <pub-id pub-id-type="doi">10.1109/TASC.2008.920784</pub-id>
</citation>
</ref>
<ref id="B25">
<citation citation-type="book">
<person-group person-group-type="author">
<name>
<surname>Lee</surname>
<given-names>G.-J.</given-names>
</name>
</person-group> (<year>2011</year>). &#x201c;<article-title>Superconductivity application in power system</article-title>,&#x201d; in <source>Applications of high-Tc superconductivity</source> (<publisher-loc>London</publisher-loc>: <publisher-name>IntechOpen</publisher-name>). <pub-id pub-id-type="doi">10.5772/16334</pub-id>
</citation>
</ref>
<ref id="B26">
<citation citation-type="journal">
<person-group person-group-type="author">
<name>
<surname>Leiva Roca</surname>
<given-names>D. A.</given-names>
</name>
<name>
<surname>Mercado</surname>
<given-names>P.</given-names>
</name>
<name>
<surname>Suvire</surname>
<given-names>G.</given-names>
</name>
</person-group> (<year>2022</year>). <article-title>System frequency response model considering the influence of power system stabilizers</article-title>. <source>IEEE Lat. Am. Trans.</source> <volume>20</volume> (<issue>6</issue>), <fpage>912</fpage>&#x2013;<lpage>920</lpage>. <pub-id pub-id-type="doi">10.1109/TLA.2022.9757373</pub-id>
</citation>
</ref>
<ref id="B27">
<citation citation-type="journal">
<person-group person-group-type="author">
<name>
<surname>Li</surname>
<given-names>B.</given-names>
</name>
<name>
<surname>Li</surname>
<given-names>C.</given-names>
</name>
<name>
<surname>Guo</surname>
<given-names>F.</given-names>
</name>
<name>
<surname>Xin</surname>
<given-names>Y.</given-names>
</name>
</person-group> (<year>2014</year>). <article-title>Overcurrent protection coordination in a power distribution network with the active superconductive fault current limiter</article-title>. <source>IEEE Trans. Appl. Supercond.</source> <volume>24</volume> (<issue>5</issue>), <fpage>1</fpage>&#x2013;<lpage>4</lpage>. <pub-id pub-id-type="doi">10.1109/TASC.2014.2333811</pub-id>
</citation>
</ref>
<ref id="B28">
<citation citation-type="journal">
<person-group person-group-type="author">
<name>
<surname>Lim</surname>
<given-names>S.</given-names>
</name>
<name>
<surname>Kim</surname>
<given-names>J.-S.</given-names>
</name>
<name>
<surname>Moon</surname>
<given-names>J. F.</given-names>
</name>
<name>
<surname>Kim</surname>
<given-names>J.-C.</given-names>
</name>
<name>
<surname>Rhee</surname>
<given-names>S.-B.</given-names>
</name>
<name>
<surname>Kim</surname>
<given-names>C.-H.</given-names>
</name>
<etal/>
</person-group> (<year>2009</year>). <article-title>Quench and recovery characteristics of a SFCL applied into neutral line of a three-phase power system</article-title>. <source>IEEE Trans. Appl. Supercond.</source> <volume>19</volume> (<issue>3</issue>), <fpage>1835</fpage>&#x2013;<lpage>1838</lpage>. <pub-id pub-id-type="doi">10.1109/TASC.2009.2017754</pub-id>
</citation>
</ref>
<ref id="B29">
<citation citation-type="book">
<person-group person-group-type="author">
<name>
<surname>Machowski</surname>
<given-names>J.</given-names>
</name>
<name>
<surname>Bialek</surname>
<given-names>J.</given-names>
</name>
<name>
<surname>Bumby</surname>
<given-names>D. J.</given-names>
</name>
</person-group> (<year>2008</year>). <source>Power system dynamics: Stability and control</source>. <edition>2nd edition</edition>. <publisher-loc>Chichester, U.K</publisher-loc>: <publisher-name>Wiley-Blackwell</publisher-name>.</citation>
</ref>
<ref id="B30">
<citation citation-type="journal">
<person-group person-group-type="author">
<name>
<surname>Martini</surname>
<given-names>L.</given-names>
</name>
<name>
<surname>Bocchi</surname>
<given-names>M.</given-names>
</name>
<name>
<surname>Ascade</surname>
<given-names>M.</given-names>
</name>
<name>
<surname>Valzasina</surname>
<given-names>A.</given-names>
</name>
<name>
<surname>Rossi</surname>
<given-names>V.</given-names>
</name>
<name>
<surname>Ravetta</surname>
<given-names>C.</given-names>
</name>
<etal/>
</person-group> (<year>2014</year>). <article-title>The first Italian Superconducting Fault Current Limiter: Results of the field testing experience after one year operation</article-title>. <source>J. Phys. Conf. Ser.</source> <volume>507</volume> (<issue>3</issue>), <fpage>032003</fpage>. <pub-id pub-id-type="doi">10.1088/1742-6596/507/3/032003</pub-id>
</citation>
</ref>
<ref id="B31">
<citation citation-type="book">
<person-group person-group-type="author">
<name>
<surname>Matsumoto</surname>
<given-names>K.</given-names>
</name>
</person-group> (<year>2010</year>). &#x201c;<article-title>General theory of high-Tc superconductors</article-title>,&#x201d; in <source>High temperature superconductors</source>. Editors <person-group person-group-type="editor">
<name>
<surname>Bhattacharya</surname>
<given-names>R.</given-names>
</name>
<name>
<surname>Paranthaman</surname>
<given-names>M. P.</given-names>
</name>
</person-group> (<publisher-loc>Weinheim, Germany</publisher-loc>: <publisher-name>Wiley-VCH Verlag GmbH &#x26; Co. KGaA</publisher-name>), <fpage>1</fpage>&#x2013;<lpage>47</lpage>. <pub-id pub-id-type="doi">10.1002/9783527631049.ch1</pub-id>
</citation>
</ref>
<ref id="B32">
<citation citation-type="journal">
<person-group person-group-type="author">
<name>
<surname>Miyashita</surname>
<given-names>M.</given-names>
</name>
<name>
<surname>Umeda</surname>
<given-names>S.</given-names>
</name>
<name>
<surname>Nagao</surname>
<given-names>S.</given-names>
</name>
<name>
<surname>Amemiya</surname>
<given-names>N.</given-names>
</name>
<name>
<surname>Kubota</surname>
<given-names>H.</given-names>
</name>
<name>
<surname>Kudo</surname>
<given-names>Y.</given-names>
</name>
<etal/>
</person-group> (<year>2005</year>). <article-title>Measurement of lateral current redistribution of fault current limiter using YBCO thin film</article-title>. <source>IEEE Trans. Appl. Supercond.</source> <volume>15</volume> (<issue>2</issue>), <fpage>2023</fpage>&#x2013;<lpage>2026</lpage>. <pub-id pub-id-type="doi">10.1109/TASC.2005.849442</pub-id>
</citation>
</ref>
<ref id="B34">
<citation citation-type="confproc">
<person-group person-group-type="author">
<name>
<surname>Mohamed</surname>
<given-names>E.</given-names>
</name>
</person-group> (<year>2012</year>). &#x201c;<article-title>Enhancement of power system transient stability using superconducting fault current limiters with YBCO and Bi-2212</article-title>,&#x201d; in <conf-name>The Middle East Power Systems Conference (MEPCON&#x2019;2012)</conf-name>, <conf-date>December 2012</conf-date> (<publisher-name>MEPCON</publisher-name>).</citation>
</ref>
<ref id="B35">
<citation citation-type="journal">
<person-group person-group-type="author">
<name>
<surname>Moon</surname>
<given-names>J.</given-names>
</name>
<name>
<surname>Lim</surname>
<given-names>S.</given-names>
</name>
<name>
<surname>Kim</surname>
<given-names>J.</given-names>
</name>
<name>
<surname>Yun</surname>
<given-names>S.</given-names>
</name>
</person-group> (<year>2011</year>). <article-title>Assessment of the impact of SFCL on voltage Sags in power distribution system</article-title>. <source>IEEE Trans. Appl. Supercond.</source> <volume>21</volume> (<issue>3</issue>), <fpage>2161</fpage>&#x2013;<lpage>2164</lpage>. <pub-id pub-id-type="doi">10.1109/TASC.2010.2093592</pub-id>
</citation>
</ref>
<ref id="B36">
<citation citation-type="journal">
<person-group person-group-type="author">
<name>
<surname>Noe</surname>
<given-names>M.</given-names>
</name>
<name>
<surname>Steurer</surname>
<given-names>M.</given-names>
</name>
</person-group> (<year>2007</year>). <article-title>High-temperature superconductor fault current limiters: Concepts, applications, and development status</article-title>. <source>Supercond. Sci. Technol.</source> <volume>20</volume> (<issue>3</issue>), <fpage>R15</fpage>&#x2013;<lpage>R29</lpage>. <pub-id pub-id-type="doi">10.1088/0953-2048/20/3/R01</pub-id>
</citation>
</ref>
<ref id="B37">
<citation citation-type="book">
<person-group person-group-type="author">
<name>
<surname>Padiyar</surname>
<given-names>K. R.</given-names>
</name>
</person-group> (<year>2004</year>). <source>Power system dynamics: Stability and control</source>. <publisher-loc>Anshan, China</publisher-loc>: <publisher-name>Wiley</publisher-name>.</citation>
</ref>
<ref id="B38">
<citation citation-type="journal">
<person-group person-group-type="author">
<name>
<surname>Pawar</surname>
<given-names>R.</given-names>
</name>
<name>
<surname>Chavan</surname>
<given-names>P.</given-names>
</name>
</person-group> (<year>2017</year>). <article-title>Minimizing of fault current using SFCL Technology</article-title>. <source>Int. J. of Eng. Dev. Res.</source> <volume>5</volume>, <fpage>1261</fpage>&#x2013;<lpage>1267</lpage>.</citation>
</ref>
<ref id="B39">
<citation citation-type="book">
<person-group person-group-type="author">
<name>
<surname>Ravindranath</surname>
<given-names>B.</given-names>
</name>
<name>
<surname>Chander</surname>
<given-names>M.</given-names>
</name>
</person-group> (<year>1977</year>). <source>Power system protection and switchgear</source>. <publisher-loc>New Delhi,India</publisher-loc>: <publisher-name>New Age</publisher-name>.</citation>
</ref>
<ref id="B40">
<citation citation-type="journal">
<person-group person-group-type="author">
<name>
<surname>Sjostrom</surname>
<given-names>M.</given-names>
</name>
<name>
<surname>Cherkaoui</surname>
<given-names>R.</given-names>
</name>
<name>
<surname>Dutoit</surname>
<given-names>B.</given-names>
</name>
</person-group> (<year>1999</year>). <article-title>Enhancement of power system transient stability using superconducting fault current limiters</article-title>. <source>IEEE Trans. Appl. Supercond.</source> <volume>9</volume> (<issue>2</issue>), <fpage>1328</fpage>&#x2013;<lpage>1330</lpage>. <pub-id pub-id-type="doi">10.1109/77.783547</pub-id>
</citation>
</ref>
<ref id="B41">
<citation citation-type="journal">
<person-group person-group-type="author">
<name>
<surname>Son</surname>
<given-names>G. T.</given-names>
</name>
<name>
<surname>Lee</surname>
<given-names>H.</given-names>
</name>
<name>
<surname>Lee</surname>
<given-names>S.</given-names>
</name>
<name>
<surname>Park</surname>
<given-names>J.</given-names>
</name>
</person-group> (<year>2012</year>). <article-title>A study on the Direct stability analysis of Multi-machine power system with resistive SFCL</article-title>. <source>IEEE Trans. Appl. Supercond.</source> <volume>22</volume> (<issue>3</issue>), <fpage>5602304</fpage>. <pub-id pub-id-type="doi">10.1109/TASC.2011.2177626</pub-id>
</citation>
</ref>
<ref id="B42">
<citation citation-type="journal">
<person-group person-group-type="author">
<name>
<surname>Sung</surname>
<given-names>B. C.</given-names>
</name>
<name>
<surname>Park</surname>
<given-names>D. K.</given-names>
</name>
<name>
<surname>Park</surname>
<given-names>J.</given-names>
</name>
<name>
<surname>Ko</surname>
<given-names>T. K.</given-names>
</name>
</person-group> (<year>2009</year>). <article-title>Study on a series resistive SFCL to improve power system transient stability: Modeling, simulation, and Experimental Verification</article-title>. <source>IEEE Trans. Industrial Electron.</source> <volume>56</volume> (<issue>7</issue>), <fpage>2412</fpage>&#x2013;<lpage>2419</lpage>. <pub-id pub-id-type="doi">10.1109/TIE.2009.2018432</pub-id>
</citation>
</ref>
<ref id="B43">
<citation citation-type="journal">
<person-group person-group-type="author">
<name>
<surname>Vojen&#x10d;iak</surname>
<given-names>M.</given-names>
</name>
<name>
<surname>Dutoit</surname>
<given-names>B.</given-names>
</name>
<name>
<surname>&#x160;ouc</surname>
<given-names>J.</given-names>
</name>
<name>
<surname>G&#xf6;m&#xf6;ry</surname>
<given-names>F.</given-names>
</name>
</person-group> (<year>2016</year>). <article-title>Can resistive-type fault current limiter operate in Cryogen-Free Environment?</article-title> <source>IEEE Trans. Appl. Supercond.</source> <volume>26</volume> (<issue>3</issue>), <fpage>1</fpage>&#x2013;<lpage>4</lpage>. <pub-id pub-id-type="doi">10.1109/TASC.2016.2535175</pub-id>
</citation>
</ref>
<ref id="B44">
<citation citation-type="journal">
<person-group person-group-type="author">
<name>
<surname>Wang</surname>
<given-names>H.</given-names>
</name>
<name>
<surname>Zhang</surname>
<given-names>J.</given-names>
</name>
<name>
<surname>Niu</surname>
<given-names>X.</given-names>
</name>
<name>
<surname>Tian</surname>
<given-names>B.</given-names>
</name>
<name>
<surname>Hong</surname>
<given-names>H.</given-names>
</name>
<name>
<surname>Xin</surname>
<given-names>Y.</given-names>
</name>
</person-group> (<year>2014</year>). <article-title>Electrical Insulation of HTS coils in saturated iron core superconducting fault current limiter</article-title>. <source>IEEE Trans. Appl. Supercond.</source> <volume>24</volume> (<issue>3</issue>), <fpage>1</fpage>&#x2013;<lpage>4</lpage>. <pub-id pub-id-type="doi">10.1109/TASC.2013.2290944</pub-id>
</citation>
</ref>
<ref id="B45">
<citation citation-type="journal">
<person-group person-group-type="author">
<name>
<surname>Wang</surname>
<given-names>M. H.</given-names>
</name>
<name>
<surname>He</surname>
<given-names>Y. F.</given-names>
</name>
<name>
<surname>Yang</surname>
<given-names>T. B.</given-names>
</name>
<name>
<surname>Jia</surname>
<given-names>Y.</given-names>
</name>
<name>
<surname>Xu</surname>
<given-names>Z.</given-names>
</name>
</person-group> (<year>2020</year>). <article-title>Cascaded voltage control for electric Springs with DC-Link film capacitors</article-title>. <source>IEEE J. Emerg. Sel. Top. Power Electron.</source> <volume>8</volume> (<issue>4</issue>), <fpage>3982</fpage>&#x2013;<lpage>3994</lpage>. <pub-id pub-id-type="doi">10.1109/jestpe.2019.2962238</pub-id>
</citation>
</ref>
<ref id="B46">
<citation citation-type="journal">
<person-group person-group-type="author">
<name>
<surname>Wang</surname>
<given-names>M. H.</given-names>
</name>
<name>
<surname>Mok</surname>
<given-names>K. T.</given-names>
</name>
<name>
<surname>Tan</surname>
<given-names>S. C.</given-names>
</name>
<name>
<surname>Hui</surname>
<given-names>S. Y. R.</given-names>
</name>
</person-group> (<year>2018</year>). <article-title>Multifunctional DC electric Springs for improving voltage Quality of DC grids</article-title>. <source>IEEE Trans. Smart Grid</source> <volume>9</volume> (<issue>3</issue>), <fpage>2248</fpage>&#x2013;<lpage>2258</lpage>.</citation>
</ref>
<ref id="B47">
<citation citation-type="journal">
<person-group person-group-type="author">
<name>
<surname>Wang</surname>
<given-names>M. H.</given-names>
</name>
<name>
<surname>Yan</surname>
<given-names>S.</given-names>
</name>
<name>
<surname>Tan</surname>
<given-names>S. C.</given-names>
</name>
<name>
<surname>Hui</surname>
<given-names>S. Y. R.</given-names>
</name>
</person-group> (<year>2018</year>). <article-title>Hybrid-DC electric Springs for DC voltage regulation and Harmonic Cancellation in DC Microgrids</article-title>. <source>IEEE Trans. Power Electron.</source> <volume>33</volume> (<issue>2</issue>), <fpage>1167</fpage>&#x2013;<lpage>1177</lpage>. <pub-id pub-id-type="doi">10.1109/tpel.2017.2681120</pub-id>
</citation>
</ref>
<ref id="B48">
<citation citation-type="journal">
<person-group person-group-type="author">
<name>
<surname>Wang</surname>
<given-names>M. H.</given-names>
</name>
<name>
<surname>Yang</surname>
<given-names>T. B.</given-names>
</name>
<name>
<surname>Tan</surname>
<given-names>S. C.</given-names>
</name>
<name>
<surname>Hui</surname>
<given-names>S. Y. R.</given-names>
</name>
</person-group> (<year>2019</year>). <article-title>Hybrid electric Springs for grid-tied power control and Storage Reduction in AC Microgrids</article-title>. <source>IEEE Trans. Power Electron.</source> <volume>34</volume> (<issue>4</issue>), <fpage>3214</fpage>&#x2013;<lpage>3225</lpage>. <pub-id pub-id-type="doi">10.1109/tpel.2018.2854569</pub-id>
</citation>
</ref>
<ref id="B49">
<citation citation-type="journal">
<person-group person-group-type="author">
<name>
<surname>Yang</surname>
<given-names>Q.</given-names>
</name>
<name>
<surname>Blond</surname>
<given-names>S. L.</given-names>
</name>
<name>
<surname>Liang</surname>
<given-names>F.</given-names>
</name>
<name>
<surname>Yuan</surname>
<given-names>W.</given-names>
</name>
<name>
<surname>Zhang</surname>
<given-names>M.</given-names>
</name>
<name>
<surname>Li</surname>
<given-names>J.</given-names>
</name>
</person-group> (<year>2017</year>). <article-title>Design and application of superconducting fault current limiter in a Multiterminal HVDC system</article-title>. <source>IEEE Trans. Appl. Supercond.</source> <volume>27</volume> (<issue>4</issue>), <fpage>1</fpage>&#x2013;<lpage>5</lpage>. <pub-id pub-id-type="doi">10.1109/TASC.2017.2669152</pub-id>
</citation>
</ref>
<ref id="B50">
<citation citation-type="journal">
<person-group person-group-type="author">
<name>
<surname>Yonemura</surname>
<given-names>N.</given-names>
</name>
<name>
<surname>Yamabe</surname>
<given-names>K.</given-names>
</name>
<name>
<surname>Shirai</surname>
<given-names>Y.</given-names>
</name>
<name>
<surname>Kobayashi</surname>
<given-names>S.</given-names>
</name>
<name>
<surname>Nagaishi</surname>
<given-names>T.</given-names>
</name>
<name>
<surname>Konishi</surname>
<given-names>M.</given-names>
</name>
</person-group> (<year>2015</year>). <article-title>Current limiting performance of transformer-type superconducting fault current limiter made of BSCCO and REBCO Wires</article-title>. <source>IEEE Trans. Appl. Supercond.</source> <volume>25</volume> (<issue>3</issue>), <fpage>1</fpage>&#x2013;<lpage>4</lpage>. <pub-id pub-id-type="doi">10.1109/TASC.2014.2377126</pub-id>
</citation>
</ref>
<ref id="B51">
<citation citation-type="web">
<person-group person-group-type="author">
<name>
<surname>Zhang</surname>
<given-names>X.</given-names>
</name>
<name>
<surname>Ruiz</surname>
<given-names>H. S.</given-names>
</name>
<name>
<surname>Zhong</surname>
<given-names>Z.</given-names>
</name>
<name>
<surname>Coombs</surname>
<given-names>T. A.</given-names>
</name>
</person-group> (<year>2015</year>). <article-title>Implementation of resistive type superconducting fault current limiters in electrical grids: Performance analysis and measuring of optimal locations</article-title>. <comment>Available at: <ext-link ext-link-type="uri" xlink:href="http://arxiv.org/abs/1508.01162">http://arxiv.org/abs/1508.01162</ext-link> (Accessed 18, 06, 2019)</comment>.</citation>
</ref>
<ref id="B52">
<citation citation-type="journal">
<person-group person-group-type="author">
<name>
<surname>Zheng</surname>
<given-names>W.</given-names>
</name>
<name>
<surname>Zhu</surname>
<given-names>J.</given-names>
</name>
<name>
<surname>Luo</surname>
<given-names>Q.</given-names>
</name>
</person-group> (<year>2022</year>). <article-title>Distributed Dispatch of Integrated Electricity-Heat Systems with Variable Mass Flow</article-title>. <source>IEEE Transactions Smart Grid</source>. <pub-id pub-id-type="doi">10.1109/TSG.2022.3210014</pub-id>
</citation>
</ref>
</ref-list>
<app-group>
<app id="app1">
<title>Appendix A1:</title>
<p>The generator parameters used in <xref ref-type="fig" rid="F4">Figure 4</xref> (the studied system) in per unit are as follows:</p>
<table-wrap id="T3" position="float">
<table>
<tbody valign="top">
<tr>
<td align="left">
<inline-formula id="inf16">
<mml:math id="m22">
<mml:mrow>
<mml:msub>
<mml:mi>X</mml:mi>
<mml:mi>d</mml:mi>
</mml:msub>
<mml:mo>&#x3d;</mml:mo>
<mml:mn>1.8</mml:mn>
</mml:mrow>
</mml:math>
</inline-formula>
</td>
<td align="left">
<inline-formula id="inf17">
<mml:math id="m23">
<mml:mrow>
<mml:msub>
<mml:mi>X</mml:mi>
<mml:mi>q</mml:mi>
</mml:msub>
<mml:mo>&#x3d;</mml:mo>
<mml:mn>1.7</mml:mn>
</mml:mrow>
</mml:math>
</inline-formula>
</td>
<td align="left">
<inline-formula id="inf18">
<mml:math id="m24">
<mml:mrow>
<mml:msub>
<mml:mi>X</mml:mi>
<mml:mi>l</mml:mi>
</mml:msub>
<mml:mo>&#x3d;</mml:mo>
<mml:mn>0.2</mml:mn>
</mml:mrow>
</mml:math>
</inline-formula>
</td>
<td align="left">
<inline-formula id="inf19">
<mml:math id="m25">
<mml:mrow>
<mml:msubsup>
<mml:mi>X</mml:mi>
<mml:mi>d</mml:mi>
<mml:mo>&#x2032;</mml:mo>
</mml:msubsup>
<mml:mo>&#x3d;</mml:mo>
<mml:mn>0.3</mml:mn>
</mml:mrow>
</mml:math>
</inline-formula>
</td>
<td align="left">
<inline-formula id="inf20">
<mml:math id="m26">
<mml:mrow>
<mml:msubsup>
<mml:mi>X</mml:mi>
<mml:mi>q</mml:mi>
<mml:mo>&#x2032;</mml:mo>
</mml:msubsup>
<mml:mo>&#x3d;</mml:mo>
<mml:mn>0.55</mml:mn>
</mml:mrow>
</mml:math>
</inline-formula>
</td>
</tr>
<tr>
<td align="left">
<inline-formula id="inf21">
<mml:math id="m27">
<mml:mrow>
<mml:msubsup>
<mml:mi>X</mml:mi>
<mml:mi>d</mml:mi>
<mml:mo>&#x2033;</mml:mo>
</mml:msubsup>
<mml:mo>&#x3d;</mml:mo>
<mml:mn>0.25</mml:mn>
</mml:mrow>
</mml:math>
</inline-formula>
</td>
<td align="left">
<inline-formula id="inf22">
<mml:math id="m28">
<mml:mrow>
<mml:msubsup>
<mml:mi>X</mml:mi>
<mml:mi>q</mml:mi>
<mml:mo>&#x2033;</mml:mo>
</mml:msubsup>
<mml:mo>&#x3d;</mml:mo>
<mml:mn>0.25</mml:mn>
</mml:mrow>
</mml:math>
</inline-formula>
</td>
<td align="left">
<inline-formula id="inf23">
<mml:math id="m29">
<mml:mrow>
<mml:msub>
<mml:mi>R</mml:mi>
<mml:mi>a</mml:mi>
</mml:msub>
<mml:mo>&#x3d;</mml:mo>
<mml:mn>0.0025</mml:mn>
</mml:mrow>
</mml:math>
</inline-formula>
</td>
<td align="left">
<inline-formula id="inf24">
<mml:math id="m30">
<mml:mrow>
<mml:msubsup>
<mml:mi>T</mml:mi>
<mml:mrow>
<mml:mi>d</mml:mi>
<mml:mn>0</mml:mn>
</mml:mrow>
<mml:mo>&#x2032;</mml:mo>
</mml:msubsup>
<mml:mo>&#x3d;</mml:mo>
<mml:mn>8</mml:mn>
<mml:mi>s</mml:mi>
</mml:mrow>
</mml:math>
</inline-formula>
</td>
<td align="left">
<inline-formula id="inf25">
<mml:math id="m31">
<mml:mrow>
<mml:msubsup>
<mml:mi>T</mml:mi>
<mml:mrow>
<mml:mi>q</mml:mi>
<mml:mn>0</mml:mn>
</mml:mrow>
<mml:mo>&#x2032;</mml:mo>
</mml:msubsup>
<mml:mo>&#x3d;</mml:mo>
<mml:mn>0.4</mml:mn>
<mml:mi>s</mml:mi>
</mml:mrow>
</mml:math>
</inline-formula>
</td>
</tr>
<tr>
<td align="left">
<inline-formula id="inf26">
<mml:math id="m32">
<mml:mrow>
<mml:msubsup>
<mml:mi>T</mml:mi>
<mml:mrow>
<mml:mi>d</mml:mi>
<mml:mn>0</mml:mn>
</mml:mrow>
<mml:mo>&#x2033;</mml:mo>
</mml:msubsup>
<mml:mo>&#x3d;</mml:mo>
<mml:mn>0.03</mml:mn>
<mml:mi>s</mml:mi>
</mml:mrow>
</mml:math>
</inline-formula>
</td>
<td align="left">
<inline-formula id="inf27">
<mml:math id="m33">
<mml:mrow>
<mml:msubsup>
<mml:mi>T</mml:mi>
<mml:mrow>
<mml:mi>q</mml:mi>
<mml:mn>0</mml:mn>
</mml:mrow>
<mml:mo>&#x2033;</mml:mo>
</mml:msubsup>
<mml:mo>&#x3d;</mml:mo>
<mml:mn>0.05</mml:mn>
<mml:mi>s</mml:mi>
</mml:mrow>
</mml:math>
</inline-formula>
</td>
<td align="left">
<inline-formula id="inf28">
<mml:math id="m34">
<mml:mrow>
<mml:msub>
<mml:mi>A</mml:mi>
<mml:mrow>
<mml:mi>S</mml:mi>
<mml:mi>a</mml:mi>
<mml:mi>t</mml:mi>
</mml:mrow>
</mml:msub>
<mml:mo>&#x3d;</mml:mo>
<mml:mn>0.015</mml:mn>
</mml:mrow>
</mml:math>
</inline-formula>
</td>
<td align="left">
<inline-formula id="inf29">
<mml:math id="m35">
<mml:mrow>
<mml:msub>
<mml:mi>B</mml:mi>
<mml:mrow>
<mml:mi>S</mml:mi>
<mml:mi>a</mml:mi>
<mml:mi>t</mml:mi>
</mml:mrow>
</mml:msub>
<mml:mo>&#x3d;</mml:mo>
<mml:mn>9.6</mml:mn>
</mml:mrow>
</mml:math>
</inline-formula>
</td>
<td align="left">
<inline-formula id="inf30">
<mml:math id="m36">
<mml:mrow>
<mml:msub>
<mml:mi>&#x3a8;</mml:mi>
<mml:mrow>
<mml:mi>T</mml:mi>
<mml:mn>1</mml:mn>
</mml:mrow>
</mml:msub>
<mml:mo>&#x3d;</mml:mo>
<mml:mn>0.9</mml:mn>
</mml:mrow>
</mml:math>
</inline-formula>
</td>
</tr>
<tr>
<td colspan="2" align="left">
<inline-formula id="inf31">
<mml:math id="m37">
<mml:mrow>
<mml:mi>H</mml:mi>
<mml:mo>&#x3d;</mml:mo>
<mml:mn>6.5</mml:mn>
</mml:mrow>
</mml:math>
</inline-formula> (for G1 and G2)</td>
<td colspan="2" align="left">
<inline-formula id="inf32">
<mml:math id="m38">
<mml:mrow>
<mml:mi>H</mml:mi>
<mml:mo>&#x3d;</mml:mo>
<mml:mn>6.175</mml:mn>
</mml:mrow>
</mml:math>
</inline-formula> (for G3 and G4)</td>
<td align="left">
<inline-formula id="inf33">
<mml:math id="m39">
<mml:mrow>
<mml:msub>
<mml:mi>K</mml:mi>
<mml:mi>D</mml:mi>
</mml:msub>
<mml:mo>&#x3d;</mml:mo>
<mml:mn>0</mml:mn>
</mml:mrow>
</mml:math>
</inline-formula>
</td>
</tr>
</tbody>
</table>
</table-wrap>
<p>Each step-up transformer has an impedance of <inline-formula id="inf34">
<mml:math id="m40">
<mml:mrow>
<mml:mn>0</mml:mn>
<mml:mo>&#x2b;</mml:mo>
<mml:mi>j</mml:mi>
<mml:mn>0.15</mml:mn>
<mml:mtext>&#xa0;</mml:mtext>
<mml:mi>p</mml:mi>
<mml:mi>u</mml:mi>
</mml:mrow>
</mml:math>
</inline-formula>, and the lines parameters in per unit.</p>
<table-wrap id="T4" position="float">
<table>
<tbody valign="top">
<tr>
<td align="left">
<inline-formula id="inf35">
<mml:math id="m41">
<mml:mrow>
<mml:mi>r</mml:mi>
<mml:mo>&#x3d;</mml:mo>
<mml:mn>0.0001</mml:mn>
<mml:mtext>&#xa0;</mml:mtext>
<mml:mi>p</mml:mi>
<mml:mi>u</mml:mi>
<mml:mo>/</mml:mo>
<mml:mi>k</mml:mi>
<mml:mi>m</mml:mi>
</mml:mrow>
</mml:math>
</inline-formula>
</td>
<td align="left">
<inline-formula id="inf36">
<mml:math id="m42">
<mml:mrow>
<mml:msub>
<mml:mi>x</mml:mi>
<mml:mi>L</mml:mi>
</mml:msub>
<mml:mo>&#x3d;</mml:mo>
<mml:mn>0.001</mml:mn>
<mml:mtext>&#xa0;</mml:mtext>
<mml:mi>p</mml:mi>
<mml:mi>u</mml:mi>
<mml:mo>/</mml:mo>
<mml:mi>k</mml:mi>
<mml:mi>m</mml:mi>
</mml:mrow>
</mml:math>
</inline-formula>
</td>
<td align="left">
<inline-formula id="inf37">
<mml:math id="m43">
<mml:mrow>
<mml:msub>
<mml:mi>b</mml:mi>
<mml:mi>c</mml:mi>
</mml:msub>
<mml:mo>&#x3d;</mml:mo>
<mml:mn>0.00175</mml:mn>
<mml:mtext>&#xa0;</mml:mtext>
<mml:mi>p</mml:mi>
<mml:mi>u</mml:mi>
<mml:mo>/</mml:mo>
<mml:mi>k</mml:mi>
<mml:mi>m</mml:mi>
</mml:mrow>
</mml:math>
</inline-formula>
</td>
</tr>
</tbody>
</table>
</table-wrap>
<p>The generating units loaded as follows:</p>
<table-wrap id="T5" position="float">
<table>
<tbody valign="top">
<tr>
<td align="left">
<inline-formula id="inf38">
<mml:math id="m44">
<mml:mrow>
<mml:mi>G</mml:mi>
<mml:mn>1</mml:mn>
<mml:mo>:</mml:mo>
</mml:mrow>
</mml:math>
</inline-formula>
</td>
<td align="left">
<inline-formula id="inf39">
<mml:math id="m45">
<mml:mrow>
<mml:mi>P</mml:mi>
<mml:mo>&#x3d;</mml:mo>
<mml:mn>700</mml:mn>
<mml:mtext>&#xa0;</mml:mtext>
<mml:mi>M</mml:mi>
<mml:mi>W</mml:mi>
</mml:mrow>
</mml:math>
</inline-formula>
</td>
<td align="left">
<inline-formula id="inf40">
<mml:math id="m46">
<mml:mrow>
<mml:mi>Q</mml:mi>
<mml:mo>&#x3d;</mml:mo>
<mml:mn>185</mml:mn>
<mml:mtext>&#xa0;</mml:mtext>
<mml:mi>M</mml:mi>
<mml:mi>V</mml:mi>
<mml:mi>a</mml:mi>
<mml:mi>r</mml:mi>
</mml:mrow>
</mml:math>
</inline-formula>
</td>
<td align="left">
<inline-formula id="inf41">
<mml:math id="m47">
<mml:mrow>
<mml:msub>
<mml:mi>E</mml:mi>
<mml:mi>t</mml:mi>
</mml:msub>
<mml:mo>&#x3d;</mml:mo>
<mml:mn>1.03</mml:mn>
<mml:mo>&#x2220;</mml:mo>
<mml:mn>20</mml:mn>
<mml:mo>.</mml:mo>
<mml:msup>
<mml:mn>2</mml:mn>
<mml:mi>o</mml:mi>
</mml:msup>
</mml:mrow>
</mml:math>
</inline-formula>
</td>
</tr>
<tr>
<td align="left">
<inline-formula id="inf42">
<mml:math id="m48">
<mml:mrow>
<mml:mi>G</mml:mi>
<mml:mn>2</mml:mn>
<mml:mo>:</mml:mo>
</mml:mrow>
</mml:math>
</inline-formula>
</td>
<td align="left">
<inline-formula id="inf43">
<mml:math id="m49">
<mml:mrow>
<mml:mi>P</mml:mi>
<mml:mo>&#x3d;</mml:mo>
<mml:mn>700</mml:mn>
<mml:mi>M</mml:mi>
<mml:mi>W</mml:mi>
</mml:mrow>
</mml:math>
</inline-formula>
</td>
<td align="left">
<inline-formula id="inf44">
<mml:math id="m50">
<mml:mrow>
<mml:mi>Q</mml:mi>
<mml:mo>&#x3d;</mml:mo>
<mml:mn>235</mml:mn>
<mml:mtext>&#xa0;</mml:mtext>
<mml:mi>M</mml:mi>
<mml:mi>V</mml:mi>
<mml:mi>a</mml:mi>
<mml:mi>r</mml:mi>
</mml:mrow>
</mml:math>
</inline-formula>
</td>
<td align="left">
<inline-formula id="inf45">
<mml:math id="m51">
<mml:mrow>
<mml:msub>
<mml:mi>E</mml:mi>
<mml:mi>t</mml:mi>
</mml:msub>
<mml:mo>&#x3d;</mml:mo>
<mml:mn>1.01</mml:mn>
<mml:mo>&#x2220;</mml:mo>
<mml:mn>10</mml:mn>
<mml:mo>.</mml:mo>
<mml:msup>
<mml:mn>5</mml:mn>
<mml:mi>o</mml:mi>
</mml:msup>
</mml:mrow>
</mml:math>
</inline-formula>
</td>
</tr>
<tr>
<td align="left">
<inline-formula id="inf46">
<mml:math id="m52">
<mml:mrow>
<mml:mi>G</mml:mi>
<mml:mn>3</mml:mn>
<mml:mo>:</mml:mo>
</mml:mrow>
</mml:math>
</inline-formula>
</td>
<td align="left">
<inline-formula id="inf47">
<mml:math id="m53">
<mml:mrow>
<mml:mi>P</mml:mi>
<mml:mo>&#x3d;</mml:mo>
<mml:mn>719</mml:mn>
<mml:mi>M</mml:mi>
<mml:mi>W</mml:mi>
</mml:mrow>
</mml:math>
</inline-formula>
</td>
<td align="left">
<inline-formula id="inf48">
<mml:math id="m54">
<mml:mrow>
<mml:mi>Q</mml:mi>
<mml:mo>&#x3d;</mml:mo>
<mml:mn>176</mml:mn>
<mml:mtext>&#xa0;</mml:mtext>
<mml:mi>M</mml:mi>
<mml:mi>V</mml:mi>
<mml:mi>a</mml:mi>
<mml:mi>r</mml:mi>
</mml:mrow>
</mml:math>
</inline-formula>
</td>
<td align="left">
<inline-formula id="inf49">
<mml:math id="m55">
<mml:mrow>
<mml:msub>
<mml:mi>E</mml:mi>
<mml:mi>t</mml:mi>
</mml:msub>
<mml:mo>&#x3d;</mml:mo>
<mml:mn>1.03</mml:mn>
<mml:mo>&#x2220;</mml:mo>
<mml:mo>&#x2212;</mml:mo>
<mml:mn>6</mml:mn>
<mml:mo>.</mml:mo>
<mml:msup>
<mml:mn>8</mml:mn>
<mml:mi>o</mml:mi>
</mml:msup>
</mml:mrow>
</mml:math>
</inline-formula>
</td>
</tr>
<tr>
<td align="left">
<inline-formula id="inf50">
<mml:math id="m56">
<mml:mrow>
<mml:mi>G</mml:mi>
<mml:mn>4</mml:mn>
<mml:mo>:</mml:mo>
</mml:mrow>
</mml:math>
</inline-formula>
</td>
<td align="left">
<inline-formula id="inf51">
<mml:math id="m57">
<mml:mrow>
<mml:mi>P</mml:mi>
<mml:mo>&#x3d;</mml:mo>
<mml:mn>700</mml:mn>
<mml:mi>M</mml:mi>
<mml:mi>W</mml:mi>
</mml:mrow>
</mml:math>
</inline-formula>
</td>
<td align="left">
<inline-formula id="inf52">
<mml:math id="m58">
<mml:mrow>
<mml:mi>Q</mml:mi>
<mml:mo>&#x3d;</mml:mo>
<mml:mn>202</mml:mn>
<mml:mtext>&#xa0;</mml:mtext>
<mml:mi>M</mml:mi>
<mml:mi>V</mml:mi>
<mml:mi>a</mml:mi>
<mml:mi>r</mml:mi>
</mml:mrow>
</mml:math>
</inline-formula>
</td>
<td align="left">
<inline-formula id="inf53">
<mml:math id="m59">
<mml:mrow>
<mml:msub>
<mml:mi>E</mml:mi>
<mml:mi>t</mml:mi>
</mml:msub>
<mml:mo>&#x3d;</mml:mo>
<mml:mn>1.01</mml:mn>
<mml:mo>&#x2220;</mml:mo>
<mml:mo>&#x2212;</mml:mo>
<mml:msup>
<mml:mn>17</mml:mn>
<mml:mi>o</mml:mi>
</mml:msup>
</mml:mrow>
</mml:math>
</inline-formula>
</td>
</tr>
</tbody>
</table>
</table-wrap>
<p>Loads and reactive power supplied by shunt capacitor at bus 7 and bus 9 are as follows:</p>
<table-wrap id="T6" position="float">
<table>
<tbody valign="top">
<tr>
<td align="left">
<inline-formula id="inf54">
<mml:math id="m60">
<mml:mrow>
<mml:mi>B</mml:mi>
<mml:mi>u</mml:mi>
<mml:mi>s</mml:mi>
<mml:mtext>&#xa0;</mml:mtext>
<mml:mn>7</mml:mn>
<mml:mo>:</mml:mo>
</mml:mrow>
</mml:math>
</inline-formula>
</td>
<td align="left">
<inline-formula id="inf55">
<mml:math id="m61">
<mml:mrow>
<mml:msub>
<mml:mi>P</mml:mi>
<mml:mi>L</mml:mi>
</mml:msub>
<mml:mo>&#x3d;</mml:mo>
<mml:mn>967</mml:mn>
<mml:mi>M</mml:mi>
<mml:mi>W</mml:mi>
</mml:mrow>
</mml:math>
</inline-formula>
</td>
<td align="left">
<inline-formula id="inf56">
<mml:math id="m62">
<mml:mrow>
<mml:msub>
<mml:mi>Q</mml:mi>
<mml:mi>L</mml:mi>
</mml:msub>
<mml:mo>&#x3d;</mml:mo>
<mml:mn>100</mml:mn>
<mml:mtext>&#xa0;</mml:mtext>
<mml:mi>M</mml:mi>
<mml:mi>V</mml:mi>
<mml:mi>a</mml:mi>
<mml:mi>r</mml:mi>
</mml:mrow>
</mml:math>
</inline-formula>
</td>
<td align="left">
<inline-formula id="inf57">
<mml:math id="m63">
<mml:mrow>
<mml:msub>
<mml:mi>Q</mml:mi>
<mml:mi>C</mml:mi>
</mml:msub>
<mml:mo>&#x3d;</mml:mo>
<mml:mn>200</mml:mn>
<mml:mtext>&#xa0;</mml:mtext>
<mml:mi>M</mml:mi>
<mml:mi>V</mml:mi>
<mml:mi>a</mml:mi>
<mml:mi>r</mml:mi>
</mml:mrow>
</mml:math>
</inline-formula>
</td>
</tr>
<tr>
<td align="left">
<inline-formula id="inf58">
<mml:math id="m64">
<mml:mrow>
<mml:mi>B</mml:mi>
<mml:mi>u</mml:mi>
<mml:mi>s</mml:mi>
<mml:mtext>&#xa0;</mml:mtext>
<mml:mn>9</mml:mn>
<mml:mo>:</mml:mo>
</mml:mrow>
</mml:math>
</inline-formula>
</td>
<td align="left">
<inline-formula id="inf59">
<mml:math id="m65">
<mml:mrow>
<mml:msub>
<mml:mi>P</mml:mi>
<mml:mi>L</mml:mi>
</mml:msub>
<mml:mo>&#x3d;</mml:mo>
<mml:mn>1767</mml:mn>
<mml:mi>M</mml:mi>
<mml:mi>W</mml:mi>
</mml:mrow>
</mml:math>
</inline-formula>
</td>
<td align="left">
<inline-formula id="inf60">
<mml:math id="m66">
<mml:mrow>
<mml:msub>
<mml:mi>Q</mml:mi>
<mml:mi>L</mml:mi>
</mml:msub>
<mml:mo>&#x3d;</mml:mo>
<mml:mn>100</mml:mn>
<mml:mtext>&#xa0;</mml:mtext>
<mml:mi>M</mml:mi>
<mml:mi>V</mml:mi>
<mml:mi>a</mml:mi>
<mml:mi>r</mml:mi>
</mml:mrow>
</mml:math>
</inline-formula>
</td>
<td align="left">
<inline-formula id="inf61">
<mml:math id="m67">
<mml:mrow>
<mml:msub>
<mml:mi>Q</mml:mi>
<mml:mi>C</mml:mi>
</mml:msub>
<mml:mo>&#x3d;</mml:mo>
<mml:mn>350</mml:mn>
<mml:mtext>&#xa0;</mml:mtext>
<mml:mi>M</mml:mi>
<mml:mi>V</mml:mi>
<mml:mi>a</mml:mi>
<mml:mi>r</mml:mi>
</mml:mrow>
</mml:math>
</inline-formula>
</td>
</tr>
</tbody>
</table>
</table-wrap>
</app>
</app-group>
</back>
</article>