<?xml version="1.0" encoding="UTF-8" standalone="no"?>
<!DOCTYPE article PUBLIC "-//NLM//DTD Journal Publishing DTD v2.3 20070202//EN" "journalpublishing.dtd">
<article xmlns:mml="http://www.w3.org/1998/Math/MathML" xmlns:xlink="http://www.w3.org/1999/xlink" article-type="research-article">
<front>
<journal-meta>
<journal-id journal-id-type="publisher-id">Front. Energy Res.</journal-id>
<journal-title>Frontiers in Energy Research</journal-title>
<abbrev-journal-title abbrev-type="pubmed">Front. Energy Res.</abbrev-journal-title>
<issn pub-type="epub">2296-598X</issn>
<publisher>
<publisher-name>Frontiers Media S.A.</publisher-name>
</publisher>
</journal-meta>
<article-meta>
<article-id pub-id-type="doi">10.3389/fenrg.2021.668908</article-id>
<article-categories>
<subj-group subj-group-type="heading">
<subject>Energy Research</subject>
<subj-group>
<subject>Original Research</subject>
</subj-group>
</subj-group>
</article-categories>
<title-group>
<article-title>Techno Economic Evaluation and Feasibility Analysis of a Hybrid Net Zero Energy Building in Pakistan: A Case Study of Hospital</article-title>
</title-group>
<contrib-group>
<contrib contrib-type="author">
<name><surname>Arif</surname> <given-names>Saba</given-names></name>
<xref ref-type="aff" rid="aff1"><sup>1</sup></xref>
<xref ref-type="aff" rid="aff2"><sup>2</sup></xref>
<xref ref-type="aff" rid="aff3"><sup>3</sup></xref>
<uri xlink:href="http://loop.frontiersin.org/people/1291971/overview"/>
</contrib>
<contrib contrib-type="author" corresp="yes">
<name><surname>Taweekun</surname> <given-names>Juntakan</given-names></name>
<xref ref-type="aff" rid="aff4"><sup>4</sup></xref>
<xref ref-type="corresp" rid="c001"><sup>&#x0002A;</sup></xref>
</contrib>
<contrib contrib-type="author">
<name><surname>Ali</surname> <given-names>Hafiz Muhammad</given-names></name>
<xref ref-type="aff" rid="aff5"><sup>5</sup></xref>
<uri xlink:href="http://loop.frontiersin.org/people/1111637/overview"/>
</contrib>
<contrib contrib-type="author">
<name><surname>Theppaya</surname> <given-names>Thanansak</given-names></name>
<xref ref-type="aff" rid="aff4"><sup>4</sup></xref>
</contrib>
</contrib-group>
<aff id="aff1"><sup>1</sup><institution>Energy Technology Program, Faculty of Engineering, Prince of Songkla University</institution>, <addr-line>Hat Yai</addr-line>, <country>Thailand</country></aff>
<aff id="aff2"><sup>2</sup><institution>Department of Mechanical Engineering, Institute of Aerospace and Avionics, Air University</institution>, <addr-line>Islamabad</addr-line>, <country>Pakistan</country></aff>
<aff id="aff3"><sup>3</sup><institution>Department of Mechanical and Manufacturing Engineering, Universiti Tun Hussein Onn Malaysia</institution>, <addr-line>Parit Raja</addr-line>, <country>Malaysia</country></aff>
<aff id="aff4"><sup>4</sup><institution>Department of Mechanical and Mechatronics Engineering, Faculty of Engineering, Prince of Songkla University</institution>, <addr-line>Hat Yai</addr-line>, <country>Thailand</country></aff>
<aff id="aff5"><sup>5</sup><institution>Department of Mechanical Engineering, King Fahd University of Petroleum and Minerals</institution>, <addr-line>Dhahran</addr-line>, <country>Saudi Arabia</country></aff>
<author-notes>
<fn fn-type="edited-by"><p>Edited by: Mohammad Hossein Ahmadi, Shahrood University of Technology, Iran</p></fn>
<fn fn-type="edited-by"><p>Reviewed by: Tolga Taner, Aksaray University, Turkey; Milad Sadeghzadeh, University of Tehran, Iran</p></fn>
<corresp id="c001">&#x0002A;Correspondence: Juntakan Taweekun <email>Juntakantaweekun&#x00040;yahoo.com</email></corresp>
<fn fn-type="other" id="fn001"><p>This article was submitted to Sustainable Energy Systems and Policies, a section of the journal Frontiers in Energy Research</p></fn></author-notes>
<pub-date pub-type="epub">
<day>30</day>
<month>04</month>
<year>2021</year>
</pub-date>
<pub-date pub-type="collection">
<year>2021</year>
</pub-date>
<volume>9</volume>
<elocation-id>668908</elocation-id>
<history>
<date date-type="received">
<day>17</day>
<month>02</month>
<year>2021</year>
</date>
<date date-type="accepted">
<day>15</day>
<month>03</month>
<year>2021</year>
</date>
</history>
<permissions>
<copyright-statement>Copyright &#x000A9; 2021 Arif, Taweekun, Ali and Theppaya.</copyright-statement>
<copyright-year>2021</copyright-year>
<copyright-holder>Arif, Taweekun, Ali and Theppaya</copyright-holder>
<license xlink:href="http://creativecommons.org/licenses/by/4.0/"><p>This is an open-access article distributed under the terms of the Creative Commons Attribution License (CC BY). The use, distribution or reproduction in other forums is permitted, provided the original author(s) and the copyright owner(s) are credited and that the original publication in this journal is cited, in accordance with accepted academic practice. No use, distribution or reproduction is permitted which does not comply with these terms.</p></license>
</permissions>
<abstract><p>The current study is an economic evaluation and feasibility study of hybrid microgrid Net Zero Energy Buildings in Pakistan. A Net Zero Energy approach is proposed for a two-story hospital building situated in Taxila, Pakistan. Consequently, to design a hybrid Net Zero Energy Building, the solar radiation potential of the subject location and electricity usage of the hospital are estimated. The proposed hybrid microgrid Net Zero Energy Building comprises photovoltaic modules and converters. However, the thermal load is computed as a grid-connected hybrid system. Economic evaluation is performed by using economic indicators of the net present cost and the payback period. Also, initial and operational costs are determined, to determine the profitability of the project. Results show that the analysis is a cost-effective approach and has a payback period of 2.53y. Additionally, the per-unit cost of electricity is reduced to 0.12 USD/kWh. Moreover, the energy produced by a hybrid system is 10.24% more economical than that of the pre-working grid system. Results explain the reduction in the cost of energy and profit margin in electricity generation and the increase in electricity production and feasibility of hybrid Net Zero Energy Buildings in Pakistan. Research will help to develop an approach toward an IEA task 47 in Pakistan with the possible development of simulation-based installations of Net Zero Energy Buildings in the health sector in Pakistan.</p></abstract>
<kwd-group>
<kwd>Net Zero Energy Building</kwd>
<kwd>hospital</kwd>
<kwd>micro grid</kwd>
<kwd>feasibility analysis</kwd>
<kwd>payback period</kwd>
<kwd>cost of electricity</kwd>
</kwd-group>
<counts>
<fig-count count="15"/>
<table-count count="7"/>
<equation-count count="12"/>
<ref-count count="66"/>
<page-count count="18"/>
<word-count count="8469"/>
</counts>
</article-meta>
</front>
<body>
<sec sec-type="intro" id="s1">
<title>Introduction</title>
<p>In the past few decades, energy consumption in buildings has been increased to 30% worldwide (Ji et al., <xref ref-type="bibr" rid="B25">2017</xref>; Si et al., <xref ref-type="bibr" rid="B47">2018</xref>). Renewable energy is not a new concept to work with. Many researchers are already working on various renewable energy systems to reduce capital costs and increase energy production. In a study, the water management of PEM fuel is inspected, and, according to the results, the effectiveness of PEM fuel cells is at maximum at 80&#x000B0;C with the removal of wastewater periodically (Taner, <xref ref-type="bibr" rid="B56">2015a</xref>). In another research, the importance of simulation and optimization techniques is highlighted by working on PEM fuel cells in the energy sector. Results conclude that by the simulation of operating pressures and voltage parameters as working parameters, the energy and exergy efficiencies are 47.6 and 50.4%, respectively (Taneer, <xref ref-type="bibr" rid="B52">2018</xref>). In a study of the PEM electrolyzer, the payback period for the hydrogen generation systems is observed. Operating parameters were the current and voltage. According to the results, the simple payback period was thought to be 2.32y (Taneer et al., <xref ref-type="bibr" rid="B53">2018</xref>). In another research, a techno economic analysis was performed for sugar production processes. The main aim of the research was to reduce capital cost with an increase in the production of turbine power. So, by way of a well-structured analysis, the unit cost ought to be 3.142 [$/kW] with a payback period of 4.32 years (Taneer and Sivrioglu, <xref ref-type="bibr" rid="B54">2017</xref>).</p>
<p>In recent times, China has emerged as a major global energy consumer in terms of the building sector (Wang et al., <xref ref-type="bibr" rid="B58">2014</xref>). However, the energy consumption of hospitals is more than double that of other ordinary buildings in society. Energy use in hospitals is important due to the high heating, cooling, and ventilation thermal loads, critical medical equipment, and operational requirements (Balaras et al., <xref ref-type="bibr" rid="B7">2007</xref>). Hence, energy-efficient designs for hospitals can play a vital role in sustainable development in society (Meegoda et al., <xref ref-type="bibr" rid="B32">2012</xref>). In the past years, many studies have been conducted in different countries especially for hospitals. For example, Ahmed H&#x000B7;S (Sherif, <xref ref-type="bibr" rid="B45">1999</xref>) proposed in 1999 that cost-effective and technical aspects should be considered for the designing of hospitals in developing nations, particularly for low-income groups. In a study in the United Kingdom in 2007 (Shu et al., <xref ref-type="bibr" rid="B46">2007</xref>), primary energy consumption was reduced by 15% by simply implementing sustainable healthcare goals. Also, a sensitivity analysis for the building energy consumption and energy-saving potential optimization of the hospital energy supply system was conducted by Japanese researchers in Asia (Schweber, <xref ref-type="bibr" rid="B42">2013</xref>). According to the research, there is little available data for energy consumption related to hospitals, especially energy data for climate diversity in different regions of Asia. Moreover, for the designing of NZEBs (Alfano et al., <xref ref-type="bibr" rid="B4">2014</xref>), two characteristics have to be measured, namely, indoor environmental quality (IEQ) and energy reduction per capita. The new regulation demands that the NZEB goal must be achieved with an acceptable IEQ level for residents, especially for medical institutions, i.e., hospital buildings. Moreover, with the help of two different groups of people, i.e., medical staff and patients, the IEQ demand can be standardized. Therefore, a lot of literature is available on IEQ in hospital buildings (Skoog et al., <xref ref-type="bibr" rid="B49">2005</xref>; Han et al., <xref ref-type="bibr" rid="B21">2007</xref>; Yau and Chew, <xref ref-type="bibr" rid="B61">2009</xref>; Pourshaghaghy and Omidvari, <xref ref-type="bibr" rid="B35">2012</xref>; Del Ferraro et al., <xref ref-type="bibr" rid="B10">2015</xref>; Golbazi and Aktas, <xref ref-type="bibr" rid="B20">2016</xref>; Alfano et al., <xref ref-type="bibr" rid="B3">2017</xref>; Khalid et al., <xref ref-type="bibr" rid="B27">2017</xref>; Sattayakorn et al., <xref ref-type="bibr" rid="B41">2017</xref>). One of the best researches in the area of indoor environmental quality is Fanger&#x00027;s research, which describes various factors regarding human thermal comfort and indoor air quality in the hospitals (Skoog et al., <xref ref-type="bibr" rid="B49">2005</xref>).</p>
<p>Presently, non-residential buildings are major power consumers in developed countries, consuming 20&#x02013;40% of the total primary energy (PE). For example, in 2010, the Dutch environment consumed 41% of the total energy consumption in the Netherlands (Vanhoutteghem et al., <xref ref-type="bibr" rid="B57">2015</xref>). For these reasons, the European Union issued the &#x0201C;Energy Performance Directive for Buildings&#x0201D; (EPBD) in May 2010 (EIA, <xref ref-type="bibr" rid="B13">2011</xref>). The directive sets forth requirements to accomplish the goals of the NZEBs regulations and EU member states (MS) legislation by 2020. Generally, from January 1, 2019, new buildings under the government must be NZEBs, and the rest of the new buildings be they either residential or public utilities must meet the NZEB requirements from January 1, 2020. As there is in the Netherlands no clear definition of NZEBs for 2020, the Dutch administration has issued a public plan to encourage NZEBs (Dutch governments, <xref ref-type="bibr" rid="B12">2012</xref>), which illustrates different schemes to decrease overall energy consumption. In another research (REHVA, <xref ref-type="bibr" rid="B67">2010</xref>), the total energy consumption by the Dutch healthcare sector accounts for 1.64%. There are 120 hospitals in the Netherlands, 8 of which are academic hospitals (Ministerie van Volkshuisvesting, <xref ref-type="bibr" rid="B33">2010</xref>; Zurghulpatias, <xref ref-type="bibr" rid="B65">2015a</xref>,<xref ref-type="bibr" rid="B66">b</xref>).</p>
<p>Similarly, in the past decade, NZEBs in the United States have received increasing attention from different organizations, i.e., ASHRAE and the American Architectural Institute (AIA). ASHRAE has set a target to develop a tool by 2020 that will facilitate the building community to develop a viable NZEB approach in the market by 2030 (AIA, <xref ref-type="bibr" rid="B1">2011</xref>). The AIA 2030 has the goal of attaining new carbon-neutral buildings all over the country (Entrop and Brouwers, <xref ref-type="bibr" rid="B14">2019</xref>). In previous literature, only a few studies were based on the actual measured performance and efficiency of NZEBs. For example (AlAjmi et al., <xref ref-type="bibr" rid="B2">2016</xref>; Zhou et al., <xref ref-type="bibr" rid="B64">2016</xref>; Kneifel and Webb, <xref ref-type="bibr" rid="B29">2018</xref>; Wu and Skye, <xref ref-type="bibr" rid="B60">2018</xref>), worked on NZEBs. AlAjmi et al. (<xref ref-type="bibr" rid="B2">2016</xref>) worked on simulation-based studies to examine the possibility of converting existing institutional buildings to NZEB in the hot and humid climate of Kuwait. In the study, solar PV and thermal cooling systems were installed in Kuwait, and feasibility analysis was performed for NZEBs.</p>
<p>Also, there are many established healthcare regulations available in Europe, the USA, and the UK. Building Research Establishment Environmental Assessment Method (BREEAM) is the earliest green building rating system, established in the UK in 1990 (Schweber and Haroglu, <xref ref-type="bibr" rid="B43">2014</xref>; Alhorr et al., <xref ref-type="bibr" rid="B5">2015</xref>). Among BREEAM products, the BREEAM healthcare version was developed for green hospital buildings in 2008 (Ferreira et al., <xref ref-type="bibr" rid="B17">2014</xref>). Leadership in Energy and Environmental Design (LEED) is another green building rating system, and it was launched by the US Green Building Council in 1998. In the LEED product family, the U.S. Green Building Council (USGBC) released LEED for healthcare in 2011. In addition, the US healthcare industry steering committee has also formulated the Green Healthcare Guidelines (GGHC) (Azhar et al., <xref ref-type="bibr" rid="B6">2011</xref>; Wu et al., <xref ref-type="bibr" rid="B59">2017</xref>). The rating systems of these developed countries set an example for other countries. However, different regions have different energy consumption attributes and impact methods, and the evaluation method must thus be suitable for the real situation of the country. Therefore, in 2006, China formulated the &#x0201C;Evaluation Standard for Green Buildings&#x0201D; (ESGB), which was the first assessment standard for the &#x0201C;environmental performance rating&#x0201D; of green buildings in China (Younger et al., <xref ref-type="bibr" rid="B62">2008</xref>; Pradinuk, <xref ref-type="bibr" rid="B36">2009</xref>).</p>
<p>In developed nations, there are many international communities that are already working on NZEBs. However, in underdeveloped nations like Pakistan, the energy consumption of buildings was 44% from 2016 to 2017. The degree of energy consumed in the building sector will be doubled in the year 2030 (Liu et al., <xref ref-type="bibr" rid="B31">2014</xref>). Similarly, buildings also account for 43% of greenhouse gas emissions and 75% of the electricity usage in Pakistan (Jian et al., <xref ref-type="bibr" rid="B26">2017</xref>; Zhang et al., <xref ref-type="bibr" rid="B63">2017</xref>). More than 38% of the total building energy is consumed in heating, ventilation, and air conditioning. The energy needs of commercial buildings account for a considerable part of the total energy consumption (Chen et al., <xref ref-type="bibr" rid="B8">2008</xref>). In Pakistan, hospitals account for 18% of the energy use and they occupy 17% of the total non-residential area [Pakistan Integrated Energy Model (Pak-IEM), Ministry of Planning Development Government of Pakistan, <xref ref-type="bibr" rid="B34">2011</xref>].</p>
<p>In order to solve this problem, one of the two solutions can be used: minimizing the building energy usage or adapting the renewable energy resources. Analysts believe that it is possible to achieve 70% financial savings by applying better design strategies and efficient tools during the building design phase (Rafique and Rehmanb, <xref ref-type="bibr" rid="B37">2017</xref>). Energy shortage in Pakistan is attributed to an ever-increasing population size, followed by consumers being subjected to frequent load shedding. Pakistan, being the sixth most populous country in the world, makes up about 2.56% of the total worldwide population (Khan and Pervaiz, <xref ref-type="bibr" rid="B28">2013</xref>; Raheem et al., <xref ref-type="bibr" rid="B38">2016</xref>). Pakistan relies on fossil fuels to fulfill its energy demands and has to spend 20% on crude oil imports (Haves, <xref ref-type="bibr" rid="B22">2019</xref>). Additionally, energy demand is growing by 8&#x02013;10% annually, in contrast to an annual supply growth of only 7% (Farooqui, <xref ref-type="bibr" rid="B16">2014</xref>).</p>
<p>By reviewing the literature, it can be inferred that the development of NZEBs is not a common practice in underdeveloped countries. Likewise, there are no set regulations and targets related to renewable energy usage in the building sector. Also, only a few studies were based on the actual measurement performance and efficiency of NZE hospitals in Asia and none in Pakistan. Furthermore, the previous studies and pre-existing energy planning modules neglect the importance of renewable energy for the commercial sector in Pakistan. Therefore, the ensuing renewable energy solutions are actually deterministic. Furthermore, the International Energy Agency (IEA) has outlined 13 tasks for the development, performance, and analysis of NZEBs in (OECD) countries. Pakistan is not an associated member of the IEA. Therefore, there is a dire need for research on energy-efficient non-residential buildings as per task 47, which is not available in Pakistan (Fritjof and Asplan Viak, <xref ref-type="bibr" rid="B18">2014</xref>). Hence, the current research will be a feasibility analysis of an efficient and effective grid-connected NZEB model for a hospital using efficient optimization techniques along with intelligent simulation and modeling methods in accordance with the IEA standards in Pakistan.</p>
<p>The developed model of the NZE hospital would be used during the building and community project planning stages. Also, it will guide decision-makers toward much more efficient energy options and will attract investors toward a better adaptation of RE at the community level in Pakistan.</p>
<p>Key objectives of current research are as follows:</p>
<list list-type="simple">
<list-item><p>&#x027A2; To develop an approach for NZEB in a non-RE building in Pakistan</p></list-item>
<list-item><p>&#x027A2; Analysis of economic indicators and design solutions that will influence non-RE NZEBs</p></list-item>
<list-item><p>&#x027A2; Finding of an optimized NZEB design</p></list-item>
<list-item><p>&#x027A2; Feasibility of non-RE NZEBs in Pakistan.</p></list-item>
</list>
<p>This section is followed by six subsections as follows: building design and site selection, estimation of thermal load of the hospital building, description of the HOMER program, design of hybrid microgrid NZEB, NZEB microgrid feasibility, and optimization step.</p>
</sec>
<sec sec-type="methods" id="s2">
<title>Methodology</title>
<p>In this particular research, a hybrid microgrid NZEB is proposed for the hospital building situated in Taxila, Pakistan. A complete methodology is given in <xref ref-type="fig" rid="F1">Figure 1</xref>. The aim of the current research is to minimize the electricity consumption expenditure of the hospital by implementing RE techniques as well as to check the feasibility of NZEBs for the Pakistani climate. So, the total thermal load is calculated for a hospital located in Taxila, Pakistan, using ASHRAE thermal load equations. Also, an energy-efficient model is developed in HOMER Pro software by using variables of NPC, operating cost, and payback period. Later on, sensitivity analysis and optimization of the parameters are performed.</p>
<fig id="F1" position="float">
<label>Figure 1</label>
<caption><p>Methodology of the research.</p></caption>
<graphic xlink:href="fenrg-09-668908-g0001.tif"/>
</fig>
</sec>
<sec id="s3">
<title>Building Design</title>
<p>To design the building, the most important task was the selection of a site in order to perform a feasibility analysis of NZEBs in Pakistan.</p>
<sec>
<title>Site Selection</title>
<p>On the basis of climate condition, Pakistan is divided into five zones as shown in <xref ref-type="fig" rid="F2">Figure 2A</xref>. However, the highest temperatures range, i.e., 25&#x02013;127&#x000B0;F exists in zone D (Salma et al., <xref ref-type="bibr" rid="B39">2012</xref>). Therefore, in this study, a hospital building is selected for the conversion into NZEB in zone D in Taxila, and it has a latitude of 33.43&#x000B0;N and longitude 72.8397&#x000B0;E. In <xref ref-type="fig" rid="F2">Figure 2B</xref>, the solar potential of Pakistan for different cities is highlighted. It can be clearly seen that the selected zone has a high potential for energy production and development of NZEBs in Pakistan (Solar resource maps of Pakistan, <xref ref-type="bibr" rid="B50">2019</xref>).</p>
<fig id="F2" position="float">
<label>Figure 2</label>
<caption><p>Zones classification of Pakistan. <bold>(A)</bold> Classification of zones on the basis of climate in Pakistan. <bold>(B)</bold> Classification of zones on the basis of solar potential in Pakistan.</p></caption>
<graphic xlink:href="fenrg-09-668908-g0002.tif"/>
</fig>
</sec>
<sec>
<title>Zone Identification and 3D Modeling</title>
<p>After selection of building type and site, a 3D model is designed in Heat Cad software as shown in <xref ref-type="fig" rid="F3">Figures 3A,B</xref>. Also, the real building is illustrated in <xref ref-type="fig" rid="F4">Figures 4A,B</xref>. In the current research, the hospital building is comprised of five offices, a patient ward, ICU, radiology, two laboratories, operation theater, pharmacy, and washrooms. However, identification of zones is dependent on the type of work, thermal conditions, and human comfort.</p>
<fig id="F3" position="float">
<label>Figure 3</label>
<caption><p><bold>(A)</bold> Ground Floor plan of the hospital building. <bold>(B)</bold> 1st Floor plan of hospital building.</p></caption>
<graphic xlink:href="fenrg-09-668908-g0003.tif"/>
</fig>
<fig id="F4" position="float">
<label>Figure 4</label>
<caption><p>Selected hospital building. <bold>(A)</bold> 3D model of the building. <bold>(B)</bold> Real hospital building.</p></caption>
<graphic xlink:href="fenrg-09-668908-g0004.tif"/>
</fig>
</sec>
</sec>
<sec id="s4">
<title>Thermal Load Assessment</title>
<p>The current hybrid on-grid system is designed to meet the electricity needs of a hospital building in Pakistan using solar energy as an alternative energy resource in addition to a conventional grid. The estimation of the thermal load is carried out carefully, taking into consideration the load requirements of the hospital building for the peak summer season. Design parameters for the building are given in <xref ref-type="table" rid="T1">Table 1</xref>.</p>
<table-wrap position="float" id="T1">
<label>Table 1</label>
<caption><p>Design parameters of each zone in the hospital building.</p></caption>
<table frame="hsides" rules="groups">
<thead><tr>
<th valign="top" align="left" style="background-color:#f3f3f4"><bold>Design parameters</bold></th>
<th style="background-color:#f3f3f4"/>
<th valign="top" align="center" colspan="5" style="background-color:#daedf3;border-bottom: thin solid #000000;"><bold>Zone 1</bold></th>
<th valign="top" align="center" colspan="5" style="background-color:#fbebda;border-bottom: thin solid #000000;"><bold>Zone 2</bold></th>
<th valign="top" align="center" colspan="2" style="background-color:#cbbfd8;border-bottom: thin solid #000000;"><bold>Zone 3</bold></th>
<th valign="top" align="center" style="background-color:#ded9c4;border-bottom: thin solid #000000;"><bold>Zone 4</bold></th>
</tr>
<tr>
<th style="background-color:#f3f3f4"/>
<th style="background-color:#f3f3f4"/>
<th style="background-color:#daedf3"/>
<th style="background-color:#daedf3"/>
<th valign="top" align="center" style="background-color:#daedf3"><bold>Offices</bold></th>
<th style="background-color:#daedf3"/>
<th style="background-color:#daedf3"/>
<th valign="top" align="center" colspan="2" style="background-color:#fbebda"><bold>Ward</bold></th>
<th valign="top" align="center" style="background-color:#fbebda;border-bottom: thin solid #000000;"><bold>Radiology</bold></th>
<th valign="top" align="center" colspan="2" style="background-color:#fbebda"><bold>Laboratory</bold></th>
<th valign="top" align="center" style="background-color:#cbbfd8;border-bottom: thin solid #000000;"><bold>OT</bold></th>
<th valign="top" align="center" style="background-color:#cbbfd8;border-bottom: thin solid #000000;"><bold>Pharmacy</bold></th>
<th valign="top" align="center" style="background-color:#ded9c4;border-bottom: thin solid #000000;"><bold>Washrooms</bold></th>
</tr>
<tr>
<th style="background-color:#f3f3f4"/>
<th style="background-color:#f3f3f4"/>
<th valign="top" align="center" style="background-color:#daedf3;border-top: thin solid #000000;"><bold>01</bold></th>
<th valign="top" align="center" style="background-color:#daedf3;border-top: thin solid #000000;"><bold>02</bold></th>
<th valign="top" align="center" style="background-color:#daedf3;border-top: thin solid #000000;"><bold>03</bold></th>
<th valign="top" align="center" style="background-color:#daedf3;border-top: thin solid #000000;"><bold>04</bold></th>
<th valign="top" align="center" style="background-color:#daedf3;border-top: thin solid #000000;"><bold>05</bold></th>
<th valign="top" align="center" style="background-color:#fbebda;border-top: thin solid #000000;"><bold>Patient</bold></th>
<th valign="top" align="center" style="background-color:#fbebda;border-top: thin solid #000000;"><bold>ICU</bold></th>
<th style="background-color:#fbebda"/>
<th valign="top" align="center" style="background-color:#fbebda;border-top: thin solid #000000;"><bold>General</bold></th>
<th valign="top" align="center" style="background-color:#fbebda;border-top: thin solid #000000;"><bold>Special</bold></th>
<th style="background-color:#cbbfd8"/>
<th style="background-color:#cbbfd8"/>
<th style="background-color:#ded9c4"/>
</tr>
</thead>
<tbody>
<tr>
<td valign="top" align="left" style="background-color:#f3f3f4"><bold>Dimensions (ft</bold><sup><bold>2</bold></sup><bold>)</bold></td>
<td style="background-color:#f3f3f4"/>
<td valign="top" align="center" style="background-color:#daedf3">20&#x0002A; 15</td>
<td valign="top" align="center" style="background-color:#daedf3">20&#x0002A; 15</td>
<td valign="top" align="center" style="background-color:#daedf3">20&#x0002A; 15</td>
<td valign="top" align="center" style="background-color:#daedf3">15&#x0002A; 15</td>
<td valign="top" align="center" style="background-color:#daedf3">15&#x0002A; 15</td>
<td valign="top" align="center" style="background-color:#fbebda">20&#x0002A;15</td>
<td valign="top" align="center" style="background-color:#fbebda">20&#x0002A;15</td>
<td valign="top" align="center" style="background-color:#fbebda">20&#x0002A;15</td>
<td valign="top" align="center" style="background-color:#fbebda">15&#x0002A;15</td>
<td valign="top" align="center" style="background-color:#fbebda">20&#x0002A;15</td>
<td valign="top" align="center" style="background-color:#cbbfd8">30&#x0002A; 15</td>
<td valign="top" align="center" style="background-color:#cbbfd8">20&#x0002A;15</td>
<td valign="top" align="center" style="background-color:#ded9c4">10&#x0002A;10</td>
</tr>
<tr>
<td valign="top" align="left" style="background-color:#f3f3f4"><bold>Outdoor temperatu re (</bold><bold>&#x000B0;</bold><bold>C)</bold></td>
<td valign="top" align="center" style="background-color:#f3f3f4">DB</td>
<td valign="top" align="center" style="background-color:#daedf3">40</td>
<td valign="top" align="center" style="background-color:#daedf3">40</td>
<td valign="top" align="center" style="background-color:#daedf3">40</td>
<td valign="top" align="center" style="background-color:#daedf3">40</td>
<td valign="top" align="center" style="background-color:#daedf3">40</td>
<td valign="top" align="center" style="background-color:#fbebda">40</td>
<td valign="top" align="center" style="background-color:#fbebda">40</td>
<td valign="top" align="center" style="background-color:#fbebda">40</td>
<td valign="top" align="center" style="background-color:#fbebda">40</td>
<td valign="top" align="center" style="background-color:#fbebda">40</td>
<td valign="top" align="center" style="background-color:#cbbfd8">40</td>
<td valign="top" align="center" style="background-color:#cbbfd8">40</td>
<td valign="top" align="center" style="background-color:#ded9c4">40</td>
</tr>
<tr>
<td style="background-color:#f3f3f4"/>
<td valign="top" align="center" style="background-color:#f3f3f4">WB</td>
<td valign="top" align="center" style="background-color:#daedf3">36</td>
<td valign="top" align="center" style="background-color:#daedf3">36</td>
<td valign="top" align="center" style="background-color:#daedf3">36</td>
<td valign="top" align="center" style="background-color:#daedf3">36</td>
<td valign="top" align="center" style="background-color:#daedf3">36</td>
<td valign="top" align="center" style="background-color:#fbebda">36</td>
<td valign="top" align="center" style="background-color:#fbebda">36</td>
<td valign="top" align="center" style="background-color:#fbebda">36</td>
<td valign="top" align="center" style="background-color:#fbebda">36</td>
<td valign="top" align="center" style="background-color:#fbebda">36</td>
<td valign="top" align="center" style="background-color:#cbbfd8">36</td>
<td valign="top" align="center" style="background-color:#cbbfd8">36</td>
<td valign="top" align="center" style="background-color:#ded9c4">36</td>
</tr>
<tr>
<td valign="top" align="left" style="background-color:#f3f3f4"><bold>Inside temperatu re (</bold><bold>&#x000B0;</bold><bold>C)</bold></td>
<td valign="top" align="center" style="background-color:#f3f3f4">DB</td>
<td valign="top" align="center" style="background-color:#daedf3">25</td>
<td valign="top" align="center" style="background-color:#daedf3">25</td>
<td valign="top" align="center" style="background-color:#daedf3">25</td>
<td valign="top" align="center" style="background-color:#daedf3">25</td>
<td valign="top" align="center" style="background-color:#daedf3">25</td>
<td valign="top" align="center" style="background-color:#fbebda">24</td>
<td valign="top" align="center" style="background-color:#fbebda">24</td>
<td valign="top" align="center" style="background-color:#fbebda">24</td>
<td valign="top" align="center" style="background-color:#fbebda">24</td>
<td valign="top" align="center" style="background-color:#fbebda">24</td>
<td valign="top" align="center" style="background-color:#cbbfd8">22</td>
<td valign="top" align="center" style="background-color:#cbbfd8">22</td>
<td valign="top" align="center" style="background-color:#ded9c4">26</td>
</tr>
<tr>
<td style="background-color:#f3f3f4"/>
<td valign="top" align="center" style="background-color:#f3f3f4">RH (%)</td>
<td valign="top" align="center" style="background-color:#daedf3">60</td>
<td valign="top" align="center" style="background-color:#daedf3">60</td>
<td valign="top" align="center" style="background-color:#daedf3">60</td>
<td valign="top" align="center" style="background-color:#daedf3">60</td>
<td valign="top" align="center" style="background-color:#daedf3">60</td>
<td valign="top" align="center" style="background-color:#fbebda">60</td>
<td valign="top" align="center" style="background-color:#fbebda">60</td>
<td valign="top" align="center" style="background-color:#fbebda">60</td>
<td valign="top" align="center" style="background-color:#fbebda">60</td>
<td valign="top" align="center" style="background-color:#fbebda">60</td>
<td valign="top" align="center" style="background-color:#cbbfd8">60</td>
<td valign="top" align="center" style="background-color:#cbbfd8">60</td>
<td valign="top" align="center" style="background-color:#ded9c4">60</td>
</tr>
<tr>
<td valign="top" align="left" style="background-color:#f3f3f4"><bold>Wall composition</bold></td>
<td style="background-color:#f3f3f4"/>
<td style="background-color:#dcdddf"/>
<td style="background-color:#dcdddf"/>
<td style="background-color:#dcdddf"/>
<td valign="top" align="center" colspan="8" style="background-color:#dcdddf">Outside surface film &#x0002B; Brick &#x0002B; Plaster &#x0002B; Inside surface film</td>
<td style="background-color:#dcdddf"/>
<td style="background-color:#dcdddf"/>
</tr>
<tr>
<td valign="top" align="left" style="background-color:#f3f3f4"><bold>U value of glass (W/m</bold><sup><bold>2</bold></sup><bold>K)</bold></td>
<td style="background-color:#f3f3f4"/>
<td style="background-color:#dcdddf"/>
<td style="background-color:#dcdddf"/>
<td style="background-color:#dcdddf"/>
<td style="background-color:#dcdddf"/>
<td style="background-color:#dcdddf"/>
<td style="background-color:#dcdddf"/>
<td valign="top" align="center" style="background-color:#dcdddf">5.9</td>
<td style="background-color:#dcdddf"/>
<td style="background-color:#dcdddf"/>
<td style="background-color:#dcdddf"/>
<td style="background-color:#dcdddf"/>
<td style="background-color:#dcdddf"/>
<td style="background-color:#dcdddf"/>
</tr>
<tr>
<td valign="top" align="left" style="background-color:#f3f3f4"><bold>Shading coefficient for glass</bold></td>
<td style="background-color:#f3f3f4"/>
<td style="background-color:#dcdddf"/>
<td style="background-color:#dcdddf"/>
<td style="background-color:#dcdddf"/>
<td style="background-color:#dcdddf"/>
<td style="background-color:#dcdddf"/>
<td valign="top" align="center" colspan="3" style="background-color:#dcdddf">0.64 (Single glass)</td>
<td style="background-color:#dcdddf"/>
<td style="background-color:#dcdddf"/>
<td style="background-color:#dcdddf"/>
<td style="background-color:#dcdddf"/>
<td style="background-color:#dcdddf"/>
</tr>
<tr>
<td valign="top" align="left" style="background-color:#f3f3f4"><bold>Infiltration</bold></td>
<td style="background-color:#f3f3f4"/>
<td style="background-color:#dcdddf"/>
<td style="background-color:#dcdddf"/>
<td style="background-color:#dcdddf"/>
<td style="background-color:#dcdddf"/>
<td valign="top" align="center" colspan="6" style="background-color:#dcdddf">0.2 ACH (Assuming completely tight building)</td>
<td style="background-color:#dcdddf"/>
<td style="background-color:#dcdddf"/>
<td style="background-color:#dcdddf"/>
</tr>
</tbody>
</table>
<table-wrap-foot>
<p><italic>Colored values are optimized and selected values for the proposed system</italic>.</p>
</table-wrap-foot>
</table-wrap>
<p>July is selected as a peak month due to the high thermal load demand in the building. Design temperatures are selected on the basis of set regulation of ASHRAE for hospitals. Also, for estimation of thermal load of the building, external as well as internal loads are calculated using ASHRAE standard equations (Delisle, <xref ref-type="bibr" rid="B11">2011</xref>; Lenoir et al., <xref ref-type="bibr" rid="B30">2011</xref>; <xref ref-type="bibr" rid="B23">J</xref>, <xref ref-type="bibr" rid="B23">2013</xref>) and the equation given below (Sandeep, <xref ref-type="bibr" rid="B40">2015</xref>).</p>
<sec>
<title>Internal Load</title>
<list list-type="simple">
<list-item><p>i) <bold>Occupants load</bold></p></list-item>
</list>
<disp-formula id="E1"><label>(1)</label><mml:math id="M1"><mml:mtable class="eqnarray" columnalign="left"><mml:mtr><mml:mtd><mml:msub><mml:mrow><mml:mi>Q</mml:mi></mml:mrow><mml:mrow><mml:mi>s</mml:mi><mml:mi>e</mml:mi><mml:mi>n</mml:mi><mml:mi>s</mml:mi><mml:mi>i</mml:mi><mml:mi>b</mml:mi><mml:mi>l</mml:mi><mml:mi>e</mml:mi></mml:mrow></mml:msub><mml:mo>=</mml:mo><mml:mi>N</mml:mi><mml:mo>&#x000D7;</mml:mo><mml:mi>S</mml:mi><mml:mi>H</mml:mi><mml:mi>G</mml:mi></mml:mtd></mml:mtr></mml:mtable></mml:math></disp-formula>
<disp-formula id="E2"><label>(2)</label><mml:math id="M2"><mml:mtable class="eqnarray" columnalign="left"><mml:mtr><mml:mtd><mml:mi>Q</mml:mi><mml:mi>l</mml:mi><mml:mi>a</mml:mi><mml:mi>t</mml:mi><mml:mi>e</mml:mi><mml:mi>n</mml:mi><mml:mi>t</mml:mi><mml:mo>=</mml:mo><mml:mi>L</mml:mi><mml:mi>H</mml:mi><mml:msup><mml:mrow><mml:mi>G</mml:mi></mml:mrow><mml:mrow><mml:mo>*</mml:mo></mml:mrow></mml:msup><mml:mi>N</mml:mi></mml:mtd></mml:mtr></mml:mtable></mml:math></disp-formula>
<p>Where;</p>
<list list-type="simple">
<list-item><p><italic>Q</italic><sub><italic>sensible</italic></sub> is the sensible heat gain/person (W).</p></list-item>
<list-item><p><italic>Qlatent</italic> is the latent heat gain/person (W).</p></list-item>
<list-item><p>N is the total number of people present in the conditioned space.</p></list-item>
<list-item><p>SHG is the sensible heat gain per person.</p></list-item>
<list-item><p>LHG is the latent heat gain per person.</p></list-item>
</list>
<list list-type="simple">
<list-item><p>ii) <bold>Heat gain from lighting</bold></p></list-item>
</list>
<p>Thermal load is estimated due to lighting is given in Equation (3):</p>
<disp-formula id="E3"><label>(3)</label><mml:math id="M3"><mml:mtable class="eqnarray" columnalign="left"><mml:mtr><mml:mtd><mml:mi>P</mml:mi><mml:mtext>&#x000A0;</mml:mtext><mml:mo>=</mml:mo><mml:mtext>&#x000A0;</mml:mtext><mml:mfrac><mml:mrow><mml:mn>1</mml:mn><mml:mo>,</mml:mo><mml:mn>000</mml:mn><mml:mfrac><mml:mrow><mml:mi>l</mml:mi><mml:mi>u</mml:mi><mml:mi>m</mml:mi><mml:mi>e</mml:mi><mml:mi>n</mml:mi></mml:mrow><mml:mrow><mml:msup><mml:mrow><mml:mi>m</mml:mi></mml:mrow><mml:mrow><mml:mn>2</mml:mn></mml:mrow></mml:msup></mml:mrow></mml:mfrac></mml:mrow><mml:mrow><mml:mn>0</mml:mn><mml:mo>.</mml:mo><mml:mn>5</mml:mn><mml:mo>&#x000D7;</mml:mo><mml:mi>l</mml:mi><mml:mi>i</mml:mi><mml:mi>g</mml:mi><mml:mi>h</mml:mi><mml:mi>t</mml:mi><mml:mi>e</mml:mi><mml:mi>m</mml:mi><mml:mi>i</mml:mi><mml:mi>t</mml:mi><mml:mi>t</mml:mi><mml:mi>e</mml:mi><mml:mi>d</mml:mi><mml:mi>f</mml:mi><mml:mi>r</mml:mi><mml:mi>o</mml:mi><mml:mi>m</mml:mi><mml:mi>s</mml:mi><mml:mi>o</mml:mi><mml:mi>u</mml:mi><mml:mi>c</mml:mi><mml:mi>e</mml:mi><mml:mfrac><mml:mrow><mml:mi>l</mml:mi><mml:mi>u</mml:mi><mml:mi>m</mml:mi><mml:mi>e</mml:mi><mml:mi>n</mml:mi></mml:mrow><mml:mrow><mml:mi>w</mml:mi><mml:mi>a</mml:mi><mml:mi>t</mml:mi><mml:mi>t</mml:mi></mml:mrow></mml:mfrac></mml:mrow></mml:mfrac></mml:mtd></mml:mtr></mml:mtable></mml:math></disp-formula>
<p>Where;</p>
<p>P is power provided per unit area.</p>
</sec>
<sec>
<title>External Load</title>
<list list-type="simple">
<list-item><p>iii) <bold>Heat transfer through roof (Q</bold><sub>roof</sub>)</p></list-item>
</list>
<p>Similarly, heat transfer through the roof is,</p>
<disp-formula id="E4"><label>(4)</label><mml:math id="M4"><mml:mtable class="eqnarray" columnalign="left"><mml:mtr><mml:mtd><mml:mtext>&#x000A0;&#x000A0;</mml:mtext><mml:msub><mml:mrow><mml:mi>Q</mml:mi></mml:mrow><mml:mrow><mml:mi>r</mml:mi><mml:mi>o</mml:mi><mml:mi>o</mml:mi><mml:mi>f</mml:mi></mml:mrow></mml:msub><mml:mo>=</mml:mo><mml:mi>C</mml:mi><mml:mi>L</mml:mi><mml:mi>T</mml:mi><mml:mi>D</mml:mi><mml:mo>&#x000D7;</mml:mo><mml:mrow><mml:mo stretchy="false">(</mml:mo><mml:mrow><mml:msub><mml:mrow><mml:mi>T</mml:mi></mml:mrow><mml:mrow><mml:mi>o</mml:mi></mml:mrow></mml:msub><mml:mo>-</mml:mo><mml:msub><mml:mrow><mml:mi>T</mml:mi></mml:mrow><mml:mrow><mml:mi>i</mml:mi></mml:mrow></mml:msub></mml:mrow><mml:mo stretchy="false">)</mml:mo></mml:mrow></mml:mtd></mml:mtr></mml:mtable></mml:math></disp-formula>
<list list-type="simple">
<list-item><p>iv) <bold>Heat transfer due to infiltration (Q</bold><sub><bold>in</bold></sub><bold>)</bold></p></list-item>
</list>
<p>For estimation of sensible and latent heat transfer due to infiltration, firstly, the mass of infiltration is estimated by Equation (5), and, using Equations (6, 7), the total heat transfer due to infiltration is then calculated.</p>
<disp-formula id="E5"><label>(5)</label><mml:math id="M5"><mml:msub><mml:mtext>M</mml:mtext><mml:mrow><mml:mtext>infiltration</mml:mtext></mml:mrow></mml:msub><mml:mtext>=&#x000A0;</mml:mtext><mml:mi>&#x003C1;</mml:mi><mml:mtext>&#x000A0;&#x000A0;</mml:mtext><mml:mo>&#x000D7;</mml:mo><mml:mtext>&#x000A0;&#x000A0;ACH&#x000A0;&#x000A0;</mml:mtext><mml:mo>&#x000D7;</mml:mo><mml:mtext>&#x000A0;&#x000A0;</mml:mtext><mml:mfrac><mml:mtext>V</mml:mtext><mml:mrow><mml:mtext>3</mml:mtext><mml:mo>,</mml:mo><mml:mtext>600</mml:mtext></mml:mrow></mml:mfrac></mml:math></disp-formula>
<disp-formula id="E6"><label>(6)</label><mml:math id="M6"><mml:msub><mml:mtext>Q</mml:mtext><mml:mrow><mml:mi>inf</mml:mi><mml:mo>.</mml:mo><mml:mtext>sensible</mml:mtext></mml:mrow></mml:msub><mml:mtext>&#x000A0;=&#x000A0;</mml:mtext><mml:msup><mml:mtext>Minfiltration</mml:mtext><mml:mo>&#x02217;</mml:mo></mml:msup><mml:mtext>cp</mml:mtext><mml:mo>,</mml:mo><mml:msup><mml:mtext>m</mml:mtext><mml:mo>&#x02217;</mml:mo></mml:msup><mml:mrow><mml:mo>(</mml:mo><mml:mrow><mml:mtext>to</mml:mtext><mml:mo>&#x02212;</mml:mo><mml:mtext>ti</mml:mtext></mml:mrow><mml:mo>)</mml:mo></mml:mrow></mml:math></disp-formula>
<disp-formula id="E7"><label>(7)</label><mml:math id="M7"><mml:msub><mml:mtext>Q</mml:mtext><mml:mrow><mml:mi>inf</mml:mi><mml:mo>.</mml:mo><mml:mtext>latent</mml:mtext></mml:mrow></mml:msub><mml:mtext>&#x000A0;&#x000A0;=&#x000A0;&#x000A0;</mml:mtext><mml:msup><mml:mtext>Minfiltration</mml:mtext><mml:mo>&#x02217;</mml:mo></mml:msup><mml:msup><mml:mtext>hfg</mml:mtext><mml:mo>&#x02217;</mml:mo></mml:msup><mml:mrow><mml:mo>(</mml:mo><mml:mrow><mml:mtext>Wo</mml:mtext><mml:mo>&#x02212;</mml:mo><mml:mtext>Wi</mml:mtext></mml:mrow><mml:mo>)</mml:mo></mml:mrow></mml:math></disp-formula>
<p>where</p>
<list list-type="simple">
<list-item><p>T<sub>o</sub> is the outdoor dry bulb temperature</p></list-item>
<list-item><p>T<sub>i</sub> is the indoor dry bulb temperature</p></list-item>
<list-item><p>C<sub>p,m</sub> is the Specific heat of the moist, infiltrated air</p></list-item>
<list-item><p>h<sub>fg</sub> is the latent heat of vaporization of water</p></list-item>
<list-item><p>W<sub>o</sub> is the outdoor humidity ratio</p></list-item>
<list-item><p>W<sub>i</sub> is the indoor humidity ratio.</p></list-item>
</list>
<list list-type="simple">
<list-item><p>v) <bold>Heat transfer due to walls (Q<sub>wall</sub>)</bold></p></list-item>
</list>
<p>Heat transfer by the walls is estimated by ASHRAE Equation (8). The <italic>Q</italic><sub><italic>wall</italic></sub> is dependent on the contact temperature of the outer and inner environment and wall material. In Pakistan, walls are usually made of a number of layers. In the current buildings, walls are composed of plaster and 255 mm face brick. The U value is used in the overall summation of thermal resistance of each layer of the wall where</p>
<disp-formula id="E8"><label>(8)</label><mml:math id="M8"><mml:mtable class="eqnarray" columnalign="left"><mml:mtr><mml:mtd><mml:mi>Q</mml:mi><mml:mo>=</mml:mo><mml:msub><mml:mrow><mml:mi>U</mml:mi></mml:mrow><mml:mrow><mml:mi>w</mml:mi><mml:mi>a</mml:mi><mml:mi>l</mml:mi><mml:mi>l</mml:mi></mml:mrow></mml:msub><mml:mo>*</mml:mo><mml:msub><mml:mrow><mml:mi>A</mml:mi></mml:mrow><mml:mrow><mml:mi>w</mml:mi><mml:mi>a</mml:mi><mml:mi>l</mml:mi><mml:mi>l</mml:mi></mml:mrow></mml:msub><mml:mo>*</mml:mo><mml:mrow><mml:mo stretchy="false">(</mml:mo><mml:mrow><mml:msub><mml:mrow><mml:mi>T</mml:mi></mml:mrow><mml:mrow><mml:mi>o</mml:mi></mml:mrow></mml:msub><mml:mo>-</mml:mo><mml:msub><mml:mrow><mml:mi>T</mml:mi></mml:mrow><mml:mrow><mml:mi>i</mml:mi></mml:mrow></mml:msub></mml:mrow><mml:mo stretchy="false">)</mml:mo></mml:mrow></mml:mtd></mml:mtr></mml:mtable></mml:math></disp-formula>
<p>and</p>
<list list-type="simple">
<list-item><p><italic>U</italic><sub><italic>wall</italic></sub> is the overall heat transfer coefficient.</p></list-item>
<list-item><p><italic>A</italic><sub><italic>wall</italic></sub> is the area of the wall.</p></list-item>
<list-item><p><italic>T</italic><sub><italic>o</italic></sub> &#x02212; <italic>T</italic><sub><italic>i</italic></sub>i is the temperature difference between the outside and inside of the wall.</p></list-item>
</list>
<list list-type="simple">
<list-item><p>vi) <bold>Heat transfer through glasses (Q<sub>g</sub>)</bold></p></list-item>
</list>
<p>Heat transfer by glass is high due to sun rays. Diffused or radiated sunrays play a major role in heat transfer. However, the heat transmitted is dependent on the wavelength of ray and compositional properties of glass. Q<sub>g</sub> is calculated by Equation (9)</p>
<disp-formula id="E9"><label>(9)</label><mml:math id="M9"><mml:mtable class="eqnarray" columnalign="left"><mml:mtr><mml:mtd><mml:mi>Q</mml:mi><mml:mo>=</mml:mo><mml:msub><mml:mrow><mml:mi>A</mml:mi></mml:mrow><mml:mrow><mml:mi>g</mml:mi><mml:mi>l</mml:mi><mml:mi>a</mml:mi><mml:mi>s</mml:mi><mml:msup><mml:mrow><mml:mi>s</mml:mi></mml:mrow><mml:mrow><mml:mo>*</mml:mo><mml:mtext>&#x000A0;</mml:mtext></mml:mrow></mml:msup></mml:mrow></mml:msub><mml:mrow><mml:mo>[</mml:mo><mml:mrow><mml:msub><mml:mrow><mml:mi>U</mml:mi></mml:mrow><mml:mrow><mml:mi>g</mml:mi><mml:mi>l</mml:mi><mml:mi>a</mml:mi><mml:mi>s</mml:mi><mml:msup><mml:mrow><mml:mi>s</mml:mi></mml:mrow><mml:mrow><mml:mo>*</mml:mo><mml:mtext>&#x000A0;</mml:mtext></mml:mrow></mml:msup></mml:mrow></mml:msub><mml:mrow><mml:mo stretchy="false">(</mml:mo><mml:mrow><mml:msub><mml:mrow><mml:mi>T</mml:mi></mml:mrow><mml:mrow><mml:mi>o</mml:mi></mml:mrow></mml:msub><mml:mo>-</mml:mo><mml:msub><mml:mrow><mml:mi>T</mml:mi></mml:mrow><mml:mrow><mml:mi>i</mml:mi></mml:mrow></mml:msub></mml:mrow><mml:mo stretchy="false">)</mml:mo></mml:mrow><mml:mo>&#x0002B;</mml:mo><mml:mrow><mml:mo stretchy="false">(</mml:mo><mml:mrow><mml:mi>S</mml:mi><mml:mi>H</mml:mi><mml:mi>G</mml:mi><mml:mi>F</mml:mi><mml:mo>*</mml:mo><mml:mi>S</mml:mi><mml:mi>C</mml:mi></mml:mrow><mml:mo stretchy="false">)</mml:mo></mml:mrow></mml:mrow><mml:mo>]</mml:mo></mml:mrow></mml:mtd></mml:mtr></mml:mtable></mml:math></disp-formula>
<p>where</p>
<list list-type="simple">
<list-item><p><italic>U</italic><sub><italic>glass</italic></sub> is the overall heat transfer coefficient</p></list-item>
<list-item><p><italic>A</italic><sub><italic>glass</italic></sub> is the area of the wall</p></list-item>
<list-item><p><italic>T</italic><sub><italic>o</italic></sub> &#x02212; <italic>T</italic><sub><italic>i</italic></sub> is the temperature difference between the outside and inside of the wall</p></list-item>
<list-item><p>SHGF is the solar heat gain factor</p></list-item>
<list-item><p>SC is the shading coefficient.</p></list-item>
</list>
<p>The sensible load, latent load, heat transfer by walls, doors, infiltration, appliances, and ventilation of each zone of the hospital is tabulated in <xref ref-type="table" rid="T2">Table 2</xref>.</p>
<table-wrap position="float" id="T2">
<label>Table 2</label>
<caption><p>Estimated thermal load for each zone in the hospital.</p></caption>
<table frame="hsides" rules="groups">
<thead><tr>
<th valign="top" align="left"><bold>Zones</bold></th>
<th valign="top" align="center"><bold>Offices</bold></th>
<th valign="top" align="center" colspan="3" style="border-bottom: thin solid #000000;"><bold>Internal Load (Watt)</bold></th>
<th style="border-bottom: thin solid #000000;"/>
<th style="border-bottom: thin solid #000000;"/>
<th valign="top" align="center" colspan="3" style="border-bottom: thin solid #000000;"><bold>External Load(Watt)</bold></th>
</tr>
<tr>
<th/>
<th/>
<th valign="top" align="center"><bold>Occupants</bold></th>
<th valign="top" align="center"><bold>Lighting</bold></th>
<th valign="top" align="center"><bold>Equipment</bold></th>
<th valign="top" align="center"><bold>Walls</bold></th>
<th valign="top" align="center"><bold>Roof</bold></th>
<th valign="top" align="center"><bold>Door</bold></th>
<th valign="top" align="center"><bold>Windows</bold></th>
<th valign="top" align="center"><bold>Infiltration</bold></th>
</tr>
</thead>
<tbody>
<tr>
<td valign="top" align="left"><bold>Zone 1</bold></td>
<td valign="top" align="center">1</td>
<td valign="top" align="center">900</td>
<td valign="top" align="center">291.8</td>
<td valign="top" align="center">787</td>
<td valign="top" align="center">9,231</td>
<td valign="top" align="center">255</td>
<td valign="top" align="center">117</td>
<td valign="top" align="center">513</td>
<td valign="top" align="center">1,739</td>
</tr>
<tr>
<td/>
<td valign="top" align="center">2</td>
<td valign="top" align="center">900</td>
<td valign="top" align="center">291.8</td>
<td valign="top" align="center">787</td>
<td valign="top" align="center">9,231</td>
<td valign="top" align="center">255</td>
<td valign="top" align="center">117</td>
<td valign="top" align="center">513</td>
<td valign="top" align="center">1,739</td>
</tr>
<tr>
<td/>
<td valign="top" align="center">3</td>
<td valign="top" align="center">500</td>
<td valign="top" align="center">291.8</td>
<td valign="top" align="center">422</td>
<td valign="top" align="center">7,457</td>
<td valign="top" align="center">244</td>
<td valign="top" align="center">177</td>
<td valign="top" align="center">513</td>
<td valign="top" align="center">1,940</td>
</tr>
<tr>
<td/>
<td valign="top" align="center">4</td>
<td valign="top" align="center">500</td>
<td valign="top" align="center">161</td>
<td valign="top" align="center">422</td>
<td valign="top" align="center">7,457</td>
<td valign="top" align="center">244</td>
<td valign="top" align="center">177</td>
<td valign="top" align="center">513</td>
<td valign="top" align="center">1,540</td>
</tr>
<tr>
<td/>
<td valign="top" align="center">5</td>
<td valign="top" align="center">500</td>
<td valign="top" align="center">161</td>
<td valign="top" align="center">422</td>
<td valign="top" align="center">7,457</td>
<td valign="top" align="center">244</td>
<td valign="top" align="center">177</td>
<td valign="top" align="center">513</td>
<td valign="top" align="center">1,540</td>
</tr>
<tr>
<td/>
<td valign="top" align="center">Patient ward</td>
<td valign="top" align="center">9,925</td>
<td valign="top" align="center">734</td>
<td valign="top" align="center">1,080</td>
<td valign="top" align="center">19,066</td>
<td valign="top" align="center">238</td>
<td valign="top" align="center">165</td>
<td valign="top" align="center">1,012</td>
<td valign="top" align="center">1,925</td>
</tr>
<tr>
<td/>
<td valign="top" align="center">ICU ward</td>
<td valign="top" align="center">8,125</td>
<td valign="top" align="center">659</td>
<td valign="top" align="center">1,060</td>
<td valign="top" align="center">1,194</td>
<td valign="top" align="center">238</td>
<td valign="top" align="center">165</td>
<td valign="top" align="center">1,012</td>
<td valign="top" align="center">1,924</td>
</tr>
<tr>
<td valign="top" align="left"><bold>Zone 2</bold></td>
<td valign="top" align="center">Radiology</td>
<td valign="top" align="center">720</td>
<td valign="top" align="center">270</td>
<td valign="top" align="center">976</td>
<td valign="top" align="center">9,435</td>
<td valign="top" align="center">290</td>
<td valign="top" align="center">154</td>
<td valign="top" align="center">167</td>
<td valign="top" align="center">1,434</td>
</tr>
<tr>
<td/>
<td valign="top" align="center">G. Laboratory</td>
<td valign="top" align="center">700</td>
<td valign="top" align="center">310</td>
<td valign="top" align="center">965</td>
<td valign="top" align="center">1,053</td>
<td valign="top" align="center">255</td>
<td valign="top" align="center">177</td>
<td valign="top" align="center">513</td>
<td valign="top" align="center">1,639</td>
</tr>
<tr>
<td/>
<td valign="top" align="center">S. Laboratory</td>
<td valign="top" align="center">700</td>
<td valign="top" align="center">240</td>
<td valign="top" align="center">780</td>
<td valign="top" align="center">1,053</td>
<td valign="top" align="center">255</td>
<td valign="top" align="center">177</td>
<td valign="top" align="center">513</td>
<td valign="top" align="center">1,539</td>
</tr>
<tr>
<td valign="top" align="left"><bold>Zone 3</bold></td>
<td valign="top" align="center">OT</td>
<td valign="top" align="center">915</td>
<td valign="top" align="center">559</td>
<td valign="top" align="center">685</td>
<td valign="top" align="center">1,785</td>
<td valign="top" align="center">306</td>
<td valign="top" align="center">212</td>
<td valign="top" align="center">0</td>
<td valign="top" align="center">9,941</td>
</tr>
<tr>
<td/>
<td valign="top" align="center">Pharmacy</td>
<td valign="top" align="center">690</td>
<td valign="top" align="center">298</td>
<td valign="top" align="center">308</td>
<td valign="top" align="center">9,599</td>
<td valign="top" align="center">238</td>
<td valign="top" align="center">165</td>
<td valign="top" align="center">177</td>
<td valign="top" align="center">4,224</td>
</tr>
<tr>
<td valign="top" align="left"><bold>Zone 4</bold></td>
<td valign="top" align="center">Washrooms</td>
<td valign="top" align="center">450</td>
<td valign="top" align="center">170</td>
<td valign="top" align="center">220</td>
<td valign="top" align="center">8,467</td>
<td valign="top" align="center">198</td>
<td valign="top" align="center">210</td>
<td valign="top" align="center">476</td>
<td valign="top" align="center">2,091</td>
</tr>
<tr>
<td valign="top" align="center" colspan="2"><bold>Total load</bold></td>
<td valign="top" align="center" colspan="3">39576.4 (39.57 kW)</td>
<td/>
<td valign="top" align="center" colspan="4">137,585 (137.85 kW)</td>
</tr>
<tr>
<td/>
<td/>
<td/>
<td valign="top" align="center" colspan="7"><bold>51TR (Ton of refrigeration)</bold></td>
</tr>
</tbody>
</table>
</table-wrap>
<p>So, the estimated total thermal load of the hospital building ought to be 51TR. Furthermore, the NZEB model of the selected hospital buildings will be developed in HOMER Pro software to check the feasibility and profitability of the hybrid NZEBs. In <xref ref-type="fig" rid="F5">Figure 5</xref>, a proposed schematic for the conversion of the selected hospital into a hybrid NZE hospital is illustrated.</p>
<fig id="F5" position="float">
<label>Figure 5</label>
<caption><p>Proposed hybrid on a grid system for a hospital.</p></caption>
<graphic xlink:href="fenrg-09-668908-g0005.tif"/>
</fig>
<p>The proposed hybrid system consists of PV modules, batteries, and a grid. The solar system will supply power as an alternative power resource. Power generated by solar modules will be stored by batteries. In case of a shortage of power, to meet the load demand, the required power will be fulfilled by the grid. Similarly, in the case of excess power generation, power will be transmitted to the grid.</p>
</sec>
</sec>
<sec id="s5">
<title>Homer Program</title>
<p>HOMER is one of the best tools for designing renewable-energy-based systems. Moreover, it can simulate the operations of a hybrid system for an entire year in time steps from 1 min to 1 h. It also enables us to compare and evaluate the disadvantages and advantages of economic and technical features. In HOMER, the design process is performed in three steps: simulation, optimization, and sensitivity analysis. In this paper, all three processes are followed to get the best overview of the feasibility of NZEBs in Pakistan.</p>
</sec>
<sec id="s6">
<title>Model Development of Hybrid NZEB Hospital Building</title>
<p>NZEB model development of the current hospital building in HOMER is illustrated in <xref ref-type="fig" rid="F6">Figure 6</xref>. The yearly thermal load and solar irradiation potential of the building are the input parameters for HOMER.</p>
<fig id="F6" position="float">
<label>Figure 6</label>
<caption><p>Schematic of hybrid NZEB hospital building in HOMER Pro.</p></caption>
<graphic xlink:href="fenrg-09-668908-g0006.tif"/>
</fig>
<sec>
<title>Available Solar Radiations</title>
<p>For the NZEB feasibility analysis, the available solar radiations are estimated for the selected location in Pakistan. For the location of latitude 33.43&#x000B0;N and longitude 72.8397&#x000B0;E, maximum solar radiation and average solar radiation were estimated to be 5.5 and 5 kWh/m<sup>2</sup>/day, respectively. The current position has excellent solar potential for producing energy using PV for the development of NZEB. <xref ref-type="fig" rid="F7">Figure 7</xref> shows solar radiation and a clearness index profile by using HOMER Pro.</p>
<fig id="F7" position="float">
<label>Figure 7</label>
<caption><p>Available solar radiations for Pakistan.</p></caption>
<graphic xlink:href="fenrg-09-668908-g0007.tif"/>
</fig>
<p>In this study, the first step was to estimate yearly thermal load and defining peak load season. So, using statistical data obtained by Solarimeter and performing simulation in HOMER Pro, the daily load profile of the hospital in Taxila, Pakistan, was obtained and is shown in <xref ref-type="fig" rid="F8">Figure 8</xref>. According to estimated thermal data, in the month of July, the energy demand is highest due to high usage of air-conditioning. The monthly profile of thermal data is given in <xref ref-type="fig" rid="F8">Figure 8</xref>. <xref ref-type="fig" rid="F8">Figure 8</xref> also presents the highest and lowest energy consumption in every month of the entire year.</p>
<fig id="F8" position="float">
<label>Figure 8</label>
<caption><p>Thermal load profile of 53 ton hospital in Taxila, Pakistan.</p></caption>
<graphic xlink:href="fenrg-09-668908-g0008.tif"/>
</fig>
<p>Additionally, it can be seen that the hospital building reaches an optimum energy consumption of about 177 kW in the summer months, i.e., June, July, and August. <xref ref-type="fig" rid="F8">Figure 8</xref> shows the thermal load profile of each month simulated in HOMER Pro. The total thermal load estimated for the hospital building in Taxila is 53 Ton. This is the required need of air-conditioning of the building.</p>
</sec>
<sec>
<title>Hourly Load Demand Curves</title>
<p>The thermal load profile is generated for 24 h, 365 days a year, in HOMER Pro. Thermal load profile depends on calculated thermal data and input solar data of the selected location. There are various types of thermal loads, i.e., fan, CFL, printers, computers, ECG machine, BP apparatus, X-ray machine, and TV, and they are used in hospital buildings. The electrical load consumption of the building for 24 h is calculated. <xref ref-type="fig" rid="F9">Figure 9</xref> shows scaled thermal load data 24 h per day for the entire year.</p>
<fig id="F9" position="float">
<label>Figure 9</label>
<caption><p>Daily thermal load consumption of hospital building.</p></caption>
<graphic xlink:href="fenrg-09-668908-g0009.tif"/>
</fig>
</sec>
</sec>
<sec id="s7">
<title>PV System Design</title>
<p>Solar radiation is converted directly into DC by using PV modules. So, the deviation of the output of the electrical power produced by PV modules is estimated using Equation (10). The output energy of a PV module is dependent on several parameters, including the following: the structure of cell type, nominal performance of the PV panel, solar radiation, derating factor, solar cell temperature, climatic conditions at the panel area, temperature coefficient, and weather conditions (Fritjof and Asplan Viak, <xref ref-type="bibr" rid="B18">2014</xref>).</p>
<disp-formula id="E10"><label>(10)</label><mml:math id="M10"><mml:mtable class="eqnarray" columnalign="left"><mml:mtr><mml:mtd><mml:msub><mml:mrow><mml:mi>P</mml:mi></mml:mrow><mml:mrow><mml:mi>p</mml:mi><mml:mi>v</mml:mi><mml:mtext>&#x000A0;</mml:mtext><mml:mo>=</mml:mo><mml:mtext>&#x000A0;</mml:mtext></mml:mrow></mml:msub><mml:msub><mml:mrow><mml:mi>Y</mml:mi></mml:mrow><mml:mrow><mml:mi>P</mml:mi><mml:mi>V</mml:mi><mml:mtext>&#x000A0;</mml:mtext></mml:mrow></mml:msub><mml:mo>&#x000D7;</mml:mo><mml:msub><mml:mrow><mml:mi>f</mml:mi></mml:mrow><mml:mrow><mml:mi>p</mml:mi><mml:mi>v</mml:mi></mml:mrow></mml:msub><mml:mtext>&#x000A0;</mml:mtext><mml:mrow><mml:mo stretchy="true">(</mml:mo><mml:mrow><mml:mfrac><mml:mrow><mml:mover accent="false" class="mml-overline"><mml:mrow><mml:msub><mml:mrow><mml:mi>G</mml:mi></mml:mrow><mml:mrow><mml:mi>T</mml:mi></mml:mrow></mml:msub></mml:mrow><mml:mo accent="true">&#x000AF;</mml:mo></mml:mover></mml:mrow><mml:mrow><mml:mover accent="false" class="mml-overline"><mml:mrow><mml:msub><mml:mrow><mml:mi>G</mml:mi></mml:mrow><mml:mrow><mml:mi>T</mml:mi><mml:mo>,</mml:mo><mml:mi>S</mml:mi><mml:mi>T</mml:mi><mml:mi>C</mml:mi></mml:mrow></mml:msub></mml:mrow><mml:mo accent="true">&#x000AF;</mml:mo></mml:mover></mml:mrow></mml:mfrac></mml:mrow><mml:mo stretchy="true">)</mml:mo></mml:mrow><mml:mtext>&#x000A0;</mml:mtext><mml:mrow><mml:mo>[</mml:mo><mml:mrow><mml:mn>1</mml:mn><mml:mo>&#x0002B;</mml:mo><mml:msub><mml:mrow><mml:mi>&#x003B1;</mml:mi></mml:mrow><mml:mrow><mml:mi>P</mml:mi></mml:mrow></mml:msub><mml:mrow><mml:mo stretchy="true">(</mml:mo><mml:mrow><mml:msub><mml:mrow><mml:mi>T</mml:mi></mml:mrow><mml:mrow><mml:mi>C</mml:mi></mml:mrow></mml:msub><mml:mo>-</mml:mo><mml:mtext>&#x000A0;</mml:mtext><mml:msub><mml:mrow><mml:mi>T</mml:mi></mml:mrow><mml:mrow><mml:mi>C</mml:mi><mml:mo>,</mml:mo><mml:mi>S</mml:mi><mml:mi>T</mml:mi><mml:mi>C</mml:mi></mml:mrow></mml:msub></mml:mrow><mml:mo stretchy="true">)</mml:mo></mml:mrow></mml:mrow><mml:mo>]</mml:mo></mml:mrow></mml:mtd></mml:mtr></mml:mtable></mml:math></disp-formula>
<p>where;</p>
<list list-type="simple">
<list-item><p><italic>Y</italic><sub><italic>PV</italic></sub> is the rated capacity of the PV array, meaning its power output under standard test conditions (kW),</p></list-item>
<list-item><p><italic>f</italic><sub><italic>pv</italic></sub> is the PV derating factor (%),</p></list-item>
<list-item><p><inline-formula><mml:math id="M11"><mml:mover accent="false" class="mml-overline"><mml:mrow><mml:msub><mml:mrow><mml:mi>G</mml:mi></mml:mrow><mml:mrow><mml:mi>T</mml:mi></mml:mrow></mml:msub></mml:mrow><mml:mo accent="true">&#x000AF;</mml:mo></mml:mover></mml:math></inline-formula> is the solar radiation incident on the PV array in the current time step (kW/m2),</p></list-item>
<list-item><p><italic>G</italic><sub><italic>T,STC</italic></sub> is the incident radiation at standard test conditions (1 kW/m2),</p></list-item>
<list-item><p><italic>&#x003B1;</italic><sub><italic>P</italic></sub> is the temperature coefficient of power (%/&#x000B0;C),</p></list-item>
<list-item><p><italic>T</italic><sub><italic>C</italic></sub> is the PV cell temperature in the current time step (&#x000B0;C), and</p></list-item>
<list-item><p><italic>T</italic><sub><italic>C,STC</italic></sub> is the PV cell temperature under standard test conditions (25&#x000B0;C).</p></list-item>
</list>
<sec>
<title>Grid Information</title>
<p>In this study, PV panels and converters are two main components of the system. A proposed system is designed, and it consists of 220 kW PV modules and 226 kW converters shown in <xref ref-type="fig" rid="F9">Figure 9</xref>. According to the results, for the hospital building, a peak load of 319.2 kW is observed. However, the average electricity consumption is 3336.07 kWh/d.</p>
</sec>
<sec>
<title>Design of Solar Module</title>
<p>In this study, 220 kW solar modules are used in combination with multiple PV solar panels. PV modules are polycrystalline and have a maximum rated power of 250 W, a nominal tension of 29.8 V, and an operating current of 8.71 A. Also, the installation cost of solar modules in Pakistan is thought to be 76,154 USD/kW with a life of 25 years. In <xref ref-type="table" rid="T3">Table 3</xref>, all the design parameters for the solar system are given.</p>
<table-wrap position="float" id="T3">
<label>Table 3</label>
<caption><p>Solar system design parameters for hospital building.</p></caption>
<table frame="hsides" rules="groups">
<thead><tr>
<th valign="top" align="left"><bold>Design parameters</bold></th>
<th valign="top" align="center"><bold>Estimated values</bold></th>
</tr>
</thead>
<tbody>
<tr>
<td valign="top" align="left">Manufacturer</td>
<td valign="top" align="center">Jinko solar</td>
</tr>
<tr>
<td valign="top" align="left">Panel type</td>
<td valign="top" align="center">Flat plate</td>
</tr>
<tr>
<td valign="top" align="left">Capital cost (USD)</td>
<td valign="top" align="center">63461.53</td>
</tr>
<tr>
<td valign="top" align="left">Replacement cost (USD)</td>
<td valign="top" align="center">31730.76</td>
</tr>
<tr>
<td valign="top" align="left">Operation &#x00026; Maintenance cost (USD/year)</td>
<td valign="top" align="center">17628.20</td>
</tr>
<tr>
<td valign="top" align="left">De-Rating Factor (%)</td>
<td valign="top" align="center">85</td>
</tr>
<tr>
<td valign="top" align="left">Rated Capacity (kW)</td>
<td valign="top" align="center">250</td>
</tr>
<tr>
<td valign="top" align="left">Lifetime (years)</td>
<td valign="top" align="center">25</td>
</tr>
<tr>
<td valign="top" align="left">Slope (Degree)</td>
<td valign="top" align="center">24.5</td>
</tr>
<tr>
<td valign="top" align="left">Maximum power voltage (V)</td>
<td valign="top" align="center">30.3</td>
</tr>
<tr>
<td valign="top" align="left">Maximum power current (A)</td>
<td valign="top" align="center">8.21</td>
</tr>
<tr>
<td valign="top" align="left">Open circuit voltage (V)</td>
<td valign="top" align="center">35.5</td>
</tr>
<tr>
<td valign="top" align="left">Short circuit current (A)</td>
<td valign="top" align="center">8.21</td>
</tr>
</tbody>
</table>
</table-wrap>
<p>Jinko solar manufacturers are the top-rated solar component providers in Pakistan. Moreover, flat-plate PV modules can be installed after the designing phase. The estimated capital cost is $63,462, the replacement cost is $3,173, the O&#x00026;M cost is $1,7628/y, the hours of operation are 4,385/y, the PV penetration is 29%, and the total lifespan of the modules is 25 years, as shown in <xref ref-type="fig" rid="F10">Figure 10</xref>. Also, <xref ref-type="fig" rid="F11">Figure 11</xref> explains the mean output of solar modules (40.3 kW), maximum output (174 kW), and the capacity factor of energy production (21.8%).</p>
<fig id="F10" position="float">
<label>Figure 10</label>
<caption><p>Hybrid NZEB schematic for selected building in HOMER Pro.</p></caption>
<graphic xlink:href="fenrg-09-668908-g0010.tif"/>
</fig>
<fig id="F11" position="float">
<label>Figure 11</label>
<caption><p>PV power output of the proposed system.</p></caption>
<graphic xlink:href="fenrg-09-668908-g0011.tif"/>
</fig>
</sec>
<sec>
<title>Converter</title>
<p>For the conversion of DC to AC, a converter is used. This function is executed using a bidirectional energy converter within a microgrid. As per the generated output, usage, and storage factors of electrical energy in microgrid, the converter functions as both a rectifier and an inverter. Usually, a converter has 80% efficiency and is evaluated on the basis of solar module selection.</p>
<disp-formula id="E11"><label>(11)</label><mml:math id="M12"><mml:mtable class="eqnarray" columnalign="left"><mml:mtr><mml:mtd><mml:msub><mml:mrow><mml:mi>C</mml:mi></mml:mrow><mml:mrow><mml:mtext>Converter</mml:mtext></mml:mrow></mml:msub><mml:mo>=</mml:mo><mml:msub><mml:mrow><mml:mi>P</mml:mi></mml:mrow><mml:mrow><mml:mtext>array</mml:mtext></mml:mrow></mml:msub><mml:mo>&#x000D7;</mml:mo><mml:mn>100</mml:mn><mml:mo>/</mml:mo><mml:mn>80</mml:mn></mml:mtd></mml:mtr></mml:mtable></mml:math></disp-formula>
<disp-formula id="E12"><label>(12)</label><mml:math id="M13"><mml:msub><mml:mtext>C</mml:mtext><mml:mrow><mml:mtext>Converter</mml:mtext></mml:mrow></mml:msub><mml:mtext>&#x000A0;=&#x000A0;&#x000A0;22kW</mml:mtext><mml:mo>&#x000D7;</mml:mo><mml:mtext>1</mml:mtext><mml:mo>.</mml:mo><mml:mtext>18&#x000A0;=&#x000A0;25</mml:mtext><mml:mo>.</mml:mo><mml:mtext>96&#x000A0;</mml:mtext><mml:mo>&#x02248;</mml:mo><mml:mtext>&#x000A0;26kW</mml:mtext></mml:math></disp-formula>
<p>A hybrid NZEB system is proposed when undergoing research in order to share Peak thermal load. Moreover, nine converters of 26 kW capacities were selected for the PV field of 226 kW. The initial cost of one converter is 18.35 USD/kW, and it provides an efficiency of 90%.</p>
</sec>
<sec>
<title>Optimization Process</title>
<p>The aim of the current research was to obtain an optimized hybrid NZE system for a hospital building. HOMER performs several optimizations under a range of input variables to determine the effect of uncertainty. Optimization estimates the optimal value of variables on which the system has the best performance (Fritjof and Asplan Viak, <xref ref-type="bibr" rid="B18">2014</xref>). HOMER gives the best possible combination of modules that will fulfill particular electrical and thermal loads (Jaman et al., <xref ref-type="bibr" rid="B24">2010</xref>). <xref ref-type="fig" rid="F12">Figure 12</xref> shows a flowchart of the optimization process for obtaining an optimized NZEB system for hospital building using HOMER in this study.</p>
<fig id="F12" position="float">
<label>Figure 12</label>
<caption><p>Configuration of optimization of NZEB performance parameters.</p></caption>
<graphic xlink:href="fenrg-09-668908-g0012.tif"/>
</fig>
<p>For optimum results using HOMER software, the selected variables are thermal load and solar data. For calculation of discount factor, the discount rate is 15%,the rate of inflation is 6.8%, the fuel cost escalation rate is 4.10%, and the interest rate is 11% (Giyler and Lilienpthal, <xref ref-type="bibr" rid="B19">2005</xref>; Tahir Masood and Shah, <xref ref-type="bibr" rid="B51">2012</xref>; Singh et al., <xref ref-type="bibr" rid="B48">2015</xref>) in Pakistan. Solar panels generally have a life between 25 and 30 years (Sen and Bhattacharyya, <xref ref-type="bibr" rid="B44">2014</xref>). <xref ref-type="table" rid="T4">Table 4</xref> shows constraints used in optimization.</p>
<table-wrap position="float" id="T4">
<label>Table 4</label>
<caption><p>Optimization constraints in HOMER Software.</p></caption>
<table frame="hsides" rules="groups">
<tbody>
<tr>
<td valign="top" align="left">Operating reserves as a percentage of hourly load</td>
<td valign="top" align="center">0.1</td>
</tr>
<tr>
<td valign="top" align="left">Operating reserves as a percentage of Peak load</td>
<td valign="top" align="center">0</td>
</tr>
<tr>
<td valign="top" align="left">Operating reserves as a percentage Solar Power</td>
<td valign="top" align="center">0.25</td>
</tr>
<tr>
<td valign="top" align="left">Output</td>
<td/>
</tr>
<tr>
<td valign="top" align="left">Renewable fraction covered by the PV system</td>
<td valign="top" align="center">0&#x02013;75%</td>
</tr>
</tbody>
</table>
</table-wrap>
</sec>
</sec>
<sec id="s8">
<title>Results and Discussion</title>
<p>Economic evaluation for NZEB conversion of a hospital building is performed by three main operations of HOMER software: simulation, optimization, and sensitivity analysis. In the current section, different obtained results will be discussed.</p>
<sec>
<title>Cost and Production Details of PV Panels and Converters</title>
<p>By way of careful analysis, the price of the 325 W panel in Pakistan is found to be $43.66USD. Additionally, the inverter mean output is 37.4 kW, the capital cost $0.082 million, and the production by PV panels ranged from 280,498 to 344,733 kWh for different solar irradiances given in <xref ref-type="table" rid="T5">Table 5</xref>.</p>
<table-wrap position="float" id="T5">
<label>Table 5</label>
<caption><p>Cost and production details of PV panels and converters for Pakistan.</p></caption>
<table frame="hsides" rules="groups">
<tbody><tr>
<td valign="top" align="left">Capital Cost (USD)</td>
<td valign="top" align="center">81,226</td>
<td valign="top" align="center">81,226</td>
<td valign="top" align="center">81,226</td>
<td valign="top" align="center">81,226</td>
<td valign="top" align="center" style="background-color:#d5e3bd">81,226</td>
<td valign="top" align="center">81,226</td>
</tr>
<tr>
<td valign="top" align="left">Production (kWh)</td>
<td valign="top" align="center">300,675</td>
<td valign="top" align="center">294,004</td>
<td valign="top" align="center">280,498</td>
<td valign="top" align="center">352,621</td>
<td valign="top" align="center" style="background-color:#d5e3bd">344,733</td>
<td valign="top" align="center">328,765</td>
</tr>
<tr>
<td valign="top" align="left">Converter (Inverter mean output in Pakistan) (kW)</td>
<td valign="top" align="center">32.6</td>
<td valign="top" align="center">31.9</td>
<td valign="top" align="center">30.0</td>
<td valign="top" align="center">38.2</td>
<td valign="top" align="center" style="background-color:#d5e3bd">37.4</td>
<td valign="top" align="center">35.7</td>
</tr>
</tbody>
</table>
<table-wrap-foot>
<p><italic>Colored values are optimized and selected values for the proposed system</italic>.</p>
</table-wrap-foot>
</table-wrap>
</sec>
<sec>
<title>Influence of Economic Indicators on Feasibility of Non-re NZEBs</title>
<p>In <xref ref-type="table" rid="T6">Table 6</xref>, the NPC, operating costs, initial capital costs, and sell-back rate are given. NPC ranges from $20.41 to $21.63 million. The operating cost for the whole installation is $0.151 million. However, initial capital cost is $0.111 million. The sell-back rate after adaptation of the NZEB system is 0.11 USD/kWh.</p>
<table-wrap position="float" id="T6">
<label>Table 6</label>
<caption><p>Net present costs of the system for installation of NZEB.</p></caption>
<table frame="hsides" rules="groups">
<tbody>
<tr>
<td valign="top" align="left">NPC (MUSD)</td>
<td valign="top" align="center">21.30</td>
<td valign="top" align="center">21.39</td>
<td valign="top" align="center">21.63</td>
<td valign="top" align="center">20.41</td>
<td valign="top" align="center" style="background-color:#d5e3bd"><bold>20.49</bold></td>
<td valign="top" align="center">20.81</td>
</tr>
<tr>
<td valign="top" align="left" colspan="7">Operating</td>
</tr>
<tr>
<td valign="top" align="left">Cost(MUSD)</td>
<td valign="top" align="center">0.156</td>
<td valign="top" align="center">0.156</td>
<td valign="top" align="center">0.159</td>
<td valign="top" align="center">0.149</td>
<td valign="top" align="center" style="background-color:#d5e3bd"><bold>0.151</bold></td>
<td valign="top" align="center">0.152</td>
</tr>
<tr style="border-top: thin solid #000000;">
<td valign="top" align="left">Initial capital cost</td>
<td valign="top" align="center">0.111</td>
<td valign="top" align="center">0.111</td>
<td valign="top" align="center">0.111</td>
<td valign="top" align="center">0.111</td>
<td valign="top" align="center" style="background-color:#d5e3bd">0.111</td>
<td valign="top" align="center">0.111</td>
</tr>
<tr>
<td valign="top" align="left" colspan="7">(MUSD)</td>
</tr>
<tr>
<td valign="top" align="left" colspan="7">Sell back rate</td>
</tr>
<tr>
<td valign="top" align="left">in Pakistan</td>
<td valign="top" align="center">0.11</td>
<td valign="top" align="center">0.11</td>
<td valign="top" align="center">0.11</td>
<td valign="top" align="center">0.11</td>
<td valign="top" align="center" style="background-color:#d5e3bd"><bold>0.11</bold></td>
<td valign="top" align="center">0.11</td>
</tr>
</tbody>
</table>
<table-wrap-foot>
<p><italic>Bold values are optimized and selected values for the proposed system. Colored values are optimized and selected values for the proposed system</italic>.</p>
</table-wrap-foot>
</table-wrap>
</sec>
<sec>
<title>Optimized NZEB Design</title>
<p><xref ref-type="table" rid="T7">Table 7</xref> shows the best optimal values for the solar-powered optimal system for the selected buildings in terms of the NPC, operating cost, and capital cost.</p>
<table-wrap position="float" id="T7">
<label>Table 7</label>
<caption><p>Solar powered optimized system.</p></caption>
<table frame="hsides" rules="groups">
<thead><tr>
<th/>
<th valign="top" align="center"><bold>Cost (MUSD)</bold></th>
</tr>
</thead>
<tbody>
<tr>
<td valign="top" align="left">Capital cost</td>
<td valign="top" align="center">0.082</td>
</tr>
<tr>
<td valign="top" align="left">NPC</td>
<td valign="top" align="center">2.04</td>
</tr>
<tr>
<td valign="top" align="left">Operating cost</td>
<td valign="top" align="center">0.15</td>
</tr>
</tbody>
</table>
</table-wrap>
<p>The optimized NZEB system has a capital cost of $0.082 million, operating cost of $0.15 million, and an optimized NPC value of $2.04 million. Additionally, the sell-back rate is 0.11 USDkW.</p>
</sec>
<sec>
<title>Electricity Generation Comparison Between PV and Grid</title>
<p><xref ref-type="fig" rid="F13">Figure 13</xref> is a representation of the monthly electricity production by PV and grid. The green bar shows the power generated by PV, whereas the orange bar represents power produced by the grid. In the proposed system, 70.7% of the production is due to PV and 28.3% is produced by the grid, as shown in <xref ref-type="fig" rid="F12">Figure 12</xref>. Total operational hours are 4,385 in a year. In Pakistan, the unit price of electricity from the grid is 0.14 USD/kWh; however, the unit price of electricity obtained by hybrid PV is thought to be 0.12 USD/kWh. Additionally, the obtained total cost of production of electricity by the hybrid system is &#x0007E;$0.102 million. Though, initially, when the system was operating only by grid, the annual cost of production of electricity was $0.114 million. So, by installing the hybrid NZEB system, an annual profit of 10.24% can be obtained. Similarly, in another study of the optimization process for the estimation of energy efficiency of drying plant. The use of a thermodynamics laws analysis was 35.40% efficient, which is 10.11% more efficient (Taner, <xref ref-type="bibr" rid="B55">2015b</xref>).</p>
<fig id="F13" position="float">
<label>Figure 13</label>
<caption><p>Average monthly electricity production by PV and grid.</p></caption>
<graphic xlink:href="fenrg-09-668908-g0013.tif"/>
</fig>
</sec>
<sec>
<title>Feasibility of Commercial NZEBs in Pakistan</title>
<p>The feasibility of any project depends on the percentage of the profit and payback period. This section describes the feasibility of commercial NZEBs in Pakistan.</p>
<sec>
<title>Cost of Electricity (COE)</title>
<p><xref ref-type="fig" rid="F14">Figure 14</xref> shows the surface plots of the cost of electricity (COE) in HOMER Pro. The cost of energy is reduced with the increase in the intensity of solar radiation. Also, the COE is reduced from $0.135 to $0.128 million for selected buildings.</p>
<fig id="F14" position="float">
<label>Figure 14</label>
<caption><p>Cost of electricity (COE).</p></caption>
<graphic xlink:href="fenrg-09-668908-g0014.tif"/>
</fig>
</sec>
<sec>
<title>Payback Period</title>
<p>After the optimization of the system, the basic objective of the research was to check the feasibility and profitability of the proposed hybrid system. HOMER Pro software works as a black box and simulates several input data. According to the results as shown in <xref ref-type="fig" rid="F15">Figure 15</xref>. the payback period of the proposed system is 2.53y after the installation of the 185 kW hybrid PV system, while the return on investment is 38.9%.</p>
<fig id="F15" position="float">
<label>Figure 15</label>
<caption><p>Results of payback period in HOMER Pro software.</p></caption>
<graphic xlink:href="fenrg-09-668908-g0015.tif"/>
</fig>
</sec>
</sec>
</sec>
<sec sec-type="conclusions" id="s9">
<title>Conclusion</title>
<p>The current study is an economic evaluation and feasibility analysis of hybrid microgrid NZEB. A hybrid PV power system is created to supply energy to the hospital building located in Taxila, Pakistan. The objectives were to decrease the total electricity price and feasibility analysis of hybrid NZEBs in Pakistan for non-residential buildings. To attain maximum advantage from the proposed hybrid NZEB system, the designing of the building, calculation of thermal load, simulation, and optimization of the suggested hybrid microgrid NZEB were all performed in HOMER Pro. An optimal range of design parameters was acquired using thermal data and solar irradiance as input. Additionally, an economic analysis was performed to evaluate the feasibility of the proposed hybrid system over the duration of 25y. The main findings of the current system were as follows: solar radiation potential, operating cost, initial capital cost, the energy produced by PV, payback period, and net present cost. The optimal NPC of the proposed NZEB is $20.49 million, the operating cost for the whole installation of a hybrid NZEB system is $0.151 million, and the initial capital cost is $0.111 million. By adaptation of the hybrid NZEB system, the electricity unit price has dropped from 0.14 to 0.12 USD/kWh. The maximum electricity generation by PV panels is 344,733 kWh. Consequently, the proposed hybrid NZEB system is economically 10.24% more profitable than the grid system only. Moreover, the proposed NZEB system has a payback period of 2.53y, thereby making it a cost-efficient and economically feasible method. Primarily, on the basis of the analysis of all the above-stated variables, it may be concluded that the current design is able to satisfy the aim and objectives of the current research by making renewable energy a viable solution to the energy shortages in Pakistan. The developed framework will assist in the decision-making of feasibility analyses and economic evaluation of NZEBs in Pakistan. Also, it will facilitate municipal and provincial planners in NZE community planning. This work will be further supported by the implementation of a federal renewable energy plan, which could act as a long-term roadmap for sustainable community planning.</p>
</sec>
<sec sec-type="data-availability-statement" id="s10">
<title>Data Availability Statement</title>
<p>The original contributions presented in the study are included in the article/supplementary material, further inquiries can be directed to the corresponding author/s.</p>
</sec>
<sec id="s11">
<title>Author&#x00027;s Note</title>
<p>By literature review it can be inferred that development of NZEBs is not a common practice in underdeveloped countries. Likewise, there is no set regulations and targets related to renewable energy usage in building sector. Also, only a few researches were based on the actual measurement performance and efficiency of NZE hospitals in Asia and none in Pakistan. Furthermore, the previous studies and pre existing energy planning modules neglect the importance of renewable energy for commercial sector in Pakistan. Therefore, the ensuing renewable energy solutions are actually deterministic. Moreover, IEA have outlined 13 tasks for the development, performance and analysis of NZEBs in (OECD) countries. Pakistan is not an associated member of the International Energy Agency (IEA). Therefore, there is a dire need of research on energy efficient non residential buildings as per task 47 which is not available in Pakistan. Hence, current research will be the feasibility analysis of an efficient and effective grid connected NZEB model for a hospital using efficient optimization technique along with intelligent simulation and modeling method in accordance with the International Energy Agency (IEA) standards in Pakistan.</p>
</sec>
<sec id="s12">
<title>Author Contributions</title>
<p>All authors listed have made a substantial, direct and intellectual contribution to the work, and approved it for publication.</p>
</sec>
<sec sec-type="COI-statement" id="conf1">
<title>Conflict of Interest</title>
<p>The authors declare that the research was conducted in the absence of any commercial or financial relationships that could be construed as a potential conflict of interest.</p>
</sec>
</body>
<back>
<ref-list>
<title>References</title>
<ref id="B1">
<citation citation-type="web"><person-group person-group-type="author"><collab>AIA</collab></person-group> (<year>2011</year>). <source>The 2030 Commitment</source>. Available online at: <ext-link ext-link-type="uri" xlink:href="https://architecture2030.org/2030_challenges/2030-challenge/">https://architecture2030.org/2030_challenges/2030-challenge/</ext-link> (assessed October 11, 2019).</citation></ref>
<ref id="B2">
<citation citation-type="journal"><person-group person-group-type="author"><name><surname>AlAjmi</surname> <given-names>A.</given-names></name> <name><surname>Abou-Ziyan</surname> <given-names>H.</given-names></name> <name><surname>Ghoneim</surname> <given-names>A.</given-names></name></person-group> (<year>2016</year>). <article-title>Achieving annual and monthly net-zero energy of existing building in hot climate</article-title>. <source>Appl. Energy</source> <volume>165</volume>:<fpage>511</fpage>&#x02013;<lpage>521</lpage>. <pub-id pub-id-type="doi">10.1016/j.apenergy.2015.11.073</pub-id></citation></ref>
<ref id="B3">
<citation citation-type="journal"><person-group person-group-type="author"><name><surname>Alfano</surname> <given-names>F. R. D.</given-names></name> <name><surname>Olesen</surname> <given-names>B. W.</given-names></name> <name><surname>Palella</surname> <given-names>B. I.</given-names></name></person-group> (<year>2017</year>). <article-title>Povl ole fanger&#x00027;s impact ten years later</article-title>. <source>Energy Build</source>. <volume>15</volume>, <fpage>243</fpage>&#x02013;<lpage>249</lpage>. <pub-id pub-id-type="doi">10.1016/j.enbuild.2017.07.052</pub-id></citation></ref>
<ref id="B4">
<citation citation-type="journal"><person-group person-group-type="author"><name><surname>Alfano</surname> <given-names>F. R. D. A.</given-names></name> <name><surname>Olesen</surname> <given-names>B. W.</given-names></name> <name><surname>Palella</surname> <given-names>B. I.</given-names></name> <name><surname>Riccio</surname> <given-names>G.</given-names></name></person-group> (<year>2014</year>). <article-title>Thermal comfort: design and assessment for energy saving</article-title>. <source>Energy Build.</source> <volume>81</volume>, <fpage>326</fpage>&#x02013;<lpage>336</lpage>. <pub-id pub-id-type="doi">10.1016/j.enbuild.2014.06.033</pub-id></citation></ref>
<ref id="B5">
<citation citation-type="journal"><person-group person-group-type="author"><name><surname>Alhorr</surname> <given-names>Y.</given-names></name> <name><surname>Arif</surname> <given-names>M.</given-names></name> <name><surname>Bano</surname> <given-names>T.</given-names></name> <name><surname>Egbu</surname> <given-names>C.</given-names></name> <name><surname>Mazroei</surname> <given-names>A.</given-names></name> <name><surname>Elsarrag</surname> <given-names>E.</given-names></name></person-group> (<year>2015</year>). <article-title>Creating a better healing environment in Qatari healthcare sector: exploring the research agenda for the future</article-title>. <source>Int. J. Sustain. Built. Environ</source>. <volume>4</volume>, <fpage>158</fpage>&#x02013;<lpage>164</lpage>. <pub-id pub-id-type="doi">10.1016/j.ijsbe.2015.03.007</pub-id></citation></ref>
<ref id="B6">
<citation citation-type="journal"><person-group person-group-type="author"><name><surname>Azhar</surname> <given-names>S.</given-names></name> <name><surname>Carlton</surname> <given-names>W. A.</given-names></name> <name><surname>Olsen</surname> <given-names>D.</given-names></name></person-group> (<year>2011</year>). <article-title>Ahmad, I</article-title>. <source>Building information modeling for sustainable design and LEED rating analysis. Autom. Constr</source>. <volume>20</volume>, <fpage>217</fpage>&#x02013;<lpage>224</lpage>. <pub-id pub-id-type="doi">10.1016/j.autcon.2010.09.019</pub-id></citation></ref>
<ref id="B7">
<citation citation-type="journal"><person-group person-group-type="author"><name><surname>Balaras</surname> <given-names>C. A.</given-names></name> <name><surname>Dascalaki</surname> <given-names>E.</given-names></name> <name><surname>Gaglia</surname> <given-names>A.</given-names></name></person-group> (<year>2007</year>). <article-title>HVAC and indoor thermal conditions in hospital operating rooms. <italic>Build</italic></article-title>. <source>Environ.</source> <volume>39</volume>, <fpage>454</fpage>&#x02013;<lpage>470</lpage>. <pub-id pub-id-type="doi">10.1016/j.enbuild.2006.09.004</pub-id></citation></ref>
<ref id="B8">
<citation citation-type="journal"><person-group person-group-type="author"><name><surname>Chen</surname> <given-names>S.</given-names></name> <name><surname>Li</surname> <given-names>N.</given-names></name> <name><surname>Guan</surname> <given-names>J.</given-names></name> <name><surname>Xie</surname> <given-names>Y.</given-names></name> <name><surname>Sun</surname> <given-names>F.</given-names></name> <name><surname>Ni</surname> <given-names>J.</given-names></name></person-group> (<year>2008</year>). <article-title>A statistical method to investigate national energy consumption in the residential building sector of China</article-title>. <source>Energy Build</source> <volume>40</volume>, <fpage>654</fpage>&#x02013;<lpage>665</lpage>. <pub-id pub-id-type="doi">10.1016/j.enbuild.2007.04.022</pub-id></citation></ref>
<ref id="B9">
<citation citation-type="book"><person-group person-group-type="author"><collab>Clima</collab></person-group> (<year>2010</year>). <source>10th REHVA World Congress: May 9-12, 2010</source>. <publisher-loc>Antalya</publisher-loc>: <publisher-name>Clima</publisher-name>.</citation></ref>
<ref id="B10">
<citation citation-type="journal"><person-group person-group-type="author"><name><surname>Del Ferraro</surname> <given-names>S.</given-names></name> <name><surname>Iavicoli</surname> <given-names>S.</given-names></name> <name><surname>Russo</surname> <given-names>S.</given-names></name> <name><surname>Molinaro</surname> <given-names>V.</given-names></name></person-group> (<year>2015</year>). <article-title>A field study on thermal comfort in an Italian hospital considering differences in gender and age</article-title>. <source>Appl. Ergon.</source> <volume>50</volume>, <fpage>177</fpage>&#x02013;<lpage>184</lpage>. <pub-id pub-id-type="doi">10.1016/j.apergo.2015.03.014</pub-id><pub-id pub-id-type="pmid">25959333</pub-id></citation></ref>
<ref id="B11">
<citation citation-type="web"><person-group person-group-type="author"><name><surname>Delisle</surname> <given-names>V.</given-names></name></person-group> (<year>2011</year>). <article-title>Net-zero energy homes: solar photovoltaic electricity scenario analysis based on current and future costs</article-title>, in <source>ASHRAE Conference Montreal</source>, <fpage>1</fpage>&#x02013;<lpage>8</lpage>. Available online at: <ext-link ext-link-type="uri" xlink:href="http://www.nrcan.gc.ca/sites/www.nrcan.gc.ca/files/canmetenergy/files/2011-040.pdf">http://www.nrcan.gc.ca/sites/www.nrcan.gc.ca/files/canmetenergy/files/2011-040.pdf</ext-link></citation></ref>
<ref id="B12">
<citation citation-type="journal"><person-group person-group-type="author"><collab>Dutch governments</collab></person-group>. (<year>2012</year>). <article-title>Nationaal Plan voor het bevorderen van Bijna-EnergieNeutrale Gebouwen (BENG) in Nederland</article-title>.</citation></ref>
<ref id="B13">
<citation citation-type="journal"><person-group person-group-type="author"><collab>EIA</collab></person-group> (<year>2011</year>). <article-title>World energy demand and economic outlook</article-title>. <source>Int. Energy Outlook</source> <volume>484</volume>, <fpage>1</fpage>&#x02013;<lpage>11</lpage>.</citation></ref>
<ref id="B14">
<citation citation-type="journal"><person-group person-group-type="author"><name><surname>Entrop</surname> <given-names>A.</given-names></name> <name><surname>Brouwers</surname> <given-names>H.</given-names></name></person-group> (<year>2019</year>). <article-title>Assessing the sustainability of buildings using a framework of triad approaches</article-title>. <source>J. Build. Apprais</source>. <volume>5</volume>, <fpage>293</fpage>&#x02013;<lpage>310</lpage>. <pub-id pub-id-type="doi">10.1057/jba.2009.36</pub-id></citation></ref>
<ref id="B16">
<citation citation-type="journal"><person-group person-group-type="author"><name><surname>Farooqui</surname> <given-names>S. K.</given-names></name></person-group> (<year>2014</year>). <article-title>Prospects of renewable penetration in the energy mix of Pakistan</article-title>. <source>Renew. Sustain. Energy Rev</source>. <volume>29</volume>, <fpage>693</fpage>&#x02013;<lpage>700</lpage>. <pub-id pub-id-type="doi">10.1016/j.rser.2013.08.083</pub-id></citation></ref>
<ref id="B17">
<citation citation-type="journal"><person-group person-group-type="author"><name><surname>Ferreira</surname> <given-names>J.</given-names></name> <name><surname>Pinheiro</surname> <given-names>M. D.</given-names></name> <name><surname>Brito</surname> <given-names>J. D.</given-names></name></person-group> (<year>2014</year>). <article-title>Portuguese sustainable construction assessment tools benchmarked with BREEAM and LEED: an energy analysis</article-title>. <source>Energy Build</source>. <volume>69</volume>, <fpage>451</fpage>&#x02013;<lpage>463</lpage>. <pub-id pub-id-type="doi">10.1016/j.enbuild.2013.11.039</pub-id></citation></ref>
<ref id="B18">
<citation citation-type="web"><person-group person-group-type="author"><name><surname>Fritjof</surname> <given-names>S.</given-names></name> <name><surname>Asplan Viak</surname> <given-names>A. S.</given-names></name></person-group> (<year>2014</year>). <source>SHC Task 47 Renovation of Non- Residential Buildings Towards Sustainable Standards</source>. Avaialbel online at: <ext-link ext-link-type="uri" xlink:href="https://task47.iea/shc.org/Data/Sites/1/publications/IEA/SHC/Task47/Highlights/2014.pdf">https://task47.iea/shc.org/Data/Sites/1/publications/IEA/SHC/Task47/Highlights/2014.pdf</ext-link> (assessed December 10, 2019).</citation></ref>
<ref id="B19">
<citation citation-type="journal"><person-group person-group-type="author"><name><surname>Giyler</surname> <given-names>T.</given-names></name> <name><surname>Lilienpthal</surname> <given-names>P.</given-names></name></person-group> (<year>2005</year>). <source>Using HOMER Software, NREL&#x00027;s Micro Power Optimization Model, to Explore the Role of Gen-Sets in Small Solar Power Systems Case Study: Pakistan</source>. Technical Report NREL/TP-710-36774.</citation></ref>
<ref id="B20">
<citation citation-type="journal"><person-group person-group-type="author"><name><surname>Golbazi</surname> <given-names>M.</given-names></name> <name><surname>Aktas</surname> <given-names>C. B.</given-names></name></person-group> (<year>2016</year>). <article-title>Analysis of credits earned by LEED healthcare certified facilities</article-title>. <source>Proc. Eng.</source> <volume>145</volume>, <fpage>203</fpage>&#x02013;<lpage>210</lpage>. <pub-id pub-id-type="doi">10.1016/j.proeng.2016.04.062</pub-id></citation></ref>
<ref id="B21">
<citation citation-type="journal"><person-group person-group-type="author"><name><surname>Han</surname> <given-names>J.</given-names></name> <name><surname>Zhang</surname> <given-names>G.</given-names></name> <name><surname>Zhang</surname> <given-names>Q.</given-names></name> <name><surname>Zhang</surname> <given-names>J.</given-names></name> <name><surname>Liu</surname> <given-names>J.</given-names></name> <name><surname>Tian</surname> <given-names>L.</given-names></name> <etal/></person-group>. (<year>2007</year>). <article-title>Field study on occupants&#x00027; thermal comfort and residential thermal environment in a hot-humid climate of China</article-title>. <source>Build. Environ.</source> <volume>42</volume>, <fpage>4043</fpage>&#x02013;<lpage>4050</lpage>. <pub-id pub-id-type="doi">10.1016/j.buildenv.2006.06.028</pub-id></citation></ref>
<ref id="B22">
<citation citation-type="journal"><person-group person-group-type="author"><name><surname>Haves</surname> <given-names>P.</given-names></name></person-group> (<year>2019</year>). <article-title>A study on energy savings and measure cost effectiveness of existing building commissioning</article-title>.</citation></ref>
<ref id="B23">
<citation citation-type="journal"><person-group person-group-type="author"><collab>J, S.</collab></person-group> (<year>2013</year>). <article-title>Passive solar building design</article-title>. <source>J. Novel Appl. Sci.</source></citation></ref>
<ref id="B24">
<citation citation-type="journal"><person-group person-group-type="author"><name><surname>Jaman</surname> <given-names>M. T.</given-names></name> <name><surname>Rahman</surname> <given-names>M. M.</given-names></name> <name><surname>Rahman</surname> <given-names>A. M.</given-names></name> <name><surname>Khulna</surname> <given-names>B.</given-names></name></person-group> (<year>2010</year>). <article-title>Design of a direct gain passive solar heating system</article-title>, in <source>Paper Presented At The Proceedings Of 2010 International Conference on Industrial Engineering and Operations Management</source> (Dhaka).</citation></ref>
<ref id="B25">
<citation citation-type="journal"><person-group person-group-type="author"><name><surname>Ji</surname> <given-names>R.</given-names></name> <name><surname>Zhang</surname> <given-names>Z.</given-names></name> <name><surname>He</surname> <given-names>Y.</given-names></name> <name><surname>Liu</surname> <given-names>J.</given-names></name> <name><surname>Qu</surname> <given-names>S.</given-names></name></person-group> (<year>2017</year>). <article-title>Simulating the effects of anchors on the thermal performance of building insulation systems</article-title>. <source>Energy Build.</source> <volume>140</volume>, <fpage>501</fpage>&#x02013;<lpage>507</lpage>. <pub-id pub-id-type="doi">10.1016/j.enbuild.2016.12.036</pub-id></citation></ref>
<ref id="B26">
<citation citation-type="journal"><person-group person-group-type="author"><name><surname>Jian</surname> <given-names>Z.</given-names></name> <name><surname>Pullen</surname> <given-names>S.</given-names></name> <name><surname>Rameezdeen</surname> <given-names>R.</given-names></name> <name><surname>Bennetts</surname> <given-names>H.</given-names></name> <name><surname>Wang</surname> <given-names>Y.</given-names></name> <name><surname>Mao</surname> <given-names>G.</given-names></name> <etal/></person-group>. (<year>2017</year>). <article-title>Green building evaluation from a life-cycle perspective in Australia: a critical review</article-title>. <source>Renew. Sustain. Energy Rev</source>. <volume>70</volume>, <fpage>358</fpage>&#x02013;<lpage>368</lpage>. <pub-id pub-id-type="doi">10.1016/j.rser.2016.11.251</pub-id></citation></ref>
<ref id="B27">
<citation citation-type="book"><person-group person-group-type="author"><name><surname>Khalid</surname> <given-names>W.</given-names></name> <name><surname>Salim</surname> <given-names>S. A. Z. S.</given-names></name> <name><surname>Rijal</surname> <given-names>H. B.</given-names></name> <name><surname>Yakub</surname> <given-names>F.</given-names></name></person-group> (<year>2017</year>). <article-title>Thermal comfort in hospitals in hot and humid climates: a literature review</article-title>, in <source>Proceedings of the 1st Green Environmental Energy and Building Science (GEEBS) International Conference</source> (<publisher-loc>Johor Bahru</publisher-loc>), <fpage>16</fpage>&#x02013;<lpage>17</lpage>.</citation></ref>
<ref id="B28">
<citation citation-type="journal"><person-group person-group-type="author"><name><surname>Khan</surname> <given-names>H. A.</given-names></name> <name><surname>Pervaiz</surname> <given-names>S.</given-names></name></person-group> (<year>2013</year>). <article-title>Technological review on solar PV in Pakistan: scope, practices and recommendations for optimized system design</article-title>. <source>Renew. Sustain. Energy Rev</source>. <volume>23</volume>, <fpage>147</fpage>&#x02013;<lpage>154</lpage>. <pub-id pub-id-type="doi">10.1016/j.rser.2013.02.031</pub-id></citation></ref>
<ref id="B29">
<citation citation-type="journal"><person-group person-group-type="author"><name><surname>Kneifel</surname> <given-names>J.</given-names></name> <name><surname>Webb</surname> <given-names>D.</given-names></name></person-group> (<year>2018</year>). <article-title>Predicting energy performance of a net-zero energy building: a statistical approach</article-title>. <source>Appl. Energy</source>. <volume>178</volume>, <fpage>468</fpage>&#x02013;<lpage>483</lpage>. <pub-id pub-id-type="doi">10.1016/j.apenergy.2016.06.013</pub-id><pub-id pub-id-type="pmid">27956756</pub-id></citation></ref>
<ref id="B30">
<citation citation-type="journal"><person-group person-group-type="author"><name><surname>Lenoir</surname> <given-names>A.</given-names></name> <name><surname>Thellier</surname> <given-names>F.</given-names></name> <name><surname>Garde</surname> <given-names>F.</given-names></name></person-group> (<year>2011</year>). <article-title>Towards net zero energy buildings in hot climate, part 2: experimental feedback</article-title>, in <source>ASHRAE Transactions</source>, <volume>Vol. 117</volume>.</citation></ref>
<ref id="B31">
<citation citation-type="journal"><person-group person-group-type="author"><name><surname>Liu</surname> <given-names>Y.</given-names></name> <name><surname>Guo</surname> <given-names>X.</given-names></name> <name><surname>Hu</surname> <given-names>F.</given-names></name></person-group> (<year>2014</year>). <article-title>Cost-benefit analysis on green building energy efficiency technology application: a case in China</article-title>. <source>Energy Build</source>. <volume>82</volume>, <fpage>37</fpage>&#x02013;<lpage>46</lpage>. <pub-id pub-id-type="doi">10.1016/j.enbuild.2014.07.008</pub-id></citation></ref>
<ref id="B32">
<citation citation-type="journal"><person-group person-group-type="author"><name><surname>Meegoda</surname> <given-names>J.</given-names></name> <name><surname>Hsieh</surname> <given-names>H. N.</given-names></name> <name><surname>Rodriguez</surname> <given-names>P.</given-names></name> <name><surname>Jawidzik</surname> <given-names>J.</given-names></name></person-group> (<year>2012</year>). <article-title>Sustainable community sanitation for a rural hospital in Haiti</article-title>. <source>Sustainability</source> <volume>4</volume>, <fpage>3362</fpage>&#x02013;<lpage>3376</lpage>. <pub-id pub-id-type="doi">10.3390/su4123362</pub-id></citation></ref>
<ref id="B33">
<citation citation-type="web"><person-group person-group-type="author"><collab>Ministerie van Volkshuisvesting</collab></person-group>, <source>Ruimtelijke Ordening en Milieubeheer.</source> (<year>2010</year>). Available online at: <ext-link ext-link-type="uri" xlink:href="https://www.parlement.com/id/vhnnmt7hw7e7/ministerie_van_volkshuisvesting">https://www.parlement.com/id/vhnnmt7hw7e7/ministerie_van_volkshuisvesting</ext-link> (accessed November 20, 2020).</citation></ref>
<ref id="B34">
<citation citation-type="book"><person-group person-group-type="author"><collab>Ministry of Planning and Development Government of Pakistan</collab></person-group>. (<year>2011</year>). <article-title>Pakistan Integrated Energy Model (Pak-IEM)</article-title>, in <source>Policy Analysis Report Volume II</source> (<publisher-loc>Islamabad</publisher-loc>).</citation></ref>
<ref id="B35">
<citation citation-type="journal"><person-group person-group-type="author"><name><surname>Pourshaghaghy</surname> <given-names>A.</given-names></name> <name><surname>Omidvari</surname> <given-names>M.</given-names></name></person-group> (<year>2012</year>). <article-title>Examination of thermal comfort in a hospital using PMV-PPD model</article-title>. <source>Appl. Ergon.</source> <volume>43</volume>, <fpage>1089</fpage>&#x02013;<lpage>1095</lpage>. <pub-id pub-id-type="doi">10.1016/j.apergo.2012.03.010</pub-id><pub-id pub-id-type="pmid">22575492</pub-id></citation></ref>
<ref id="B36">
<citation citation-type="journal"><person-group person-group-type="author"><name><surname>Pradinuk</surname> <given-names>R.</given-names></name></person-group> (<year>2009</year>). <article-title>Incentivizing the Daylit Hospital: the green guide for health care approach</article-title>. <source>HERD Health Environ. Res. Des. J</source>. <volume>2</volume>, <fpage>92</fpage>&#x02013;<lpage>112</lpage>. <pub-id pub-id-type="doi">10.1177/193758670900200408</pub-id><pub-id pub-id-type="pmid">21165844</pub-id></citation></ref>
<ref id="B37">
<citation citation-type="journal"><person-group person-group-type="author"><name><surname>Rafique</surname> <given-names>M. M.</given-names></name> <name><surname>Rehmanb</surname> <given-names>S.</given-names></name></person-group> (<year>2017</year>). <article-title>National energy scenario of Pakistan: current status, future alternatives and institutional infrastructure: an overview</article-title>. <source>Renew. Sustain. Energy Rev</source>. <volume>69</volume>, <fpage>156</fpage>&#x02013;<lpage>167</lpage>. <pub-id pub-id-type="doi">10.1016/j.rser.2016.11.057</pub-id></citation></ref>
<ref id="B67">
<citation citation-type="book"><person-group person-group-type="author"><collab>REHVA</collab></person-group>. (<year>2010</year>). <article-title>EU, Directive 2010/31/EU of the European Parliament and of the Council &#x0201C;REHVA EPBD recast, of 19 May 2010 on the energy performance of buildings,&#x0201D;</article-title> in <source>Official Journal of the European Union</source>.</citation>
</ref>
<ref id="B38">
<citation citation-type="journal"><person-group person-group-type="author"><name><surname>Raheem</surname> <given-names>S. A.</given-names></name> <name><surname>Abbasi</surname> <given-names>A.</given-names></name> <name><surname>Memon</surname> <given-names>A.</given-names></name> <name><surname>Samo</surname> <given-names>S. R.</given-names></name> <name><surname>Taufiq-Yap</surname> <given-names>Y. H.</given-names></name> <name><surname>Danquah</surname> <given-names>M. K.</given-names></name> <etal/></person-group>. (<year>2016</year>). <article-title>Renewable energy deployment to combat energy crisis in Pakistan,|| Energy</article-title>. <source>Sustain. Soc</source>. <volume>6</volume>:<fpage>16</fpage>. <pub-id pub-id-type="doi">10.1186/s13705-016-0082-z</pub-id></citation></ref>
<ref id="B39">
<citation citation-type="journal"><person-group person-group-type="author"><name><surname>Salma</surname> <given-names>S.</given-names></name> <name><surname>Rehman</surname> <given-names>S.</given-names></name> <name><surname>Shah</surname> <given-names>M. A</given-names></name></person-group>. (<year>2012</year>). <article-title>Pakistan Journal of Meteorology:Rainfall Trends in Different Climate Zones of <italic>Pakistan</italic></article-title>. <source>Pakistan J. Meteorol.</source> <volume>9</volume>:<fpage>39</fpage>.</citation></ref>
<ref id="B40">
<citation citation-type="journal"><person-group person-group-type="author"><name><surname>Sandeep</surname> <given-names>K.</given-names></name></person-group> (<year>2015</year>). <source>Cooling Load Equation for Multistory Office building</source>. Thermal engineering.</citation></ref>
<ref id="B41">
<citation citation-type="journal"><person-group person-group-type="author"><name><surname>Sattayakorn</surname> <given-names>S.</given-names></name> <name><surname>Ichinose</surname> <given-names>M.</given-names></name> <name><surname>Sasaki</surname> <given-names>R.</given-names></name></person-group> (<year>2017</year>). <article-title>Clarifying thermal comfort of healthcare occupants in tropical region: a case of indoor environment in Thai hospitals</article-title>. <source>Energy Build.</source> <volume>149</volume>, <fpage>45</fpage>&#x02013;<lpage>57</lpage>. <pub-id pub-id-type="doi">10.1016/j.enbuild.2017.05.025</pub-id></citation></ref>
<ref id="B42">
<citation citation-type="journal"><person-group person-group-type="author"><name><surname>Schweber</surname> <given-names>L.</given-names></name></person-group> (<year>2013</year>). <article-title>The effect of BREEAM on clients and construction professionals</article-title>. <source>Build. Res. Inf.</source> <volume>41</volume>, <fpage>129</fpage>&#x02013;<lpage>145</lpage>. <pub-id pub-id-type="doi">10.1080/09613218.2013.768495</pub-id></citation></ref>
<ref id="B43">
<citation citation-type="journal"><person-group person-group-type="author"><name><surname>Schweber</surname> <given-names>L.</given-names></name> <name><surname>Haroglu</surname> <given-names>H.</given-names></name></person-group> (<year>2014</year>). <article-title>Comparing the fit between BREEAM assessment and design processes</article-title>. <source>Build. Res. Inf</source>. <volume>42</volume>, <fpage>300</fpage>&#x02013;<lpage>317</lpage>. <pub-id pub-id-type="doi">10.1080/09613218.2014.889490</pub-id></citation></ref>
<ref id="B44">
<citation citation-type="journal"><person-group person-group-type="author"><name><surname>Sen</surname> <given-names>R.</given-names></name> <name><surname>Bhattacharyya</surname> <given-names>S.</given-names></name></person-group> (<year>2014</year>). <article-title>Off-grid electricity generation with renewable energy technologies in India: an application of HOMER</article-title>. <source>Renew. Energy</source> <volume>62</volume>, <fpage>388</fpage>&#x02013;<lpage>453</lpage>. <pub-id pub-id-type="doi">10.1016/j.renene.2013.07.028</pub-id></citation></ref>
<ref id="B45">
<citation citation-type="journal"><person-group person-group-type="author"><name><surname>Sherif</surname> <given-names>A. H.</given-names></name></person-group> (<year>1999</year>). <article-title>Hospitals of developing countries: design and construction economics</article-title>. <source>J. Archit. Eng.</source> <volume>5</volume>, <fpage>74</fpage>&#x02013;<lpage>81</lpage>. <pub-id pub-id-type="doi">10.1061/(ASCE)1076-0431(1999)5:3(74)</pub-id></citation></ref>
<ref id="B46">
<citation citation-type="journal"><person-group person-group-type="author"><name><surname>Shu</surname> <given-names>Y.</given-names></name> <name><surname>Ito</surname> <given-names>K.</given-names></name> <name><surname>Yokoyama</surname> <given-names>R.</given-names></name></person-group> (<year>2007</year>). <article-title>Sensitivity analysis in structure optimization of energy supply systems for a hospital</article-title>. <source>Energy Conv. Manag.</source> <volume>48</volume>, <fpage>2836</fpage>&#x02013;<lpage>2843</lpage>. <pub-id pub-id-type="doi">10.1016/j.enconman.2007.06.045</pub-id></citation></ref>
<ref id="B47">
<citation citation-type="journal"><person-group person-group-type="author"><name><surname>Si</surname> <given-names>B.</given-names></name> <name><surname>Tian</surname> <given-names>Z.</given-names></name> <name><surname>Chen</surname> <given-names>W.</given-names></name> <name><surname>Jin</surname> <given-names>X.</given-names></name> <name><surname>Zhou</surname> <given-names>X.</given-names></name> <name><surname>Shi</surname> <given-names>X.</given-names></name></person-group> (<year>2018</year>). <article-title>Performance assessment of algorithms for building energy optimization problems with different properties</article-title>. <source>Sustainability</source> <volume>11</volume>:<fpage>18</fpage>. <pub-id pub-id-type="doi">10.3390/su11010018</pub-id></citation></ref>
<ref id="B48">
<citation citation-type="journal"><person-group person-group-type="author"><name><surname>Singh</surname> <given-names>A.</given-names></name> <name><surname>Baredar</surname> <given-names>P.</given-names></name> <name><surname>Gupta</surname> <given-names>B.</given-names></name></person-group> (<year>2015</year>). <article-title>Computational simulation &#x00026; optimization of a solar, fuel cell and biomass hybrid energy system using HOMER Pro software</article-title>. <source>Proc. Eng.</source> <volume>127</volume>, <fpage>743</fpage>&#x02013;<lpage>750</lpage>. <pub-id pub-id-type="doi">10.1016/j.proeng.2015.11.408</pub-id></citation></ref>
<ref id="B49">
<citation citation-type="journal"><person-group person-group-type="author"><name><surname>Skoog</surname> <given-names>J.</given-names></name> <name><surname>Fransson</surname> <given-names>N.</given-names></name> <name><surname>Jagemar</surname> <given-names>L.</given-names></name></person-group> (<year>2005</year>). <article-title>Thermal environment in Swedish hospitals: summer and winter measurements</article-title>. <source>Energy Build.</source> <volume>37</volume>, <fpage>872</fpage>&#x02013;<lpage>877</lpage>. <pub-id pub-id-type="doi">10.1016/j.enbuild.2004.11.003</pub-id></citation></ref>
<ref id="B50">
<citation citation-type="web"><person-group person-group-type="author"><collab>Solar resource maps of Pakistan.</collab></person-group> (<year>2019</year>). Available online at: <ext-link ext-link-type="uri" xlink:href="https://solargis.com/maps-and-gis-data/download/Pakistan">https://solargis.com/maps-and-gis-data/download/Pakistan</ext-link> (accessed March 11, 2021).</citation></ref>
<ref id="B51">
<citation citation-type="journal"><person-group person-group-type="author"><name><surname>Tahir Masood</surname> <given-names>M.</given-names></name> <name><surname>Shah</surname> <given-names>F.</given-names></name></person-group> (<year>2012</year>). <article-title>Dilemma of third world countries &#x02013; problems facing pakistan energy crisis a case-in-point</article-title>. <source>Int. J. Bus. Manag.</source> <volume>7</volume>:<fpage>231</fpage>. <pub-id pub-id-type="doi">10.5539/ijbm.v7n5p231</pub-id></citation></ref>
<ref id="B52">
<citation citation-type="journal"><person-group person-group-type="author"><name><surname>Taneer</surname> <given-names>T.</given-names></name></person-group> (<year>2018</year>). <article-title>Energy and exergy analyze of PEM fuel cell: a case study of modeling and simulations</article-title>. <source>Energy</source> <volume>143</volume>, <fpage>284</fpage>&#x02013;<lpage>294</lpage>. <pub-id pub-id-type="doi">10.1016/j.energy.2017.10.102</pub-id></citation></ref>
<ref id="B53">
<citation citation-type="journal"><person-group person-group-type="author"><name><surname>Taneer</surname> <given-names>T.</given-names></name> <name><surname>Naqvi</surname> <given-names>S. A. H.</given-names></name> <name><surname>Ozkaymak</surname> <given-names>M.</given-names></name></person-group> (<year>2018</year>). <article-title>Techno-economic analysis of a more efficient hydrogen generation system prototype: a case study of PEM electrolyzer with Cr-C coated SS304 bipolar plates</article-title>. <source>Fuel Cells</source>. <volume>19</volume>, <fpage>19</fpage>&#x02013;<lpage>26</lpage>. <pub-id pub-id-type="doi">10.1002/fuce.201700225</pub-id></citation></ref>
<ref id="B54">
<citation citation-type="journal"><person-group person-group-type="author"><name><surname>Taneer</surname> <given-names>T.</given-names></name> <name><surname>Sivrioglu</surname> <given-names>M.</given-names></name></person-group> (<year>2017</year>). <article-title>A techno-economic &#x00026; cost analysis of a turbine power plant: a case study for sugar plant</article-title>. <source>Renew. Sustain. Energy Rev.</source> <volume>78</volume>, <fpage>722</fpage>&#x02013;<lpage>730</lpage>. <pub-id pub-id-type="doi">10.1016/j.rser.2017.04.104</pub-id></citation></ref>
<ref id="B55">
<citation citation-type="journal"><person-group person-group-type="author"><name><surname>Taner</surname> <given-names>T.</given-names></name></person-group> (<year>2015b</year>). <article-title>Optimisation processes of energy efficiency for a drying plant: a case of study for Turkey</article-title>. <source>Appl. Therm. Eng.</source> <volume>80</volume>, <fpage>247</fpage>&#x02013;<lpage>260</lpage>. <pub-id pub-id-type="doi">10.1016/j.applthermaleng.2015.01.076</pub-id></citation></ref>
<ref id="B56">
<citation citation-type="journal"><person-group person-group-type="author"><name><surname>Taner</surname> <given-names>T.</given-names></name></person-group> (<year>2015a</year>). <article-title>Alternative energy of the future: a technical note of PEM fuel cell water management</article-title>. <source>J. Fundament. Renew. Energy Appl.</source> <volume>5</volume>:<fpage>3</fpage>. <pub-id pub-id-type="doi">10.4172/2090-4541.1000163</pub-id></citation></ref>
<ref id="B57">
<citation citation-type="journal"><person-group person-group-type="author"><name><surname>Vanhoutteghem</surname> <given-names>L.</given-names></name> <name><surname>Skarning</surname> <given-names>G. C. J.</given-names></name> <name><surname>Hviid</surname> <given-names>C. A.</given-names></name> <name><surname>Svendsen</surname> <given-names>S.</given-names></name></person-group> (<year>2015</year>). <article-title>Impact of fa&#x000E7;ade window design on energy, day lighting and thermal comfort in nearly zero-energy houses</article-title>. <source>Energy Build</source>. <volume>102</volume>, <fpage>149</fpage>&#x02013;<lpage>156</lpage>. <pub-id pub-id-type="doi">10.1016/j.enbuild.2015.05.018</pub-id></citation></ref>
<ref id="B58">
<citation citation-type="journal"><person-group person-group-type="author"><name><surname>Wang</surname> <given-names>Q.</given-names></name> <name><surname>Zhou</surname> <given-names>P.</given-names></name> <name><surname>Zhao</surname> <given-names>Z.</given-names></name> <name><surname>Shen</surname> <given-names>N.</given-names></name></person-group> (<year>2014</year>). <article-title>Energy efficiency and energy saving potential in China: a directional meta-frontier DEA approach</article-title>. <source>Sustainability</source> <volume>6</volume>, <fpage>5476</fpage>&#x02013;<lpage>5492</lpage>. <pub-id pub-id-type="doi">10.3390/su6085476</pub-id></citation></ref>
<ref id="B59">
<citation citation-type="journal"><person-group person-group-type="author"><name><surname>Wu</surname> <given-names>P.</given-names></name> <name><surname>Song</surname> <given-names>Y.</given-names></name> <name><surname>Shou</surname> <given-names>W.</given-names></name> <name><surname>Chi</surname> <given-names>H.</given-names></name> <name><surname>Chong</surname> <given-names>H. Y.</given-names></name></person-group> (<year>2017</year>). <article-title>Sutrisna, M. A comprehensive analysis of the credits obtained by LEED 2009 certified green buildings</article-title>. <source>Renew. Sustain. Energy Rev</source>. <volume>68</volume>, <fpage>370</fpage>&#x02013;<lpage>379</lpage>. <pub-id pub-id-type="doi">10.1016/j.rser.2016.10.007</pub-id></citation></ref>
<ref id="B60">
<citation citation-type="journal"><person-group person-group-type="author"><name><surname>Wu</surname> <given-names>W.</given-names></name> <name><surname>Skye</surname> <given-names>H. M.</given-names></name></person-group> (<year>2018</year>). <article-title>Domanski PA. Selecting HVAC systems to achieve comfortable and costeffective residential net zero energy buildings</article-title>. <source>Appl. Energy</source> <volume>212</volume>, <fpage>577</fpage>&#x02013;<lpage>591</lpage>. <pub-id pub-id-type="doi">10.1016/j.apenergy.2017.12.046</pub-id></citation></ref>
<ref id="B61">
<citation citation-type="journal"><person-group person-group-type="author"><name><surname>Yau</surname> <given-names>Y. H.</given-names></name> <name><surname>Chew</surname> <given-names>B. T.</given-names></name></person-group> (<year>2009</year>). <article-title>Thermal comfort study of hospital workers in Malaysia</article-title>. <source>Indoor Air</source> <volume>19</volume>, <fpage>500</fpage>&#x02013;<lpage>510</lpage>. <pub-id pub-id-type="doi">10.1111/j.1600-0668.2009.00617.x</pub-id></citation>
</ref>
<ref id="B62">
<citation citation-type="journal"><person-group person-group-type="author"><name><surname>Younger</surname> <given-names>M.</given-names></name> <name><surname>Morrow-Almeida</surname> <given-names>H. R.</given-names></name> <name><surname>Vindigni</surname> <given-names>S. M.</given-names></name> <name><surname>Dannenberg</surname> <given-names>A. L.</given-names></name></person-group> (<year>2008</year>). <article-title>The built environment, climate change, and health: opportunities for co-benefits</article-title>. <source>Am. J. Prev. Med</source>. <volume>35</volume>, <fpage>517</fpage>&#x02013;<lpage>526</lpage>. <pub-id pub-id-type="doi">10.1016/j.amepre.2008.08.017</pub-id></citation>
</ref>
<ref id="B63">
<citation citation-type="journal"><person-group person-group-type="author"><name><surname>Zhang</surname> <given-names>Y.</given-names></name> <name><surname>Wang</surname> <given-names>J.</given-names></name> <name><surname>Hu</surname> <given-names>F.</given-names></name> <name><surname>Wang</surname> <given-names>Y.</given-names></name></person-group> (<year>2017</year>). <article-title>Comparison of evaluation standards for green building in China, Britain, United States</article-title>. <source>Renew. Sustain. Energy Rev.</source> <volume>68</volume> (<issue>Pt 1</issue>), <fpage>262</fpage>&#x02013;<lpage>271</lpage>. <pub-id pub-id-type="doi">10.1016/j.rser.2016.09.139</pub-id></citation></ref>
<ref id="B64">
<citation citation-type="journal"><person-group person-group-type="author"><name><surname>Zhou</surname> <given-names>Z.</given-names></name> <name><surname>Feng</surname> <given-names>L.</given-names></name> <name><surname>Zhang</surname> <given-names>S.</given-names></name> <name><surname>Wang</surname> <given-names>C.</given-names></name> <name><surname>Chen</surname> <given-names>G.</given-names></name> <name><surname>Du</surname> <given-names>T.</given-names></name> <etal/></person-group>. (<year>2016</year>). <article-title>The operational performance of &#x0201C;net zero energy building&#x0201D;: a study in China</article-title>. <source>Appl. Energy</source> <volume>177</volume>, <fpage>716</fpage>&#x02013;<lpage>728</lpage>. <pub-id pub-id-type="doi">10.1016/j.apenergy.2016.05.093</pub-id></citation></ref>
<ref id="B65">
<citation citation-type="web"><person-group person-group-type="author"><collab>Zurghulpatias.</collab></person-group> (<year>2015a</year>). <source>Overzicht Algemene Ziekenhuizen in Nederland</source>. Available online at: <ext-link ext-link-type="uri" xlink:href="http://www.zorghulpatlas.nl/zorginnederland/ziekenhuiszorg/algemeneenacademische/ziekenhuizen/overzicht/algemeneziekenhuizen/innederland/">http://www.zorghulpatlas.nl/zorginnederland/ziekenhuiszorg/algemeneenacademische/ziekenhuizen/overzicht/algemeneziekenhuizen/innederland/</ext-link> (accessed December 17, 2017).</citation></ref>
<ref id="B66">
<citation citation-type="web"><person-group person-group-type="author"><collab>Zurghulpatias.</collab></person-group> (<year>2015b</year>). <source>Academische Ziekenhuizen in Nederland</source>. Available online at: <ext-link ext-link-type="uri" xlink:href="http://www.zorghulpatlas.nl/zorg/innederland/ziekenhuiszorg/algemene/enacademische/ziekenhuizen/academischeziekenhuizen/in/nederland/">http://www.zorghulpatlas.nl/zorg/innederland/ziekenhuiszorg/algemene/enacademische/ziekenhuizen/academischeziekenhuizen/in/nederland/</ext-link> (accessed December 17, 2018).</citation></ref>
</ref-list>
<sec id="s13">
<title>Nomenclature</title>
<table-wrap position="float">
<table frame="hsides" rules="groups">
<tbody>
<tr>
<td valign="top" align="left">Q<sub>s</sub></td>
<td valign="top" align="left">Sensible heat transfer</td>
<td valign="top" align="left">kW</td>
</tr>
<tr>
<td valign="top" align="left">Ql</td>
<td valign="top" align="left">Latent heat transfer</td>
<td valign="top" align="left">kW</td>
</tr>
<tr>
<td valign="top" align="left">Q<sub>roof</sub></td>
<td valign="top" align="left">Heat transfer rate by roof</td>
<td valign="top" align="left">kW</td>
</tr>
<tr>
<td valign="top" align="left">Qg</td>
<td valign="top" align="left">Heat transfer rate by glass</td>
<td valign="top" align="left">kW</td>
</tr>
<tr>
<td valign="top" align="left">Q<sub>wall</sub></td>
<td valign="top" align="left">Heat transfer rate by walls</td>
<td valign="top" align="left">kW</td>
</tr>
<tr>
<td valign="top" align="left">M<sub>infiltration</sub></td>
<td valign="top" align="left">Heat Transfer due to infiltration</td>
<td valign="top" align="left">kW</td>
</tr>
<tr>
<td valign="top" align="left">P</td>
<td valign="top" align="left">Power provided per unit area for lightning</td>
<td/>
</tr>
<tr>
<td valign="top" align="left">W<sub>i</sub></td>
<td valign="top" align="left">Inside specific humidity</td>
<td valign="top" align="left">g/Kg</td>
</tr>
<tr>
<td valign="top" align="left">Wo</td>
<td valign="top" align="left">Outside specific humidity</td>
<td valign="top" align="left">g/Kg</td>
</tr>
<tr>
<td valign="top" align="left">NZEB</td>
<td valign="top" align="left">Net Zero Energy Building</td>
<td valign="top" align="left">&#x02013;</td>
</tr>
<tr>
<td valign="top" align="left">NZE</td>
<td valign="top" align="left">Net Zero Energy</td>
<td valign="top" align="left">&#x02013;</td>
</tr>
<tr>
<td valign="top" align="left">RE</td>
<td valign="top" align="left">Renewable energy</td>
<td valign="top" align="left">&#x02013;</td>
</tr>
<tr>
<td valign="top" align="left">LCC</td>
<td valign="top" align="left">Life cycle cost</td>
<td valign="top" align="left">&#x02013;</td>
</tr>
<tr>
<td valign="top" align="left">COE</td>
<td valign="top" align="left">Cost of Electricity</td>
<td valign="top" align="left">&#x02013;</td>
</tr>
<tr>
<td valign="top" align="left">NPC</td>
<td valign="top" align="left">Net Present Cost</td>
<td valign="top" align="left">&#x02013;</td>
</tr>
<tr>
<td valign="top" align="left"><bold>Subscripts</bold></td>
<td/>
<td/>
</tr>
<tr>
<td valign="top" align="left">S</td>
<td valign="top" align="left">Sensible</td>
<td valign="top" align="left">&#x02013;</td>
</tr>
<tr>
<td valign="top" align="left">L</td>
<td valign="top" align="left">Latent</td>
<td valign="top" align="left">&#x02013;</td>
</tr>
<tr>
<td valign="top" align="left">e</td>
<td valign="top" align="left">Exit</td>
<td valign="top" align="left">&#x02013;</td>
</tr>
</tbody>
</table>
</table-wrap>